[fusion_table fusion_table_type=”1″ fusion_table_rows=”” fusion_table_columns=”” margin_top=”” margin_right=”” margin_bottom=”” margin_left=”” hide_on_mobile=”small-visibility,medium-visibility,large-visibility” class=”” id=”” animation_type=”” animation_direction=”left” animation_color=”” hue=”” saturation=”” lightness=”” alpha=”” animation_speed=”0.3″ animation_delay=”0″ animation_offset=””]

Article number 6EP1336-3BA10
Product SITOP PSU8200
Power supply, type 24 V/20 A
Input
type of the power supply network 1-phase and 2-phase AC or DC
supply voltage at AC
● minimum rated value 120 V
● maximum rated value 230 V
● initial value 85 V; Derating of temperature necessary down to 50 °C at Vin < 100 V AC or DC
● full-scale value 275 V
supply voltage
● 1 at AC rated value
● 2 at AC rated value
● at DC 110 … 220 V
input voltage
● 1 at AC
● 2 at AC
● at DC 88 … 350 V
design of input wide range input Yes
operating condition of the mains buffering at Vin = 230 V
buffering time for rated value of the output current in the event of power failure minimum 20 ms
operating condition of the mains buffering at Vin = 230 V
line frequency
● 1 rated value 50 Hz
● 2 rated value 60 Hz
line frequency 45 … 65 Hz
input current
● at rated input voltage 120 V 4.6 A
● at rated input voltage 230 V 2.5 A
current limitation of inrush current at 25 °C maximum 20 A
I2t value maximum 5 A²·s
fuse protection type Yes
● in the feeder Recommended miniature circuit breaker at 1-phase operation: 10 A characteristic C; required at 2-phase operation: circuit breaker 2-pole connected or circuit breaker 3RV2711-1HD10 (UL 489) at 120 V or 3RV2711-1ED10 (UL 489) at 230 V
Output
voltage curve at output Controlled, isolated DC voltage
output voltage at DC rated value 24 V
output voltage
● at output 1 at DC rated value 24 V
relative overall tolerance of the voltage 3 %
relative control precision of the output voltage
● on slow fluctuation of input voltage 0.1 %
● on slow fluctuation of ohm loading 0.3 %
residual ripple
● maximum 100 mV
● typical 80 mV
voltage peak
● maximum 200 mV
● typical 100 mV
adjustable output voltage 24 … 28.8 V
product function output voltage adjustable Yes
type of output voltage setting via potentiometer
display version for normal operation Green LED for 24 V OK
type of signal at output Relay contact (NO contact, rating 60 V DC/ 0.3 A) for “24 V OK”
behavior of the output voltage when switching on No overshoot of Vout (soft start)
response delay maximum 1.5 s
voltage increase time of the output voltage
● typical 50 ms
output current
● rated value 20 A
● rated range 0 … 20 A; +60 … +70 °C: Derating 3%/K
supplied active power typical 480 W
short-term overload current
● on short-circuiting during the start-up typical
● at short-circuit during operation typical 60 A
duration of overloading capability for excess current
● on short-circuiting during the start-up
● at short-circuit during operation 25 ms
constant overload current
● on short-circuiting during the start-up typical 30 A
product feature
● bridging of equipment Yes; switchable characteristic
number of parallel-switched equipment resources for increasing the power 2
Efficiency
efficiency in percent 93 %
power loss [W]
● at rated output voltage for rated value of the output current typical 42 W
● during no-load operation maximum
Closed-loop control
relative control precision of the output voltage with rapid fluctuation of the input voltage by +/- 15% typical 0.5 %
relative control precision of the output voltage load step of resistive load 50/100/50 % typical 1 %
setting time
● load step 50 to 100% typical 1 ms
● load step 100 to 50% typical 1 ms
relative control precision of the output voltage at load step of resistive load 10/90/10 % typical
setting time
● load step 10 to 90% typical
● load step 90 to 10% typical
● maximum 5 ms
Protection and monitoring
design of the overvoltage protection < 33 V
● typical 21.5 A
property of the output short-circuit proof Yes
design of short-circuit protection Alternatively, constant current characteristic approx. 23 A or latching shutdown
enduring short circuit current RMS value
● typical 23 A
overcurrent overload capability in normal operation overload capability 150 % Iout rated up to 5 s/min
display version for overload and short circuit LED yellow for “overload”, LED red for “latching shutdown”
Safety
galvanic isolation between input and output Yes
galvanic isolation Safety extra-low output voltage Uout acc. to EN 60950-1 and EN 50178
operating resource protection class Class I
leakage current
● maximum 3.5 mA
● typical 1 mA
protection class IP IP20
Approvals
certificate of suitability
● CE marking Yes
● UL approval Yes; cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259; cCSAus (CSA C22.2 No. 60950-1, UL 60950-1)
● CSA approval Yes; cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259; cCSAus (CSA C22.2 No. 60950-1, UL 60950-1)
● cCSAus, Class 1, Division 2 No
● ATEX No
certificate of suitability
● IECEx No
● NEC Class 2 No
● ULhazloc approval No
● FM registration No
type of certification CB-certificate Yes
certificate of suitability
● EAC approval Yes
certificate of suitability shipbuilding approval Yes
shipbuilding approval ABS, DNV GL
Marine classification association
● American Bureau of Shipping Europe Ltd. (ABS) Yes
● French marine classification society (BV) No
● DNV GL Yes
● Lloyds Register of Shipping (LRS) No
● Nippon Kaiji Kyokai (NK) No
EMC
standard
● for emitted interference EN 55022 Class B
● for mains harmonics limitation EN 61000-3-2
● for interference immunity EN 61000-6-2
environmental conditions
ambient temperature
● during operation -25 … +70 °C; With natural convection; startup tested starting from -40 °C nominal voltage
● during transport -40 … +85 °C
● during storage -40 … +85 °C
environmental category according to IEC 60721 Climate class 3K3, 5 … 95% no condensation
Mechanics
type of electrical connection screw-type terminals
● at input L, N, PE: 1 screw terminal each for 0.2 … 4 mm² single-core/finely stranded
● at output +, -: 2 screw terminals each for 0.2 … 4 mm²
● for auxiliary contacts 13, 14 (alarm signal): 1 screw terminal each for 0.14 … 1.5 mm²
width of the enclosure 90 mm
height of the enclosure 125 mm
depth of the enclosure 125 mm
required spacing
● top 50 mm
● bottom 50 mm
● left 0 mm
● right 0 mm
net weight 1.2 kg
product feature of the enclosure housing can be lined up Yes
fastening method Snaps onto DIN rail EN 60715 35×7.5/15
electrical accessories Buffer module
mechanical accessories Device identification label 20 mm × 7 mm, TI-grey 3RT2900-1SB20
MTBF at 40 °C 667 048 h
other information Specifications at rated input voltage and ambient temperature +25 °C (unless otherwise specified)

