| Main | ||||
| Part Number | LC1D12B7C | LC1D12BDC | LC1D12CC7C | LC1D12E7C | 
| Product Series | TeSys Deca | TeSys Deca | TeSys Deca | TeSys Deca | 
| Product Series | TeSys Deca | TeSys Deca | TeSys Deca | TeSys Deca | 
| product type | Contactor | Contactor | Contactor | Contactor | 
| product short name | LC1D | LC1D | LC1D | LC1D | 
| Application field of contactor | Applied to AC loads with power factor greater than or equal to 0.95 Applied to non-inductive or slightly inductive loads, resistance furnaces | Applied to non-inductive or micro-inductive loads, and resistance furnaces to AC loads with a power factor greater than or equal to 0.95 | Applied to AC loads with power factor greater than or equal to 0.95 Applied to non-inductive or slightly inductive loads, resistance furnaces | Applied to AC loads with power factor greater than or equal to 0.95 Applied to non-inductive or slightly inductive loads, resistance furnaces | 
| use category | AC-4 AC-1 AC-3 AC-3e | AC-4 AC-1 AC-3 AC-3e | AC-4 AC-1 AC-3 AC-3e | AC-4 AC-1 AC-3 AC-3e | 
| number of poles | 3P | 3P | 3P | 3P | 
| Rated working voltage [Ue] | Power circuit: <= 690 V AC 25…400 Hz Power circuit: <= 300 V DC | Power circuit: <= 690 V AC 25…400 Hz Power circuit: <= 300 V DC | Power circuit: <= 690 V AC 25…400 Hz Power circuit: <= 300 V DC | Power circuit: <= 690 V AC 25…400 Hz Power circuit: <= 300 V DC | 
| Rated operating current [Ie] | 25 A 60 °C) at <= 440 V AC AC-1 for power circuit 12 A 60 °C) at <= 440 V AC AC-3 for power circuit 12 A 60 °C) at< = 440 V AC AC-3e for power circuit | 25 A 60 °C) at <= 440 V AC AC-1 for power circuit 12 A 60 °C) at <= 440 V AC AC-3 for power circuit 12 A 60 °C) at< = 440 V AC AC-3e for power circuit | 25 A 60 °C) at <= 440 V AC AC-1 for power circuit 12 A 60 °C) at <= 440 V AC AC-3 for power circuit 12 A 60 °C) at< = 440 V AC AC-3e for power circuit | 25 A 60 °C) at <= 440 V AC AC-1 for power circuit 12 A 60 °C) at <= 440 V AC AC-3 for power circuit 12 A 60 °C) at< = 440 V AC AC-3e for power circuit | 
| [Uc] control circuit voltage | 24 V AC 50/60 Hz | 24 V DC | 36 V AC 50/60 Hz | 48 V AC 50/60 Hz | 
| Additional information | ||||
| Motor power (kW) | 7.5 kW at 500 V AC 50/60 Hz (AC-3) 3 kW at 220/240 V AC 50/60 Hz (AC-3) 5.5 kW at 380/400 V AC 50/60 Hz (AC-3) 5.5 kW at 415/440 V AC 50/60 Hz (AC-3) 7.5 kW at 660/690 V AC 50/60 Hz (AC-3) 7.5 kW at 500 V AC 50/60 Hz (AC-3e) 3 kW at 220/240 V AC 50/60 Hz (AC-3e) 5.5 kW at 380/400 V AC 50/60 Hz (AC-3e) 5.5 kW at 415/440 V AC 50/60 Hz (AC-3e) 7.5 kW at 660/690 V AC 50/60 Hz (AC-3e) | 7.5 kW at 500 V AC 50/60 Hz (AC-3) 3 kW at 220/240 V AC 50/60 Hz (AC-3) 5.5 kW at 380/400 V AC 50/60 Hz (AC-3) 5.5 kW at 415/440 V AC 50/60 Hz (AC-3) 7.5 kW at 660/690 V AC 50/60 Hz (AC-3) 3.7 kW at 400 V AC 50/60 Hz (AC-4) 7.5 kW at 500 V AC 50/60 Hz (AC-3e) 3 kW at 220/240 V AC 50/60 Hz (AC-3e) 5.5 kW at… at 380/400 V AC 50/60 Hz (AC-3e) 5.5 kW at 415/440 V AC 50/60 Hz (AC-3e) 7.5 kW at 660/690 V AC 50/60 Hz (AC -3e) | 7.5 kW at 500 V AC 50/60 Hz (AC-3) 3 kW at 220/240 V AC 50/60 Hz (AC-3) 5.5 kW at 380/400 V AC 50/60 Hz (AC-3) 5.5 kW at 415/440 V AC 50/60 Hz (AC-3) 7.5 kW at 660/690 V AC 50/60 Hz (AC-3) 7.5 kW at 500 V AC 50/60 Hz (AC-3e) 3 