Part number |
3RV6021-4AA10 |
3RV6021-4BA10 |
3RV6021-4CA10 |
3RV6021-4DA10 |
product brand name |
SIRIUS |
SIRIUS |
SIRIUS |
SIRIUS |
product designation |
Circuit breaker |
Circuit breaker |
Circuit breaker |
Circuit breaker |
design of the product |
for motor protection |
for motor protection |
for motor protection |
for motor protection |
product type designation |
3RV6 |
3RV6 |
3RV6 |
3RV6 |
General technical data |
size of the circuit-breaker |
S0 |
S0 |
S0 |
S0 |
power loss [W] total typical |
7 W |
8 W |
8 W |
8 W |
insulation voltage with degree of pollution 3 at AC rated value |
690 V |
690 V |
690 V |
690 V |
surge voltage resistance rated value |
6 kV |
6 kV |
6 kV |
6 kV |
shock resistance according to IEC 60068-2-27 |
25g / 11 ms |
25g / 11 ms |
25g / 11 ms |
25g / 11 ms |
Substance Prohibitance (Date) |
5/1/2012 |
5/1/2012 |
5/1/2012 |
5/1/2012 |
Ambient conditions |
installation altitude at height above sea level maximum |
2 000 m |
2 000 m |
2 000 m |
2 000 m |
ambient temperature |
|
|
|
|
? during operation |
-20 … +60 °C |
-20 … +60 °C |
-20 … +60 °C |
-20 … +60 °C |
? during transport |
-50 … +80 °C |
-50 … +80 °C |
-50 … +80 °C |
-50 … +80 °C |
relative humidity during operation |
10 … 95 % |
10 … 95 % |
10 … 95 % |
10 … 95 % |
Main circuit |
number of poles for main current circuit |
3 |
3 |
3 |
3 |
adjustable current response value current of the current-dependent overload release |
10 … 16 A |
13 … 20 A |
16 … 22 A |
18 … 25 A |
operating voltage |
|
|
|
|
rated value |
690 V |
690 V |
690 V |
690 V |
at AC-3 rated value maximum |
690 V |
690 V |
690 V |
690 V |
operating frequency rated value |
50 … 60 Hz |
50 … 60 Hz |
50 … 60 Hz |
50 … 60 Hz |
operational current rated value 25 A |
16 A |
20 A |
22 A |
25 A |
operational current at AC-3 at 400 V rated value |
16 A |
20 A |
22 A |
25 A |
operating frequency at AC-3 maximum |
15 1/h |
15 1/h |
15 1/h |
15 1/h |
Protective and monitoring functions |
trip class |
CLASS 10 |
CLASS 10 |
CLASS 10 |
CLASS 10 |
design of the overload release |
thermal |
thermal |
thermal |
thermal |
maximum short-circuit current breaking capacity (Icu) at AC at 400 V rated value |
55 kA |
55 kA |
55 kA |
55 kA |
operating short-circuit current breaking capacity (Ics) at AC at 400 V rated value |
25 kA |
25 kA |
25 kA |
25 kA |
response value current of instantaneous short-circuit trip unit |
208 A |
260 A |
286 A |
325 A |
Short-circuit protection |
product function short circuit protection |
Yes |
Yes |
Yes |
Yes |
design of the short-circuit trip |
magnetic |
magnetic |
magnetic |
magnetic |
Installation/ mounting/ dimensions |
mounting position |
any |
any |
any |
any |
fastening method |
screw and snap-on mounting onto 35 mm DIN rail according to DIN EN60715 |
screw and snap-on mounting onto 35 mm DIN rail according to DIN EN60715 |
screw and snap-on mounting onto 35 mm DIN rail according to DIN EN60715 |
screw and snap-on mounting onto 35 mm DIN rail according to DIN EN60715 |
height |
97 mm |
97 mm |
97 mm |
97 mm |
width |
45 mm |
45 mm |
45 mm |
45 mm |
depth |
96 mm |
96 mm |
96 mm |
96 mm |
required spacing for grounded parts |
|
|
|
|
forwards |
0 mm |
0 mm |
0 mm |
0 mm |
backwards |
0 mm |