[/fusion_table]

 

 

 

[fusion_table fusion_table_type=”1″ fusion_table_rows=”” fusion_table_columns=”” margin_top=”” margin_right=”” margin_bottom=”” margin_left=”” hide_on_mobile=”small-visibility,medium-visibility,large-visibility” class=”” id=”” animation_type=”” animation_direction=”left” animation_color=”” hue=”” saturation=”” lightness=”” alpha=”” animation_speed=”0.3″ animation_delay=”0″ animation_offset=””]

Article number 6EP3334-8SB00-0AY0
Product SITOP PSU8200
Input
type of the power supply network 1-phase AC
supply voltage at AC
● initial value Automatic range selection
supply voltage
● 1 at AC rated value  120 V
● 2 at AC rated value  230 V
input voltage
● 1 at AC 85 … 132 V
● 2 at AC 170 … 264 V
design of input wide range input No
operating condition of the mains buffering at Vin = 120/230 V
buffering time for rated value of the output current in the 35 ms
event of power failure minimum
operating condition of the mains buffering at Vin = 120/230 V
line frequency
● 1 rated value 50 Hz
● 2 rated value 60 Hz
line frequency 47 … 63 Hz
input current
● at rated input voltage 120 V 4A
● at rated input voltage 230 V 1.9A
current limitation of inrush current at 25 °C maximum 10A
I2t value maximum 0.3 A²·s
fuse protection type T 6.3 A (not accessible)
● in the feeder Recommended miniature circuit breaker at 1-phase operation: from 6 A (10 A) characteristic C (B); required at 2-phase operation: circuit breaker 2-pole connected or circuit breaker 3RV2011-1EA10 (setting 3.8 A) or 3RV2711-1ED10 (UL 489) at 230 V; 3RV2011-1DA10 (setting 3 A) or 3RV2711-1DD10 (UL 489) at 400/500 V
Output
voltage curve at output Controlled, isolated DC voltage
output voltage at DC rated value 24v
output voltage
● at output 1 at DC rated value 24V
relative overall tolerance of the voltage 3%
relative control precision of the output voltage
● on slow fluctuation of input voltage 0.1%
● on slow fluctuation of ohm loading 0.3%
residual ripple
● maximum 50 mV
voltage peak
● maximum 200 mV
adjustable output voltage 24 … 28.8 V
product function output voltage adjustable Yes
type of output voltage setting via potentiometer; max. 240 W
display version for normal operation Green LED for 24 V OK
type of signal at output Relay contact (NO contact, rating 60 V DC/ 0.3 A) for “24 V OK”
behavior of the output voltage when switching on Overshoot of Vout approx. 3 %
response delay maximum 1.5 s
voltage increase time of the output voltage
● typical 70 ms
output current
● rated value 10A
● rated range 0 … 10 A; +60 … +70 °C: Derating 2%/K; as of Ua>24 V: 4% [Ia]/V [Ua];
at Ue<100 V/<200 V: 80% Ia rated
supplied active power typical 240 W
short-term overload current
● at short-circuit during operation typical 30 A
duration of overloading capability for excess current
● at short-circuit during operation 25 ms
constant overload current
● on short-circuiting during the start-up typical product feature 12 A
● bridging of equipment Yes; switchable characteristic
number of parallel-switched equipment resources for increasing the power 2
Efficiency
efficiency in percent 94%
power loss [W]
● at rated output voltage for rated value of the output current typical 18 W
● during no-load operation maximum 1.5 W
Closed-loop control
relative control precision of the output voltage with rapid
fluctuation of the input voltage by +/- 15% typical
0.1%
