input | |
type of the power supply network | 1-phase AC or DC |
supply voltage at AC | |
● minimum rated value | 100 V |
● maximum rated value | 230 V |
● initial value | 85 V |
● full-scale value | 264 V |
input voltage at DC | 110 … 300 V |
wide range input | Yes |
overvoltage overload capability | 2.3 × Vin rated, 1.3 ms |
buffering time for rated value of the output current in the event of power failure minimum |
20 ms |
operating condition of the mains buffering | at Vin = 230 V |
line frequency | 50/60 Hz |
line frequency | 47 … 63 Hz |
input current | |
● at rated input voltage 100 V | 0.28 A |
● at rated input voltage 230 V | 0.18 A |
current limitation of inrush current at 25 °C maximum | 28 A |
I2t value maximum | 0.7 A²·s |
fuse protection type | internal |
fuse protection type in the feeder | Recommended miniature circuit breaker: from 16 A characteristic B or from 10 A characteristic C |
output | |
voltage curve at output | Controlled, isolated DC voltage |
output voltage at DC rated value | 24 V |
output voltage | |
● at output 1 at DC rated value | 24 V |
output voltage adjustable | No; – |
relative overall tolerance of the voltage | 3 % |
relative control precision of the output voltage | |
● on slow fluctuation of input voltage | 0.1 % |
● on slow fluctuation of ohm loading | 0.2 % |
residual ripple | |
● maximum | 200 mV |
● typical | 40 mV |
voltage peak | |
● maximum | 300 mV |
● typical | 20 mV |
display version for normal operation | Green LED for output voltage OK |
behavior of the output voltage when switching on | Overshoot of Vout approx. 5 % |
response delay maximum | 1 s |
voltage increase time of the output voltage | |
● typical | 25 ms |
output current | |
● rated value | 0.6 A |
● rated range | 0 … 0.6 A |
supplied active power typical | 14 W |
short-term overload current | |
● at short-circuit during operation typical | 1 A |
bridging of equipment | No |
efficiency | |
efficiency in percent | 82 % |
power loss [W] | |
● at rated output voltage for rated value of the output current typical |
2.6 W |
● during no-load operation maximum | 0.75 W |
closed-loop control | |
relative control precision of the output voltage with rapid fluctuation of the input voltage by +/- 15% typical |
0.1 % |
relative control precision of the output voltage at load step of resistive load 10/90/10 % typical |
3 % |
setting time | |
● load step 10 to 90% typical | 3 ms |
● load step 90 to 10% typical | 3 ms |
protection and monitoring | |
design of the overvoltage protection | Yes, according to EN 60950-1 |
property of the output short-circuit proof | Yes |
design of short-circuit protection | Electronic shutdown, automatic restart |
● typical | 0.7 A |
safety | |
galvanic isolation between input and output | Yes |
galvanic isolation | Safety extra-low output voltage Uout acc. to EN 60950-1 and EN 50178 |
operating resource protection class | Class I |
leakage current | |
● maximum | 3.5 mA |
● typical | 0.4 mA |
protection class IP | IP20 |
EMC | |
standard | |
● for emitted interference | EN 55022 Class B |
● for mains harmonics limitation | not applicable |
● for interference immunity | EN 61000-6-2 |
standards, specifications, approvals | |
certificate of suitability | |
● CE marking | Yes |
● UL approval | Yes; cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259; cURus- Recognized (UL 60950, CSA C22.2 No. 60950), File E151273, NEC class 2 (acc. to UL 1310) |
● CSA approval | Yes; cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259; cURus- Recognized (UL 60950, CSA C22.2 No. 60950), File E151273, NEC class 2 (acc. to UL 1310) |
● EAC approval | Yes |
● NEC Class 2 | Yes; according to UL1310, File E151273 |
type of certification | |
● CB-certificate | Yes |
MTBF at 40 °C | 3 910 833 h |
standards, specifications, approvals hazardous environments | |
certificate of suitability | |
● IECEx | No |
● ATEX | No |
● ULhazloc approval | No |
● cCSAus, Class 1, Division 2 | No |
● FM registration | No |
standards, specifications, approvals marine classification | |
shipbuilding approval | Yes |
Marine classification association | |
● American Bureau of Shipping Europe Ltd. (ABS) | Yes |
● French marine classification society (BV) | No |
● Det Norske Veritas (DNV) | Yes |
● Lloyds Register of Shipping (LRS) | No |
standards, specifications, approvals Environmental Product Declaration | |
Environmental Product Declaration | Yes |
global warming potential [CO2 eq] | |
● total | 73.5 kg |
● during manufacturing | 2.3 kg |
● during operation | 71.1 kg |
● after end of life | 0.08 kg |
ambient conditions | |
ambient temperature | |
● during operation | -20 … +70; with natural convection |
● during transport | -40 … +85 |
● during storage | -40 … +85 |
environmental category according to IEC 60721 | Climate class 3K3, 5 … 95% no condensation |
connection method | |
type of electrical connection | screw terminal |
● at input | L, N, PE: Removable screw terminal, each for 1 x 0.5 … 2.5 mm² |
● at output | +: 1 screw terminal for 0.5 … 2.5 mm²; -: 2 screw terminals for 0.5 … 2.5 mm² |
● for auxiliary contacts | – |
mechanical data | |
width × height × depth of the enclosure | 22.5 × 80 × 100 mm |
installation width × mounting height | 22.5 mm × 180 mm |
required spacing | |
● top | 50 mm |
● bottom | 50 mm |
● left | 0 mm |
● right | 0 mm |
fastening method | Snaps onto DIN rail EN 60715 35×7.5/15 |
● DIN-rail mounting | Yes |
● S7 rail mounting | No |
● wall mounting | No |
housing can be lined up | Yes |
net weight | 0.12 kg |
accessories | |
electrical accessories | Removable spring-type terminal 6EP1971-5BA00 |
Weight | 0.120 kg |
---|---|
Dimensions | 10 × 11 × 2.8 cm |
Axmatic Sdn Bhd
2-1-9, Ground Floor, One Square, Tingkat Mahsuri 1,
11900 Bayan Lepas, Penang