TeSys Deca contactor, 3 poles (3NO), for motor control applications up to 95A/1000V AC-3/AC-3e (45kW@400V). It provides a 24V 50/60Hz AC coil, 1NO+1NC built-in auxiliary contacts, power connections by screw terminals and control by screw clamp terminals. For operating rates until 3600 cycles/hour and environments until 60°C, it procures high reliability and durability. Compact (85mm width), DIN-rail mounting or screw fixing. Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine), Green Premium compliant (RoHS/REACh).
| Main | |
| Range | TeSys | 
| Range of product | TeSys Deca | 
| Contactor application | Motor control | 
| Utilisation category | AC-3 | 
| AC-4 | |
| AC-1 | |
| [Ue] rated operational voltage | Power circuit: <= 690 V AC 25…400 Hz | 
| [Ie] rated operational current | 95 A (at <60 °C) at <= 440 V AC-3 for power circuit | 
| 95 A (at <60 °C) at <= 440 V AC-3e for power circuit | |
| [Uc] control circuit voltage | 24 V AC 50/60 Hz | 
| 45 kW at 415…440 V AC 50 Hz (AC-3) | |
| 55 kW at 500 V AC 50 Hz (AC-3) | |
| 15 kW at 400 V AC 50 Hz (AC-4) | |
| 45 kW at 380…400 V AC 50 Hz (AC-3e) | |
| 45 kW at 660…690 V AC 50 Hz (AC-3e) | |
| 15 hp at 230/240 V AC 60 Hz for 1 phase motors | |
| 30 hp at 200/208 V AC 60 Hz for 3 phases motors | |
| 30 hp at 230/240 V AC 60 Hz for 3 phases motors | |
| 60 hp at 575/600 V AC 60 Hz for 3 phases motors | |
| Pole contact composition | 3 NO | 
| Protective cover | With | 
| [Ith] conventional free air thermal current | 10 A (at 60 °C) for signalling circuit | 
| 125 A (at 60 °C) for power circuit | |
| 140 A AC for signalling circuit conforming to IEC 60947-5-1 | |
| 250 A DC for signalling circuit conforming to IEC 60947-5-1 | |
| Rated breaking capacity | 1100 A at 440 V for power circuit conforming to IEC 60947 | 
| 800 A 40 °C – 10 s for power circuit | |
| 400 A 40 °C – 1 min for power circuit | |
| 120 A – 500 ms for signalling circuit | |
| 100 A – 1 s for signalling circuit | |
| Associated fuse rating | 10 A gG for signalling circuit conforming to IEC 60947-5-1 | 
| 200 A gG at <= 690 V coordination type 1 for power circuit | |
| 160 A gG at <= 690 V coordination type 2 for power circuit | |
| Power dissipation per pole | 12.5 W AC-1 | 
| [Ui] rated insulation voltage | Power circuit: 1000 V conforming to IEC 60947-4-1 | 
| Power circuit: 600 V CSA certified | |
| Power circuit: 600 V UL certified | |
| Signalling circuit: 600 V CSA certified | |
| Pollution degree | 3 | 
| [Uimp] rated impulse withstand voltage | 8 kV conforming to IEC 60947 | 
| Safety reliability level | B10d = 1.3 Mcycles contactor with nominal load conforming to EN/ISO 13849-1 | 
| Mechanical durability | 4 Mcycles | 
| Electrical durability | 1.2 Mcycles 95 A AC-3 | 
| 1.3 Mcycles 125 A AC-1 | |
| Control circuit type | AC at 50/60 Hz standard | 
| Coil technology | Without built-in suppressor module | 
| Control circuit voltage limits | 0.8…1.1 Uc (-40…55 °C):operational AC 50 Hz | 
| 0.3…0.6 Uc (-40…70 °C):drop-out AC 50/60 Hz | |
| 1…1.1 Uc (55…70 °C):operational AC 50/60 Hz | |
| Inrush power in VA | 245 VA 60 Hz cos phi 0.75 (at 20 °C) | 
| 245 VA 50 Hz cos phi 0.75 (at 20 °C) | |
| Hold-in power consumption in VA | 26 VA 60 Hz cos phi 0.3 (at 20 °C) | 
| Heat dissipation | 6…10 W at 50/60 Hz | 
| Operating time | 20…35 ms closing | 
| 6…20 ms opening | |
| Maximum operating rate | 3600 cyc/h 60 °C | 
| Connections – terminals | Control circuit: screw clamp terminals 2 1…2.5 mm² – cable stiffness: flexible with cable end | 
| Control circuit: screw clamp terminals 1 1…2.5 mm² – cable stiffness: flexible with cable end | |
| Control circuit: screw clamp terminals 1 1…4 mm² – cable stiffness: flexible without cable end | |