kW at 220/240 V AC 50/60 Hz (AC-3e) 5.5 kW at 380/400 V AC 50/60 Hz (AC-3e) 5.5 kW at 415/440 V AC 50/60 Hz (AC-3e) 7.5 kW at 660/690 V AC 50/60 Hz (AC-3e) | 7.5 kW at 500 V AC 50/60 Hz (AC-3) 3 kW at 220/240 V AC 50/60 Hz (AC-3) 5.5 kW at 380/400 V AC 50/60 Hz (AC-3) 5.5 kW at 415/440 V AC 50/60 Hz (AC-3) 7.5 kW at 660/690 V AC 50/60 Hz (AC-3) 7.5 kW at 500 V AC 50/60 Hz (AC-3e) 3 kW at 220/240 V AC 50/60 Hz (AC-3e) 5.5 kW at 380/400 V AC 50/60 Hz (AC-3e) 5.5 kW at 415/440 V AC 50/60 Hz (AC-3e) 7.5 kW at 660/690 V AC 50/60 Hz (AC-3e) | 
| model | LC1D | LC1D | LC1D | LC1D | 
| Loop contact type | 3 NO | 3 NO | 3 NO | 3 NO | 
| protection cap | None | None | None | None | 
| Conventional thermal current [Ith] | 25 A at <60 °C for power circuits 10 A at <60 °C for signal circuits | 25 A at <60 °C for power circuits 10 A at <60 °C for signal circuits | 25 A at <60 °C for power circuits 10 A at <60 °C for signal circuits | 25 A at <60 °C for power circuits 10 A at <60 °C for signal circuits | 
| Rated short-time withstand current [Icw] | 105 A at <40 °C – 10 s for power circuit 210 A at <40 °C – 1 s for power circuit 30 A at <40 °C – 10 min for power circuit 61 A at <40 °C – 1 minute for power circuit 100 A – 1 s for signal circuit 120 A – 500 ms for signal circuit 140 A – 100 ms for signal circuit | 105 A at <40 °C – 10 s for power circuit 210 A at <40 °C – 1 s for power circuit 30 A at <40 °C – 10 min for power circuit 61 A at <40 °C – 1 minute for power circuit 100 A – 1 s for signal circuit 120 A – 500 ms for signal circuit 140 A – 100 ms for signal circuit | 105 A at <40 °C – 10 s for power circuit 210 A at <40 °C – 1 s for power circuit 30 A at <40 °C – 10 min for power circuit 61 A at <40 °C – 1 minute for power circuit 100 A – 1 s for signal circuit 120 A – 500 ms for signal circuit 140 A – 100 ms for signal circuit | 105 A at <40 °C – 10 s for power circuit 210 A at <40 °C – 1 s for power circuit 30 A at <40 °C – 10 min for power circuit 61 A at <40 °C – 1 minute for power circuit 100 A – 1 s for signal circuit 120 A – 500 ms for signal circuit 140 A – 100 ms for signal circuit | 
| Fuses for use with relays | 10 A gG for signal circuits according to IEC 60947-5-1 40 A gG at <= 690 V for power circuits type 1 25 A gG for power circuits for type 2 at <= 690 V | 10 A gG for signal circuits according to IEC 60947-5-1 40 A gG at <= 690 V for power circuits type 1 25 A gG for power circuits for type 2 at <= 690 V | 10 A gG for signal circuits according to IEC 60947-5-1 40 A gG at <= 690 V for power circuits type 1 25 A gG for power circuits for type 2 at <= 690 V | 10 A gG for signal circuits according to IEC 60947-5-1 40 A gG at <= 690 V for power circuits type 1 25 A gG for power circuits for type 2 at <= 690 V | 
| average impedance | 2.5 mΩ – Ith 25 A 50 Hz for power loop | 2.5 mΩ – Ith 25 A 50 Hz for power loop | 2.5 mΩ – Ith 25 A 50 Hz for power loop | 2.5 mΩ – Ith 25 A 50 Hz for power loop | 
| Rated insulation voltage [Ui] | Power circuit: 690 V conforming to IEC 60947-4-1 Signal circuit: 690 V conforming to IEC 60947-1 | Power circuit: 690 V conforming to IEC 60947-4-1 Signal circuit: 690 V conforming to IEC 60947-1 | Power circuit: 690 V conforming to IEC 60947-4-1 Signal circuit: 690 V conforming to IEC 60947-1 | Power circuit: 690 V conforming to IEC 60947-4-1 Signal circuit: 690 V conforming to IEC 60947-1 | 
