| input | |
| type of the power supply network | 1-phase AC or DC |
| supply voltage at AC | |
| ● minimum rated value | 100 V |
| ● maximum rated value | 230 V |
| ● initial value | 85 V |
| ● full-scale value | 264 V |
| input voltage at DC | 110 … 300 V |
| wide range input | Yes |
| overvoltage overload capability | 2.3 × Vin rated, 1.3 ms |
| buffering time for rated value of the output current in the event of power failure minimum |
20 ms |
| operating condition of the mains buffering | at Vin = 230 V |
| line frequency | 50/60 Hz |
| line frequency | 47 … 63 Hz |
| input current | |
| ● at rated input voltage 100 V | 0.28 A |
| ● at rated input voltage 230 V | 0.18 A |
| current limitation of inrush current at 25 °C maximum | 28 A |
| I2t value maximum | 0.7 A²·s |
| fuse protection type | internal |
| fuse protection type in the feeder | Recommended miniature circuit breaker: from 16 A characteristic B or from 10 A characteristic C |
| output | |
| voltage curve at output | Controlled, isolated DC voltage |
| output voltage at DC rated value | 24 V |
| output voltage | |
| ● at output 1 at DC rated value | 24 V |
| output voltage adjustable | No; – |
| relative overall tolerance of the voltage | 3 % |
| relative control precision of the output voltage | |
| ● on slow fluctuation of input voltage | 0.1 % |
| ● on slow fluctuation of ohm loading | 0.2 % |
| residual ripple | |
| ● maximum | 200 mV |
| ● typical | 40 mV |
| voltage peak | |
| ● maximum | 300 mV |
| ● typical | 20 mV |
| display version for normal operation | Green LED for output voltage OK |
| behavior of the output voltage when switching on | Overshoot of Vout approx. 5 % |
| response delay maximum | 1 s |
| voltage increase time of the output voltage | |
| ● typical | 25 ms |
| output current | |
| ● rated value | 0.6 A |
| ● rated range | 0 … 0.6 A |
| supplied active power typical | 14 W |
| short-term overload current | |
| ● at short-circuit during operation typical | 1 A |
| bridging of equipment | No |
| efficiency | |
| efficiency in percent | 82 % |
| power loss [W] | |
| ● at rated output voltage for rated value of the output current typical |
2.6 W |
| ● during no-load operation maximum | 0.75 W |
| closed-loop control | |
| relative control precision of the output voltage with rapid fluctuation of the input voltage by +/- 15% typical |
0.1 % |
| relative control precision of the output voltage at load step of resistive load 10/90/10 % typical |
3 % |
| setting time | |
| ● load step 10 to 90% typical | 3 ms |
| ● load step 90 to 10% typical | 3 ms |
| protection and monitoring | |
| design of the overvoltage protection | Yes, according to EN 60950-1 |
| property of the output short-circuit proof | Yes |
| design of short-circuit protection | Electronic shutdown, automatic restart |
| ● typical | 0.7 A |
| safety | |
| galvanic isolation between input and output | Yes |
| galvanic isolation | Safety extra-low output voltage Uout acc. to EN 60950-1 and EN 50178 |
| operating resource protection class | Class I |
| leakage current | |
| ● maximum | 3.5 mA |
| ● typical | 0.4 mA |
| protection class IP | IP20 |
| EMC | |
| standard | |
| ● for emitted interference | EN 55022 Class B |
| ● for mains harmonics limitation | not applicable |
| ● for interference immunity | EN 61000-6-2 |
| standards, specifications, approvals | |
| certificate of suitability | |
| ● CE marking | Yes |
| ● UL approval | Yes; cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259; cURus- Recognized (UL 60950, CSA C22.2 No. 60950), File E151273, NEC class 2 (acc. to UL 1310) |
| ● CSA approval | Yes; cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259; cURus- Recognized (UL 60950, CSA C22.2 No. 60950), File E151273, NEC class 2 (acc. to UL 1310) |
| ● EAC approval | Yes |
| ● NEC Class 2 | Yes; according to UL1310, File E151273 |
| type of certification | |
| ● CB-certificate | Yes |
| MTBF at 40 °C | 3 910 833 h |
| standards, specifications, approvals hazardous environments | |
| certificate of suitability | |
| ● IECEx | No |
| ● ATEX | No |
| ● ULhazloc approval | No |
| ● cCSAus, Class 1, Division 2 | No |
| ● FM registration | No |
| standards, specifications, approvals marine classification | |
| shipbuilding approval | Yes |
| Marine classification association | |
| ● American Bureau of Shipping Europe Ltd. (ABS) | Yes |
| ● French marine classification society (BV) | No |
| ● Det Norske Veritas (DNV) | Yes |
| ● Lloyds Register of Shipping (LRS) | No |
| standards, specifications, approvals Environmental Product Declaration | |
| Environmental Product Declaration | Yes |
| global warming potential [CO2 eq] | |
| ● total | 73.5 kg |
| ● during manufacturing | 2.3 kg |
| ● during operation | 71.1 kg |
| ● after end of life | 0.08 kg |
| ambient conditions | |
| ambient temperature | |
| ● during operation | -20 … +70; with natural convection |
| ● during transport | -40 … +85 |
| ● during storage | -40 … +85 |
| environmental category according to IEC 60721 | Climate class 3K3, 5 … 95% no condensation |
| connection method | |
| type of electrical connection | screw terminal |
| ● at input | L, N, PE: Removable screw terminal, each for 1 x 0.5 … 2.5 mm² |
| ● at output | +: 1 screw terminal for 0.5 … 2.5 mm²; -: 2 screw terminals for 0.5 … 2.5 mm² |
| ● for auxiliary contacts | – |
| mechanical data | |
| width × height × depth of the enclosure | 22.5 × 80 × 100 mm |
| installation width × mounting height | 22.5 mm × 180 mm |
| required spacing | |
| ● top | 50 mm |
| ● bottom | 50 mm |
| ● left | 0 mm |
| ● right | 0 mm |
| fastening method | Snaps onto DIN rail EN 60715 35×7.5/15 |
| ● DIN-rail mounting | Yes |
| ● S7 rail mounting | No |
| ● wall mounting | No |
| housing can be lined up | Yes |
| net weight | 0.12 kg |
| accessories | |
| electrical accessories | Removable spring-type terminal 6EP1971-5BA00 |
| Weight | 0.120 kg |
|---|---|
| Dimensions | 10 × 11 × 2.8 cm |