input | |
type of the power supply network | DC voltage |
supply voltage at DC | 24 … 24 V |
input voltage at DC | 24 … 28.8 V |
output | |
voltage curve at output | Controlled, isolated DC voltage |
output voltage at DC rated value | 24 V |
formula for output voltage | Vin – approx. 0.5 V |
output voltage | |
● at output 1 at DC rated value | 24 V |
output voltage adjustable | No |
display version for normal operation | Green LED for “both Input voltages > switching threshold”; red LED: for “at least one input voltage < switching threshold” |
type of signal at output | Isolated relay contact (changeover contacts, rating 8 A/240 V AC, 24 V DC): Signals OK if both input voltages > switching threshold, setting range of threshold 20 … 25 V |
output current | |
● rated value | 40 A |
● rated range | 40 A; max. aggregate current 40 A; +60 … +70 °C: derating 3%/K |
efficiency | |
efficiency in percent | 96.6 % |
power loss [W] | |
● at rated output voltage for rated value of the output current typical |
34 W |
● during no-load operation maximum | 1.5 W |
safety | |
galvanic isolation | yes, SELV acc. to EN 60950-1 (relay contact) |
operating resource protection class | Class III |
protection class IP | IP20 |
EMC | |
standard | |
● for emitted interference | EN 55022 Class B |
● for interference immunity | EN 61000-6-2 |
standards, specifications, approvals | |
certificate of suitability | |
● CE marking | Yes |
● UL approval | Yes; cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259 |
● CSA approval | Yes; cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259 |
● EAC approval | Yes |
● NEC Class 2 | No |
type of certification | |
● CB-certificate | No |
MTBF at 40 °C | 6 471 654 h |
standards, specifications, approvals hazardous environments | |
certificate of suitability | |
● IECEx | No |
● ATEX | No |
● ULhazloc approval | No |
● cCSAus, Class 1, Division 2 | No |
● FM registration | No |
standards, specifications, approvals marine classification | |
shipbuilding approval | Yes |
Marine classification association | |
● American Bureau of Shipping Europe Ltd. (ABS) | Yes |
● French marine classification society (BV) | No |
● Det Norske Veritas (DNV) | Yes |
● Lloyds Register of Shipping (LRS) | No |
ambient conditions | |
ambient temperature | |
● during operation | -25 … +60; with natural convection |
● during transport | -40 … +85 |
● during storage | -40 … +85 |
environmental category according to IEC 60721 | Climate class 3K3, 5 … 95% no condensation |
connection method | |
type of electrical connection | screw terminal |
● at input | Input, output and ground: 1 screw terminal each for 0.33 … 10 mm² single- core/finely stranded |
● for auxiliary contacts | Relay contact: 3 screw terminals for 0.5 … 2.5 mm² single-core/finely stranded |
mechanical data | |
width × height × depth of the enclosure | 70 × 125 × 120 mm |
installation width × mounting height | 70 mm × 225 mm |
required spacing | |
● top | 50 mm |
● bottom | 50 mm |
● left | 0 mm |
● right | 0 mm |
fastening method | Snaps onto DIN rail EN 60715 35×7.5/15 |
● DIN-rail mounting | Yes |
● S7 rail mounting | No |
● wall mounting | No |
housing can be lined up | Yes |
net weight | 0.5 kg |
Weight | 0.400 kg |
---|---|
Dimensions | 13.5 × 13.5 × 8 cm |
Axmatic Sdn Bhd
2-1-9, Ground Floor, One Square, Tingkat Mahsuri 1,
11900 Bayan Lepas, Penang