$ 296.70
input | |
type of the power supply network | 1-phase AC |
supply voltage at AC | Automatic range selection |
supply voltage | 120 V/230 V |
input voltage 1 at AC | 85 … 132 V |
input voltage 2 at AC | 176 … 264 V |
wide range input | No |
overvoltage overload capability | 2.3 × Vin rated, 1.3 ms |
buffering time for rated value of the output current in the event of power failure minimum |
20 ms |
operating condition of the mains buffering | at Vin = 93/187 V |
line frequency | 50/60 Hz |
line frequency | 47 … 63 Hz |
input current | |
● at rated input voltage 120 V | 1.2 A |
● at rated input voltage 230 V | 0.67 A |
current limitation of inrush current at 25 °C maximum | 13 A |
duration of inrush current limiting at 25 °C | |
● maximum | 3 ms |
I2t value maximum | 0.5 A²·s |
fuse protection type | T 3,15 A/250 V (not accessible) |
fuse protection type in the feeder | Recommended miniature circuit breaker: 16 A characteristic B or 10 A characteristic C |
output | |
voltage curve at output | Controlled, isolated DC voltage |
output voltage at DC rated value | 24 V |
output voltage | |
● at output 1 at DC rated value | 24 V |
output voltage adjustable | No; – |
relative overall tolerance of the voltage | 3 % |
relative control precision of the output voltage | |
● on slow fluctuation of input voltage | 0.1 % |
● on slow fluctuation of ohm loading | 0.2 % |
residual ripple | |
● maximum | 150 mV |
voltage peak | |
● maximum | 240 mV |
display version for normal operation | Green LED for 24 V OK |
behavior of the output voltage when switching on | No overshoot of Vout (soft start) |
response delay maximum | 6 s; 2 s at 230 V, 6 s at 120 V |
voltage increase time of the output voltage | |
● typical | 10 ms |
output current | |
● rated value | 2.5 A |
● rated range | 0 … 2.5 A |
supplied active power typical | 60 W |
short-term overload current | |
● on short-circuiting during the start-up typical | 6 A |
● at short-circuit during operation typical | 6 A |
duration of overloading capability for excess current | |
● on short-circuiting during the start-up | 100 ms |
● at short-circuit during operation | 100 ms |
bridging of equipment | Yes |
number of parallel-switched equipment resources for increasing the power |
2 |
efficiency | |
efficiency in percent | 83 % |
power loss [W] | |
● at rated output voltage for rated value of the output current typical |
12 W |
closed-loop control | |
relative control precision of the output voltage with rapid fluctuation of the input voltage by +/- 15% typical |
0.3 % |
relative control precision of the output voltage load step of resistive load 50/100/50 % typical |
3 % |
setting time | |
● load step 50 to 100% typical | 5 ms |
● load step 100 to 50% typical | 5 ms |
setting time | |
● maximum | 5 ms |
protection and monitoring | |
design of the overvoltage protection | < 33 V |
property of the output short-circuit proof | Yes |
design of short-circuit protection | Constant current characteristic |
● typical | 2.65 A |
enduring short circuit current RMS value | |
● typical | 2.7 A |
safety | |
galvanic isolation between input and output | Yes |
galvanic isolation | Safety extra-low output voltage Uout acc. to EN 60950-1 and EN 50178 |
operating resource protection class | Class I |
leakage current | |
● maximum | 3.5 mA |
protection class IP | IP20 |
EMC | |
standard | |
● for emitted interference | EN 55022 Class B |
● for mains harmonics limitation | not applicable |
● for interference immunity | EN 61000-6-2 |
standards, specifications, approvals | |
certificate of suitability | |
● CE marking | Yes |
● UKCA marking | Yes |
MTBF at 40 °C | 1 492 537 h |
ambient conditions | |
ambient temperature | |
● in horizontal mounting position during operation | 0 … 60 °C; with natural convection |
● during transport | -40 … +85 |
● during storage | -40 … +85 |
installation altitude at height above sea level maximum | 6 000 m |
ambient condition relating to ambient temperature – air pressure – installation altitude |
In case of operation at altitudes of 2000 – 6000 m above sea level: Output power derating of -7.5 %/1000 m or reduction of the ambient temperature by 5 K/1000 m |
relative humidity with condensation according to IEC 60068-2- 38 maximum |
100 %; RH incl. condensation/frost (no commissioning if condensation is present), horizontal installation |
chemical resistance to commercially available cooling lubricants | Yes; incl. diesel and oil droplets in the air |
resistance to biologically active substances conformity according to EN 60721-3-3 |
Yes; Class 3B2 mold, fungal, sponge spores (except fauna); class 3B3 upon request |
resistance to chemically active substances conformity according to EN 60721-3-3 |
Yes; Class 3C4 (RH < 75%) incl. salt spray acc. to EN 60068-2-52 (severity level 3) |
resistance to mechanically active substances conformity according to EN 60721-3-3 |
Yes; Class 3S4 incl. sand, dust |
resistance to biologically active substances conformity according to EN 60721-3-6 |
Yes; Class 6B2 mold, fungal, sponge spores (except fauna) |
resistance to chemically active substances conformity according to EN 60721-3-6 |
Yes; Class 6C3 (RH < 75%) incl. salt spray acc. to EN 60068-2-52 (severity level 3) |
resistance to mechanically active substances conformity according to EN 60721-3-6 |
Yes; Class 6S3 incl. sand, dust |
coating for equipped printed circuit board according to EN 61086 |
Yes; Class 2 for high availability |
type of coating protection against pollution according to EN 60664-3 |
Yes; Type 1 protection |
type of test of the coating according to MIL-I-46058C | Yes; Discoloration of the coating during service life possible |
product conformity of the coating Qualification and Performance of Electrical Insulating Compound for Printed Board Assemblies according to IPC-CC-830A |
Yes; Conformal Coating, Class A |
connection method | |
type of electrical connection | screw terminal |
● at input | L, N, PE: 1 screw terminal each for 0.5 … 2.5 mm² |
● at output | L+, M: 2 screw terminals each for 0.5 … 2.5 mm² |
● for auxiliary contacts | – |
mechanical data | |
width × height × depth of the enclosure | 70 × 100 × 75 mm |
installation width × mounting height | 70 mm × 140 mm |
required spacing | |
● top | 20 mm |
● bottom | 20 mm |
● left | 0 mm |
● right | 0 mm |
fastening method | Snaps onto DIN rail EN 60715 35×7.5/15, wall mounting |
● DIN-rail mounting | Yes |
● S7 rail mounting | No |
● wall mounting | Yes |
housing can be lined up | Yes |
net weight | 0.3 kg |
Weight | 0.326 kg |
---|---|
Dimensions | 8 × 10.50 × 8.50 cm |
INOSAKI Limited
RM B 5/F Gaylord Comm,
Bldg 114-118 Lockhart Rd.
Hong Kong
INOSAKI Sdn. Bhd.
2-1-9, Ground Floor, One Square, Tingkat Mahsuri 1,
11900 Bayan Lepas, Penang
INOSAKI Pte. Ltd.
101 Upper Cross Street,
No. 06-17, People’s Park Centre,
Singapore (058357)