| Control circuit: screw clamp terminals 2 1…4 mm² – cable stiffness: flexible without cable end | |
| Control circuit: screw clamp terminals 1 1…4 mm² – cable stiffness: solid without cable end | |
| Control circuit: screw clamp terminals 2 1…4 mm² – cable stiffness: solid without cable end | |
| Power circuit: connector 1 4…50 mm² – cable stiffness: flexible without cable end | |
| Power circuit: connector 2 4…25 mm² – cable stiffness: flexible without cable end | |
| Power circuit: connector 1 4…50 mm² – cable stiffness: flexible with cable end | |
| Power circuit: connector 2 4…16 mm² – cable stiffness: flexible with cable end | |
| Power circuit: connector 1 4…50 mm² – cable stiffness: solid without cable end | |
| Power circuit: connector 2 4…25 mm² – cable stiffness: solid without cable end | |
| Tightening torque | Control circuit: 1.2 N.m – on screw clamp terminals – with screwdriver flat Ø 6 mm | 
| Control circuit: 1.2 N.m – on screw clamp terminals – with screwdriver Philips No 2 | |
| Power circuit: 12 N.m – on connector – with screwdriver flat Ø 6 to Ø 8 mm | |
| Power circuit: 12 N.m – on connector hexagonal screw head 4 mm | |
| Control circuit: 1.2 N.m – on screw clamp terminals – with screwdriver pozidriv No 2 | |
| Auxiliary contact composition | 1 NO + 1 NC | 
| Auxiliary contacts type | Type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1 | 
| type mirror contact 1 NC conforming to IEC 60947-4-1 | |
| Signalling circuit frequency | 25…400 Hz | 
| Minimum switching voltage | 17 V for signalling circuit | 
| Minimum switching current | 5 mA for signalling circuit | 
| Insulation resistance | > 10 MOhm for signalling circuit | 
| Non-overlap time | 1.5 ms on de-energisation between NC and NO contact | 
| 1.5 ms on energisation between NC and NO contact | |
| Mounting support | Plate | 
| Rail | |
| Environment | |
| Standards | EN/IEC 60947-1 | 
| EN/IEC 60947-4-1 | |
| EN/IEC 60947-5-1 | |
| UL 60947-4-1 | |
| UL 60947-5-1 | |
| CSA C22.2 No 60947-4-1 | |
| CSA C22.2 No 60947-5-1 | |
| GB/T 14048.4 | |
| Product certifications | IECEE CB Scheme | 
| UL | |
| CSA | |
| CCC | |
| EAC | |
| LROS (Lloyds register of shipping) | |
| RINA | |
| BV | |
| DNV-GL | |
| IP degree of protection | IP20 front face conforming to IEC 60529 | 
| Protective treatment | TH conforming to IEC 60068-2-30 | 
| Climatic withstand | Conforming to IACS E10 exposure to damp heat | 
| Permissible ambient air temperature around the device | -40…60 °C | 
| 60…70 °C with derating | |
| Operating altitude | 0…3000 m | 
| Fire resistance | 850 °C conforming to IEC 60695-2-1 | 
| Flame retardance | V1 conforming to UL 94 | 
| Mechanical robustness | Vibrations contactor open (2 Gn, 5…300 Hz) | 
| Shocks contactor open (8 Gn for 11 ms) | |
| Vibrations contactor closed (3 Gn, 5…300 Hz) | |
| Shocks contactor closed (10 Gn for 11 ms) | |
| Height | 127 mm | 
| Width | 85 mm | 
| Depth | 130 mm | 
| Product weight | 1.61 kg | 
| Packing Units | |
| Unit Type of Package 1 | PCE | 
| Number of Units in Package 1 | 1 | 
| Package 1 Height | 9.5 cm | 
| Package 1 Width | 13.5 cm | 
| Package 1 Length | 14 cm | 
| Package 1 Weight | 1.564 kg | 
| Unit Type of Package 2 | S02 | 
| Number of Units in Package 2 | 5 | 
| Package 2 Height | 15 cm | 
| Package 2 Width | 30 cm | 
| Package 2 Length | 40 cm | 
| Package 2 Weight | 8.275 kg | 
| Unit Type of Package 3 | P06 | 
| Number of Units in Package 3 | 80 | 
| Package 3 Height | 80 cm | 
| Package 3 Width | 80 cm | 
| Package 3 Length | 60 cm | 
| Package 3 Weight | 140.9 kg | 
| Contractual warranty | |
| Warranty | 18 months | 
| Weight | 1.610 kg | 
|---|---|
| Dimensions | 13 × 8.5 × 12.7 cm |