| Overvoltage category | III | III | III | III | 
| pollution level | 3 | 3 | 3 | 3 | 
| Rated impulse withstand voltage [Uimp] | 6 kV according to IEC 60947 | 6 kV according to IEC 60947 | 6 kV according to IEC 60947 | 6 kV according to IEC 60947 | 
| Safety and reliability level | B10d = Contactor for 1369863 nominal loads according to EN/ISO 13849-1 B10d = Contactor for 20000000 mechanical loads according to EN/ISO 13849-1 | B10d = Contactor for 1369863 nominal loads according to EN/ISO 13849-1 B10d = Contactor for 20000000 mechanical loads according to EN/ISO 13849-1 | B10d = Contactor for 1369863 nominal loads according to EN/ISO 13849-1 B10d = Contactor for 20000000 mechanical loads according to EN/ISO 13849-1 | B10d = Contactor for 1369863 nominal loads according to EN/ISO 13849-1 B10d = Contactor for 20000000 mechanical loads according to EN/ISO 13849-1 | 
| Mechanical life | 15 Mcycles | 30 Mcycles | 15 Mcycles | 15 Mcycles | 
| Electrical life | 2 Mcycles 12 A AC-3 Ue <= 440 V 0.8 Mcycles 25 A AC-1 Ue <= 440 V 2.2 Mcycles 9 A AC-3 Ue 660/690 V 2 Mcycles 12 A AC-3e Ue <= 440 V at 2.2 Mcycles 9 A AC-3e at 660/690 V at Ue | 2 Mcycles 12 A AC-3 Ue <= 440 V 0.8 Mcycles 25 A AC-1 Ue <= 440 V 2.2 Mcycles 9 A AC-3 Ue 660/690 V 2 Mcycles 12 A AC-3e Ue <= 440 V at 2.2 Mcycles 9 A AC-3e at 660/690 V at Ue | 2 Mcycles 12 A AC-3 Ue <= 440 V 0.8 Mcycles 25 A AC-1 Ue <= 440 V 2.2 Mcycles 9 A AC-3 Ue 660/690 V 2 Mcycles 12 A AC-3e Ue <= 440 V at 2.2 Mcycles 9 A AC-3e at 660/690 V at Ue | 2 Mcycles 12 A AC-3 Ue <= 440 V 0.8 Mcycles 25 A AC-1 Ue <= 440 V 2.2 Mcycles 9 A AC-3 Ue 660/690 V 2 Mcycles 12 A AC-3e Ue <= 440 V at 2.2 Mcycles 9 A AC-3e at 660/690 V at Ue | 
| Control loop characteristics | AC at 50/60 Hz | DC standard | AC at 50/60 Hz | AC at 50/60 Hz | 
| Surge Suppression Module | No built-in surge suppression module | Built-in bidirectional peak current limiting diode | No built-in surge suppression module | No built-in surge suppression module | 
| Control voltage limit | 0.3…0.6 Uc -40…60 °C release 50/60 Hz 0.8…1.1 Uc -40…60 °C run 50 Hz 0.85…1.1 Uc -40…60 °C run 60 Hz | 0.1…0.25 Uc -40…60 °C release 0.7…1.25 Uc -40…60 °C run | 0.3…0.6 Uc -40…60 °C release 50/60 Hz 0.8…1.1 Uc -40…60 °C run 50 Hz 0.85…1.1 Uc -40…60 °C run 60 Hz | 0.3…0.6 Uc -40…60 °C release 50/60 Hz 0.8…1.1 Uc -40…60 °C run 50 Hz 0.85…1.1 Uc -40…60 °C run 60 Hz | 
| (~50Hz pickup) power consumption (VA) | 70 VA 60 Hz 0.75 20 °C) 70 VA 50 Hz 0.75 20 °C) | 70 VA 60 Hz 0.75 20 °C) 70 VA 50 Hz 0.75 20 °C) | 70 VA 60 Hz 0.75 20 °C) 70 VA 50 Hz 0.75 20 °C) | |
| (~50Hz hold) power consumption (VA) | 7.5 VA 60 Hz 0.3 20 °C) 7 VA 50 Hz 0.3 20 °C) | 7.5 VA 60 Hz 0.3 20 °C) 7 VA 50 Hz 0.3 20 °C) | 7.5 VA 60 Hz 0.3 20 °C) 7 VA 50 Hz 0.3 20 °C) | |
| heat dissipation | 2…3 W at 50/60 Hz | 2…3 W at 50/60 Hz | 2…3 W at 50/60 Hz | |
| action time | 12…22 ms close 4…19 ms break | 55 ms to close, 20 ms to break | 12…22 ms close 4…19 ms break | 12…22 ms close 4…19 ms break | 
| operating frequency | 3600 cycles/h at <60 °C | 3600 cycles/h at <60 °C | 3600 cycles/h at <60 °C | 3600 cycles/h at <60 °C | 
