| General information | |
| based on | 6ES7422-1BL00-0AA0 | 
| Supply voltage | |
| Load voltage L+ | |
| ● Rated value (DC) | 24 V | 
| ● permissible range, lower limit (DC) | 20.4 V | 
| ● permissible range, upper limit (DC) | 28.8 V | 
| Input current | |
| from load voltage L+ (without load), max. | 30 mA | 
| from backplane bus 5 V DC, max. | 200 mA | 
| Power loss | |
| Power loss, typ. | 4 W | 
| Digital outputs | |
| Number of digital outputs | 32 | 
| Short-circuit protection | Yes; Clocked electronically | 
| ● Response threshold, typ. | 0.7 to 1.5 A | 
| Limitation of inductive shutdown voltage to | -27 V | 
| Controlling a digital input | Yes; possible | 
| Switching capacity of the outputs | |
| ● on lamp load, max. | 5 W | 
| Load resistance range | |
| ● lower limit | 48 Ω | 
| ● upper limit | 4 Ω | 
| Output voltage | |
| ● for signal “1”, min. | L+ (-0.3 V) | 
| Output current | |
| ● for signal “1” rated value | 0.5 A | 
| ● for signal “1” permissible range, min. | 5 mA | 
| ● for signal “1” permissible range, max. | 0.6 A | 
| ● for signal “0” residual current, max. | 0.3 mA | 
| Output delay with resistive load | |
| ● “0” to “1”, max. | 1 ms | 
| ● “1” to “0”, max. | 1 ms | 
| Parallel switching of two outputs | |
| ● for uprating | Yes; possible (only outputs of the same group) | 
| ● for redundant control of a load | Yes; possible (only outputs of the same group) | 
| Switching frequency | |
| ● with resistive load, max. | 100 Hz | 
| ● with inductive load, max. | 0.5 Hz | 
| ● with inductive load (acc. to IEC 60947-5-1, DC13), max. | 2 Hz; 2 Hz at 0.3 A; 0.5 Hz at 0.5 A | 
| ● on lamp load, max. | 10 Hz | 
| Total current of the outputs (per group) | |
| all mounting positions | |
| – up to 40 °C, max. | 4:00 AM | 
| – up to 60 °C, max. | 2 A; 8 adjacent outputs each | 
| Cable length | |
| ● shielded, max. | 1 000 m | 
| ● unshielded, max. | 600 m | 
| Interrupts/diagnostics/status information | |
| Diagnostics function | No | 
| Potential separation | |
| Potential separation digital outputs | |
| ● between the channels | No | 
| ● between the channels, in groups of | 32 | 
| ● between the channels and backplane bus | Yes | 
| Isolation | |
| Isolation tested with | 500 V DC | 
| Ambient conditions | |
| Ambient temperature during operation | |
| ● min. | -25 °C; = Tmin | 
| ● max. | 60 °C; = Tmax | 
| Ambient temperature during storage/transportation | |
| ● min. | -40 °C | 
| ● max. | 70 °C | 
| Altitude during operation relating to sea level | |
| ● Installation altitude above sea level, max. | 5 000 m | 
| ● Ambient air temperature-barometric pressure-altitude | Tmin … Tmax at 1 140 hPa … 795 hPa (-1 000 m … +2 000 m) // Tmin … (Tmax – 10 K) at 795 hPa … 658 hPa (+2 000 m … +3 500 m) // Tmin … (Tmax -20 K) at 658 hPa … 540 hPa (+3 500 m … +5 000 m) | 
| Relative humidity | |
| ● With condensation, tested in accordance with IEC 60068- 2-38, max. | 100 %; RH incl. condensation/frost (no commissioning under condensation conditions) | 
| Resistance | |
| Use in stationary industrial systems | |
| – to biologically active substances according to EN 60721-3-3 | Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request | 
| – to chemically active substances according to EN 60721-3-3 | Yes; Class 3C4 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); * | 
| – to mechanically active substances according to EN 60721-3-3 | Yes; Class 3S4 incl. sand, dust, * | 
| Use on ships/at sea | |
| – to biologically active substances according to EN 60721-3-6 | Yes; Class 6B2 mold and fungal spores (excluding fauna); Class 6B3 on request | 
| – to chemically active substances according to EN 60721-3-6 | Yes; Class 6C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); * | 
| – to mechanically active substances according to EN 60721-3-6 | Yes; Class 6S3 incl. sand, dust; * | 
| Usage in industrial process technology | |
| – Against chemically active substances acc. to EN 60654-4 | Yes; Class 3 (excluding trichlorethylene) | 
| – Environmental conditions for process, measuring and control systems acc. to ANSI/ISA-71.04 | Yes; Level GX group A/B (excluding trichlorethylene; harmful gas concentrations up to the limits of EN 60721-3-3 class 3C4 permissible); level LC3 (salt spray) and level LB3 (oil) | 
| Remark | |
| – Note regarding classification of environmental conditions acc. to EN 60721, EN 60654-4 and ANSI/ISA-71.04 | * The supplied plug covers must remain in place over the unused interfaces during operation! | 
| Conformal coating | |
| ● Coatings for printed circuit board assemblies acc. to EN 61086 | Yes; Class 2 for high reliability | 
| ● Protection against fouling acc. to EN 60664-3 | Yes; Type 1 protection | 
| ● Military testing according to MIL-I-46058C, Amendment 7 | Yes; Discoloration of coating possible during service life | 
| ● Qualification and Performance of Electrical Insulating Compound for Printed Board Assemblies according to IPC- CC-830A | Yes; Conformal coating, Class A | 
| Dimensions | |
| Width | 25 mm | 
| Height | 290 mm | 
| Depth | 210 mm | 
| Weights | |
| Weight, approx. | 600 g | 
| Weight | 0.784 kg | 
|---|---|
| Dimensions | 23 × 30 × 3.5 cm |