0 mm |
0 mm |
0 mm |
upwards |
50 mm |
50 mm |
50 mm |
50 mm |
at the side |
30 mm |
30 mm |
30 mm |
30 mm |
downwards |
50 mm |
50 mm |
50 mm |
50 mm |
Connections/ Terminals |
type of electrical connection |
|
|
|
|
for main current circuit |
screw-type terminals |
screw-type terminals |
screw-type terminals |
screw-type terminals |
arrangement of electrical connectors for main current circuit |
Top and bottom |
Top and bottom |
Top and bottom |
Top and bottom |
type of connectable conductor cross-sections |
|
|
|
|
for main contacts |
|
|
|
|
— solid or stranded |
2x (1 … 2.5 mm²), 2x (2.5 … 10 mm²) |
2x (1 … 2.5 mm²), 2x (2.5 … 10 mm²) |
2x (1 … 2.5 mm²), 2x (2.5 … 10 mm²) |
2x (1 … 2.5 mm²), 2x (2.5 … 10 mm²) |
— finely stranded with core end processing |
2x (1 … 2.5 mm²), 2x (2.5 … 6 mm²), 1x 10 mm² |
2x (1 … 2.5 mm²), 2x (2.5 … 6 mm²), 1x 10 mm² |
2x (1 … 2.5 mm²), 2x (2.5 … 6 mm²), 1x 10 mm² |
2x (1 … 2.5 mm²), 2x (2.5 … 6 mm²), 1x 10 mm² |
at AWG cables for main contacts |
2x (16 … 12), 2x (14 … 8) |
2x (16 … 12), 2x (14 … 8) |
2x (16 … 12), 2x (14 … 8) |
2x (16 … 12), 2x (14 … 8) |
tightening torque |
|
|
|
|
for main contacts with screw-type terminals |
2 … 2.5 N·m |
2 … 2.5 N·m |
2 … 2.5 N·m |
2 … 2.5 N·m |
Safety related data |
protection class IP on the front according to IEC 60529 |
IP20 |
IP20 |
IP20 |
IP20 |
touch protection on the front according to IEC 60529 |
finger-safe, for vertical contact from the front |
finger-safe, for vertical contact from the front |
finger-safe, for vertical contact from the front |
finger-safe, for vertical contact from the front |
|
Part number |
3RV6021-4EA10 |
3RV6021-4FA10 |
3RV6021-4NA10 |
3RV6021-4PA10 |
product brand name |
SIRIUS |
SIRIUS |
SIRIUS |
SIRIUS |
product designation |
Circuit breaker |
Circuit breaker |
Circuit breaker |
Circuit breaker |
design of the product |
for motor protection |
for motor protection |
for motor protection |
for motor protection |
product type designation |
3RV6 |
3RV6 |
3RV6 |
3RV6 |
General technical data |
size of the circuit-breaker |
S0 |
S0 |
S0 |
S0 |
power loss [W] total typical |
11 W |
14 W |
11 W |
14 W |
insulation voltage with degree of pollution 3 at AC rated value |
690 V |
690 V |
690 V |
690 V |
surge voltage resistance rated value |
6 kV |
6 kV |
6 kV |
6 kV |
shock resistance according to IEC 60068-2-27 |
25g / 11 ms |
25g / 11 ms |
25g / 11 ms |
25g / 11 ms |
Substance Prohibitance (Date) |
5/1/2012 |
5/1/2012 |
5/1/2012 |
5/1/2012 |
Ambient conditions |
installation altitude at height above sea level maximum |
2 000 m |
2 000 m |
2 000 m |
2 000 m |
ambient temperature |
|
|
|
|
? during operation |
-20 … +60 °C |
-20 … +40 °C |
-20 … +60 °C |
-20 … +40 °C |
? during transport |
-50 … +80 °C |
-50 … +80 °C |
-50 … +80 °C |
-50 … +80 °C |
relative humidity during operation |
10 … 95 % |
10 … 95 % |
10 … 95 % |
10 … 95 % |
Main circuit |
number of poles for main current circuit |
3 |
3 |
3 |
3 |
adjustable current response value current of the current-dependent overload release |
27 … 32 A |
34 … 40 A |
23 … 28 A |
30 … 36 A |
operating voltage |
|
|
|
|
rated value |
690 V |
690 V |
690 V |
690 V |
at AC-3 rated value maximum |
690 V |
690 V |
690 V |