| Wiring capacity | Power circuit: screw fastening1 1…4 mm² Lug O.D. Ø: 8 mm Cable option: flexible cord without wire terminal Power Circuit: screw fastening2 1…4 mm² Lug O.D. Ø: 8 mm Cable Selection: flexible cord without wire terminals Power circuit: screw fastening1 1…4 mm² Lug outer diameter Ø: 8 mm Cable selection: flexible cord with wire terminal Power circuit: screw fastening2 1…2.5 mm² Lug outer diameter Ø: 8 mm Cable option: flexible with wire terminals Power circuit: screw fastening1 1…4 mm² Lug outer diameter Ø: 8 mm Cable option: Solid without wire terminals Power circuit : Bolt fastening2 1…4 mm² Lug O.D. Ø: 8 mm Cable option: Rigid without wire terminals Control circuit: Bolt tight1 1…4 mm² Cable option: Flexible wire without wire terminals Control circuit: screw-on2 1…4 mm² Cable option: flexible without cable terminals Control circuit: screw-on1 1…4 mm² cable option: flexible with cable terminals Control circuit: screw-on2 1…2.5 mm² cable selection: flexible wire with wire terminals control circuit: screw fastened1 1…4 mm² cable selection: rigid without wire terminal control circuit: screw fastened2 1…4 mm² cable selection : Hard wire without wire terminal | Power circuit: screw fastening1 1…4 mm² Lug O.D. Ø: 8 mm Cable option: flexible cord without wire terminal Power Circuit: screw fastening2 1…4 mm² Lug O.D. Ø: 8 mm Cable Selection: flexible cord without wire terminals Power circuit: screw fastening1 1…4 mm² Lug outer diameter Ø: 8 mm Cable selection: flexible cord with wire terminal Power circuit: screw fastening2 1…2.5 mm² Lug outer diameter Ø: 8 mm Cable option: flexible with wire terminals Power circuit: screw fastening1 1…4 mm² Lug outer diameter Ø: 8 mm Cable option: Solid without wire terminals Power circuit : Bolt fastening2 1…4 mm² Lug O.D. Ø: 8 mm Cable option: Rigid without wire terminals Control circuit: Bolt tight1 1…4 mm² Cable option: Flexible wire without wire terminals Control circuit: screw-on2 1…4 mm² Cable option: flexible without cable terminals Control circuit: screw-on1 1…4 mm² cable option: flexible with cable terminals Control circuit: screw-on2 1…2.5 mm² cable selection: flexible wire with wire terminals control circuit: screw fastened1 1…4 mm² cable selection: rigid without wire terminal control circuit: screw fastened2 1…4 mm² cable selection : Hard wire without wire terminal | Power circuit: screw fastening1 1…4 mm² Lug O.D. Ø: 8 mm Cable option: flexible cord without wire terminal Power Circuit: screw fastening2 1…4 mm² Lug O.D. Ø: 8 mm Cable Selection: flexible cord without wire terminals Power circuit: screw fastening1 1…4 mm² Lug outer diameter Ø: 8 mm Cable selection: flexible cord with wire terminal Power circuit: screw fastening2 1…2.5 mm² Lug outer diameter Ø: 8 mm Cable option: flexible with wire terminals Power circuit: screw fastening1 1…4 mm² Lug outer diameter Ø: 8 mm Cable option: Solid without wire terminals Power circuit : Bolt fastening2 1…4 mm² Lug O.D. Ø: 8 mm Cable option: Rigid without wire terminals Control circuit: Bolt tight1 1…4 mm² Cable option: Flexible wire without wire terminals Control circuit: screw-on2 1…4 mm² Cable option: flexible without cable terminals Control