relative control precision of the output voltage load step of 4%
resistive load 50/100/50 % typical
setting time
● load step 50 to 100% typical 0.25 ms
● load step 100 to 50% typical 0.5 ms
relative control precision of the output voltage at load step 4%
of resistive load 10/90/10 % typical
setting time
● load step 10 to 90% typical 0.25 ms
● load step 90 to 10% typical 0.5 ms
● maximum 1 ms
Protection and monitoring
design of the overvoltage protection < 33 V
● typical 12 A
property of the output short-circuit proof Yes
design of short-circuit protection Alternatively, constant current characteristic approx. 12 A or latching
shutdown
enduring short circuit current RMS value
● typical 12 A
overcurrent overload capability in normal operation overload capability 150 % Iout rated up to 5 s/min
display version for overload and short circuit LED yellow for “overload”, LED red for “latching shutdown”
Safety
galvanic isolation between input and output Yes
galvanic isolation Safety extra-low output voltage Uout acc. to EN 60950-1 and EN 50178
operating resource protection class Class I
leakage current
● maximum 3.4 mA
● typical 1 mA
protection class IP IP20
Approvals
certificate of suitability
● CE marking Yes
● UL approval Yes; cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259; cCSAus (CSA C22.2 No. 60950-1, UL 60950-1)
● CSA approval Yes; cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259;
cCSAus (CSA C22.2 No. 60950-1, UL 60950-1)
● cCSAus, Class 1, Division 2 No
● ATEX No
certificate of suitability
● IECEx No
 ● NEC Class 2 No
● ULhazloc approval No
● FM registration No
type of certification CB-certificate Yes
certificate of suitability
● EAC approval Yes
certificate of suitability shipbuilding approval Yes
shipbuilding approval ABS, DNV GL
Marine classification association
● American Bureau of Shipping Europe Ltd. (ABS) Yes
● French marine classification society (BV) No
● DNV GL Yes
● Lloyds Register of Shipping (LRS) No
● Nippon Kaiji Kyokai (NK) No
EMC
standard
● for emitted interference EN 55022 Class B
● for mains harmonics limitation EN 61000-3-2
● for interference immunity EN 61000-6-2
environmental conditions
ambient temperature
● during operation -25 … +70 °C; With natural convection; startup tested starting from -40
°C nominal voltage
● during transport -40 … +85 °C
● during storage -40 … +85 °C
environmental category according to IEC 60721 Climate class 3K3, 5 … 95% no condensation
Mechanics
type of electrical connection screw-type terminals
● at input L, N, PE: 1 screw terminal each for 0.2 … 2.5 mm² single-core/finely
stranded
● at output +, -: 2 screw terminals each for 0.2 … 2.5 mm²
13, 14 (alarm signal): 1 screw terminal each for 0.14 … 1.5 mm²; 15, 16
(Remote): 1 screw terminal each for 0.14 … 1.5 mm²
width of the enclosure 55 mm
height of the enclosure 125 mm
depth of the enclosure 125 mm
required spacing
● top 50 mm
● bottom 50 mm
● left 0 mm
● right 0 mm
net weight 1kg
product feature of the enclosure housing can be lined up Yes
fastening method Snaps onto DIN rail EN 60715 35×7.5/15
electrical accessories Buffer module
mechanical accessories Device identification label 20 mm × 7 mm, TI-grey 3RT2900-1SB20
MTBF at 40 °C 1 292 102 h
other information Specifications at rated input voltage and ambient temperature +25 °C
(unless otherwise specified)

[/fusion_table]

Weight N/A
Dimensions N/A
Model

6EP1336-3BA10, 6EP3334-8SB00-0AY0