690 V |
operating frequency rated value |
50 … 60 Hz |
50 … 60 Hz |
50 … 60 Hz |
50 … 60 Hz |
operational current rated value 25 A |
32 A |
40 A |
28 A |
36 A |
operational current at AC-3 at 400 V rated value |
32 A |
40 A |
28 A |
36 A |
operating frequency at AC-3 maximum |
15 1/h |
15 1/h |
15 1/h |
15 1/h |
Protective and monitoring functions |
trip class |
CLASS 10 |
CLASS 10 |
CLASS 10 |
CLASS 10 |
design of the overload release |
thermal |
thermal |
thermal |
thermal |
maximum short-circuit current breaking capacity (Icu) at AC at 400 V rated value |
55 kA |
20 kA |
55 kA |
20 kA |
operating short-circuit current breaking capacity (Ics) at AC at 400 V rated value |
25 kA |
10 kA |
25 kA |
10 kA |
response value current of instantaneous short-circuit trip unit |
400 A |
480 A |
364 A |
432 A |
Short-circuit protection |
product function short circuit protection |
Yes |
Yes |
Yes |
Yes |
design of the short-circuit trip |
magnetic |
magnetic |
magnetic |
magnetic |
Installation/ mounting/ dimensions |
mounting position |
any |
any |
any |
any |
fastening method |
screw and snap-on mounting onto 35 mm DIN rail according to DIN EN60715 |
screw and snap-on mounting onto 35 mm DIN rail according to DIN EN60715 |
screw and snap-on mounting onto 35 mm DIN rail according to DIN EN60715 |
screw and snap-on mounting onto 35 mm DIN rail according to DIN EN60715 |
height |
97 mm |
97 mm |
97 mm |
97 mm |
width |
45 mm |
45 mm |
45 mm |
45 mm |
depth |
96 mm |
96 mm |
96 mm |
96 mm |
required spacing for grounded parts |
|
|
|
|
forwards |
0 mm |
0 mm |
0 mm |
0 mm |
backwards |
0 mm |
0 mm |
0 mm |
0 mm |
upwards |
50 mm |
70 mm |
50 mm |
70 mm |
at the side |
30 mm |
30 mm |
30 mm |
30 mm |
downwards |
50 mm |
70 mm |
50 mm |
70 mm |
Connections/ Terminals |
type of electrical connection |
|
|
|
|
for main current circuit |
screw-type terminals |
screw-type terminals |
screw-type terminals |
screw-type terminals |
arrangement of electrical connectors for main current circuit |
Top and bottom |
Top and bottom |
Top and bottom |
Top and bottom |
type of connectable conductor cross-sections |
|
|
|
|
for main contacts |
|
|
|
|
— solid or stranded |
2x (1 … 2.5 mm²), 2x (2.5 … 10 mm²) |
2x (1 … 2.5 mm²), 2x (2.5 … 10 mm²) |
2x (1 … 2.5 mm²), 2x (2.5 … 10 mm²) |
2x (1 … 2.5 mm²), 2x (2.5 … 10 mm²) |
— finely stranded with core end processing |
2x (1 … 2.5 mm²), 2x (2.5 … 6 mm²), 1x 10 mm² |
2x (1 … 2.5 mm²), 2x (2.5 … 6 mm²), 1x 10 mm² |
2x (1 … 2.5 mm²), 2x (2.5 … 6 mm²), 1x 10 mm² |
2x (1 … 2.5 mm²), 2x (2.5 … 6 mm²), 1x 10 mm² |
at AWG cables for main contacts |
2x (16 … 12), 2x (14 … 8) |
2x (16 … 12), 2x (14 … 8) |
2x (16 … 12), 2x (14 … 8) |
2x (16 … 12), 2x (14 … 8) |
tightening torque |
|
|
|
|
for main contacts with screw-type terminals |
2 … 2.5 N·m |
2 … 2.5 N·m |
2 … 2.5 N·m |
2 … 2.5 N·m |
Safety related data |
protection class IP on the front according to IEC 60529 |
IP20 |
IP20 |
IP20 |
IP20 |
touch protection on the front according to IEC 60529 |
finger-safe, for vertical contact from the front |
finger-safe, for vertical contact from the front |
finger-safe, for vertical contact from the front |
finger-safe, for vertical contact from the front |