circuit: screw-on1 1…4 mm² cable option: flexible with cable terminals Control circuit: screw-on2 1…2.5 mm² cable selection: flexible wire with wire terminals control circuit: screw fastened1 1…4 mm² cable selection: rigid without wire terminal control circuit: screw fastened2 1…4 mm² cable selection : Hard wire without wire terminal | Power circuit: screw fastening1 1…4 mm² Lug O.D. Ø: 8 mm Cable option: flexible cord without wire terminal Power Circuit: screw fastening2 1…4 mm² Lug O.D. Ø: 8 mm Cable Selection: flexible cord without wire terminals Power circuit: screw fastening1 1…4 mm² Lug outer diameter Ø: 8 mm Cable selection: flexible cord with wire terminal Power circuit: screw fastening2 1…2.5 mm² Lug outer diameter Ø: 8 mm Cable option: flexible with wire terminals Power circuit: screw fastening1 1…4 mm² Lug outer diameter Ø: 8 mm Cable option: Solid without wire terminals Power circuit : Bolt fastening2 1…4 mm² Lug O.D. Ø: 8 mm Cable option: Rigid without wire terminals Control circuit: Bolt tight1 1…4 mm² Cable option: Flexible wire without wire terminals Control circuit: screw-on2 1…4 mm² Cable option: flexible without cable terminals Control circuit: screw-on1 1…4 mm² cable option: flexible with cable terminals Control circuit: screw-on2 1…2.5 mm² cable selection: flexible wire with wire terminals control circuit: screw fastened1 1…4 mm² cable selection: rigid without wire terminal control circuit: screw fastened2 1…4 mm² cable selection : Hard wire without wire terminal | 
| Tightening torque | Power circuit: 1.7 Nm via screwdriver Ø 6 flat power circuit: 1.7 Nm via screwdriver No 2 Phillips screw control circuit: 1.7 Nm via screwdriver Ø 6 flat control circuit: 1.7 Nm via screw Screwdriver No. 2 for fastening Phillips screw Power circuit: 1.7 Nm Screwdriver Ø 6 flat-blade screw via cable connector: M3.5 Power circuit : 1.7 Nm Phillips screw driver No. 2 via cable connector Screw: M3.5 Control circuit: 1.7 Nm Screwdriver pozidriv No 2 for screw tightening Power circuit: 1.7 Nm Screwdriver pozidriv No 2 for screw tightening | Power circuit: 1.7 Nm via screwdriver Ø 6 flat power circuit: 1.7 Nm via screwdriver No 2 Phillips screw control circuit: 1.7 Nm via screwdriver Ø 6 flat control circuit: 1.7 Nm via screw Screwdriver No. 2 for fastening Phillips screw Power circuit: 1.7 Nm Screwdriver Ø 6 flat-blade screw via cable connector: M3.5 Power circuit : 1.7 Nm Phillips screw driver No. 2 via cable connector Screw: M3.5 Control circuit: 1.7 Nm Screwdriver pozidriv No 2 for screw tightening Power circuit: 1.7 Nm Screwdriver pozidriv No 2 for screw tightening | Power circuit: 1.7 Nm via screwdriver Ø 6 flat power circuit: 1.7 Nm via screwdriver No 2 Phillips screw control circuit: 1.7 Nm via screwdriver Ø 6 flat control circuit: 1.7 Nm via screw Screwdriver No. 2 for fastening Phillips screw Power circuit: 1.7 Nm Screwdriver Ø 6 flat-blade screw via cable connector: M3.5 Power circuit : 1.7 Nm Phillips screw driver No. 2 via cable connector Screw: M3.5 Control circuit: 1.7 Nm Screwdriver pozidriv No 2 for screw tightening Power circuit: 1.7 Nm Screwdriver pozidriv No 2 for screw tightening | Power circuit: 1.7 Nm via screwdriver Ø 6 flat power circuit: 1.7 Nm via screwdriver No 2 Phillips screw control circuit: 1.7 Nm via screwdriver Ø 6 flat control circuit: 1.7 Nm via screw Screwdriver No. 2 for fastening Phillips screw Power circuit: 1.7 Nm Screwdriver Ø 6 flat-blade screw via cable connector: M3.5 Power circuit : 1.7 Nm Phillips screw driver No. 2 via cable connector Screw: M3.5 Control circuit: 1.7 Nm Screwdriver pozidriv No 2 for screw tightening Power circuit: 1.7 Nm Screwdriver pozidriv No 2 for screw tightening | 
