Specifications

[fusion_table fusion_table_type=”1″ fusion_table_rows=”” fusion_table_columns=”” margin_top=”” margin_right=”” margin_bottom=”” margin_left=”” hide_on_mobile=”small-visibility,medium-visibility,large-visibility” class=”” id=”” animation_type=”” animation_direction=”left” animation_color=”” hue=”” saturation=”” lightness=”” alpha=”” animation_speed=”0.3″ animation_delay=”0″ animation_offset=””]

product brand name SIRIUS ACT
product designation Contact module
product type designation 3SU1
Contact block/ lampholder
socket design other
General technical data
product function positive opening Yes
insulation voltage rated value 500 V
degree of pollution 3
type of voltage
● of the operating voltage  AC/DC
● of the input voltage  AC/DC
surge voltage resistance rated value  6 Kv
protection class IP
● of the enclosure  IP40
● of the terminal  IP20
shock resistance
● according to IEC 60068-2-27 sinusoidal half-wave 15g / 11 ms
● for railway applications according to EN 61373 Category 1, Class B
vibration resistance
● according to IEC 60068-2-6 10 … 500 Hz: 5g
● for railway applications according to EN 61373 Category 1, Class B
operating frequency maximum 3 600 1/h
mechanical service life (operating cycles) typical 10 000 000
electrical endurance (operating cycles) typical 10 000 000
thermal current 10 A
reference code according to IEC 81346-2 S
continuous current of the C characteristic MCB 10 A
Substance Prohibitance (Date) 10/1/2014
operating voltage
● at AC
— at 50 Hz rated value 5 … 500 V
— at 60 Hz rated value 5 … 500 V
● at DC rated value 5 … 500 V
Power Electronics
contact reliability One maloperation per 100 million (17 V, 5 mA), one maloperation per 10
million (5 V, 1 mA)
Auxiliary circuit
design of the contact of auxiliary contacts Silver alloy
number of NC contacts for auxiliary contacts 1
● lagging switching 0
number of NO contacts for auxiliary contacts 0
● leading contact 0 0
operational current at AC-12
● at 24 V rated value 10 A
● at 48 V rated value 10 A
● at 110 V rated value 10 A
● at 230 V rated value 8 A
● at 400 V rated value 8 A
operational current at AC-15
● at 24 V rated value 6 A
● at 48 V rated value 6 A
● at 110 V rated value 6 A
● at 230 V rated value 6 A
● at 400 V rated value 3 A
● at 500 V rated value 1.4 A
operational current at DC-12
● at 24 V rated value 10 A 10 A
● at 48 V rated value 5 A 5 A
● at 110 V rated value 2.5 A 2.5 A
● at 230 V rated value 1 A 1 A
● at 400 V rated value 0.3 A 0.3 A
● at 500 V rated value 0.3 A 0.3 A
operational current at DC-13
● at 24 V rated value 3 A 3 A
● at 48 V rated value 1.5 A 1.5 A
● at 110 V rated value 0.7 A 0.7 A
● at 230 V rated value 0.3 A 0.3 A
● at 400 V rated value 0.1 A 0.1 A
● at 500 V rated value 0.1 A 0.1 A
Connections/ Terminals
type of electrical connection screw-type terminals
type of connectable conductor cross-sections
● solid with core end processing 2x (0.5 … 0.75 mm²)
● solid without core end processing 2x (1.0 … 1.5 mm²)
● finely stranded with core end processing 2x (0.5 … 1.5 mm²)
● finely stranded without core end processing 2x (1,0 … 1,5 mm²)
● at AWG cables 2x (18 … 14)
tightening torque with screw-type terminals 0.8 … 0.9 N·m
Ambient conditions
ambient temperature
● during operation  -25 … +70 °C
● during storage  -40 … +80 °C
environmental category during operation according to IEC 3M6, 3S2, 3B2, 3C3 (without salt spray), 3K6 (with relative humidity of
60721 10 … 95%, no condensation in operation permitted)
Installation/ mounting/ dimensions
fastening method floor mounting
● of modules and accessories Floor mounting
height 33.2 mm
width 9.8 mm
depth 27.7 mm
suitability for integration
● plastic enclosure Yes
● metal enclosure Yes

[/fusion_table]

Weight 0.01 kg
Dimensions 7.8 × 10.7 × 1.7 cm