| Auxiliary contact type | 1 NO + 1 NC | 1 NO + 1 NC | 1 NO + 1 NC | 1 NO + 1 NC | 
| Auxiliary contact type | Type Mechanical connection 1 NO + 1 NC conforming to IEC 60947-5-1 Type mirrored with main contact status 1 NC conforming to IEC 60947-4-1 | 1 NO + 1 NC | 1 NO + 1 NC | 1 NO + 1 NC | 
| Signal loop frequency | 25…400Hz | 25…400Hz | 25…400Hz | 25…400Hz | 
| Minimum switching voltage | 17 V for signal return | 17 V for signal return | 17 V for signal return | |
| Minimum switching current [Imin] | 5 mA for signal loop | 5 mA for signal loop | 5 mA for signal loop | 5 mA for signal loop | 
| Insulation resistance | > 10 MΩ for signal loops | > 10 MΩ for signal loops | > 10 MΩ for signal loops | > 10 MΩ for signal loops | 
| non-overlapping time | 1.5 ms between de-energized NC and NO contacts 1.5 ms between energized NC and NO contacts | 1.5 ms between de-energized NC and NO contacts 1.5 ms between energized NC and NO contacts | 1.5 ms between de-energized NC and NO contacts 1.5 ms between energized NC and NO contacts | 1.5 ms between de-energized NC and NO contacts 1.5 ms between energized NC and NO contacts | 
| installation method | DIN rail installation base plate installation | Chassis mounting rail installation | DIN rail installation base plate installation | DIN rail installation base plate installation | 
| environment | ||||
| standard | IEC 60947-4-1 GB 14048.4 | GB 14048.4 IEC 60947-4-1 | GB 14048.4 IEC 60947-4-1 | GB 14048.4 IEC 60947-4-1 | 
| certified product | CCC CE UKCA | CCC CE UKCA | CCC CE UKCA | CCC CE UKCA | 
| IP protection class | IP2x front panel for main circuits conforming to IEC 60529 IP2x front panel for coil circuits conforming to IEC 60529 | IP2x front panel for main circuits conforming to IEC 60529 IP2x front panel for coil circuits conforming to IEC 60529 | IP2x front panel for main circuits conforming to IEC 60529 IP2x front panel for coil circuits conforming to IEC 60529 | IP2x front panel for main circuits conforming to IEC 60529 IP2x front panel for coil circuits conforming to IEC 60529 | 
| Protective measures | TH conforms to IEC 60068-2-30 | TH conforms to IEC 60068-2-30 | TH conforms to IEC 60068-2-30 | TH conforms to IEC 60068-2-30 | 
| ambient air temperature | -40…60 °C operation 60…70 °C with derating -60…80 °C storage | -40…60 °C operation 60…70 °C with derating -60…80 °C storage | -40…60 °C operation 60…70 °C with derating -60…80 °C storage | -40…60 °C operation 60…70 °C with derating -60…80 °C storage | 
| working altitude | 3000 m None | 3000 m None | 3000 m None | 3000 m None | 
| Fire resistance and abnormal high temperature resistance | 850 °C conforming to IEC 60695-2-11 | 850 °C conforming to IEC 60695-2-11 | 850 °C conforming to IEC 60695-2-11 | 850 °C conforming to IEC 60695-2-11 | 
| Shock and vibration resistance | Shock resistance with contacts open (2 gn (5…300 Hz)) conforming to IEC 60068-2-6 Shock resistance with contacts closed ( 4 gn (5…300 Hz)) conforming to IEC 60068-2-6 Shock performance 11 ms with contacts open (10 gn) conforming to IEC 60068-2-27 Shock resistance 11 ms with contacts closed (15 gn) conforming to IEC 60068-2-27 | Shock resistance with contacts open (2 gn (5…300 Hz)) conforming to IEC 60068-2-6 Shock resistance with contacts closed ( 4 gn (5…300 Hz)) conforming to IEC 60068-2-6 Shock performance 11 ms with contacts open (10 gn) conforming to IEC 60068-2-27 Shock resistance 11 ms with contacts closed (15 gn) conforming to IEC 60068-2-27 | Shock resistance with contacts open (2 gn (5…300 Hz)) conforming to IEC 60068-2-6 Shock resistance with contacts closed ( 4 gn (5…300 Hz)) conforming to IEC 60068-2-6 Shock performance 11 ms with contacts open (10 gn) conforming to IEC 60068-2-27 Shock resistance 11 ms with contacts closed (15 gn) conforming to IEC 60068-2-27 | Shock resistance with contacts open (2 gn (5…300 Hz)) conforming to IEC 60068-2-6 Shock resistance with contacts closed ( 4 gn (5…300 Hz)) conforming to IEC 60068-2-6 Shock performance 11 ms with contacts open (10 gn) conforming to IEC 60068-2-27 Shock resistance 11 ms with contacts closed (15 gn) conforming to IEC 60068-2-27 | 
| high | 77 mm | 77 mm | 77 mm | 77 mm | 
| width | 45 mm | 45 mm | 45 mm | 45 mm | 
| depth | 86 mm | 95 mm | 86 mm | 86 mm | 
| Product Weight | 0.325 kg | 0.325 kg | 0.325 kg | 0.325 kg | 
| packaging unit | ||||
| Unit Type of Package 1 | PCE | PCE | PCE | PCE | 
| Number of Units in Package 1 | 1 | 1 | 1 | 1 | 
| Package 1 Height | 5.7cm | 5.46cm | 5.152 cm | 5.096 cm | 
| Package 1 Width | 8.2 cm | 7.939 cm | 7.874 cm | 7.903 cm | 
| Package 1 Length | 9.5cm | 10.397 cm | 9.441 cm | 9.324 cm | 
| Package 1 Weight | 357.0g | 519.8g | 341.0g | 355.5g | 
| Unit Type of Package 2 | S02 | S02 | S02 | S02 | 
| Number of Units in Package 2 | Twenty four | Twenty one | Twenty four | Twenty four | 
| Package 2 Height | 15.0cm | 15.0cm | 15.0cm | 15.0cm | 
| Package 2 Width | 30.0cm | 30.0cm | 30.0cm | 30.0cm | 
| Package 2 Length | 40.0cm | 40.0cm | 40.0cm | 40.0cm | 
| Package 2 Weight | 8.931kg | 11.0 kg | 8.771kg | 9.0 kg | 
| Unit Type of Package 3 | PAL | PAL | PAL | PAL | 
| Number of Units in Package 3 | 384 | 336 | 384 | 384 | 
| Package 3 Height | 60.0cm | 60.0cm | 60.0cm | 60.0cm | 
| Package 3 Width | 80.0cm | 80.0cm | 80.0cm | 80.0cm | 
| Package 3 Length | 75.0cm | 75.0cm | 75.0cm | 75.0cm | 
| Package 3 Weight | 147.488 kg | 182.632kg | 130.994kg | 130.336 kg | 
| contract warranty | ||||
| Warranty | 18 months | 18 months | 18 months | 18 months | 
| Main | ||||
| Part Number | LC1D12F7C | LC1D12FDC | LC1D12M7C | LC1D12Q7C | 
| Product Series | TeSys Deca | TeSys Deca | TeSys Deca | TeSys Deca | 
| Product Series | TeSys Deca | TeSys Deca | TeSys Deca | TeSys Deca | 
| product type | Contactor | Contactor | Contactor | Contactor | 
| product short name | LC1D | LC1D | LC1D | LC1D | 
| Application field of contactor | Applied to non-inductive or micro-inductive loads, and resistance furnaces to AC loads with a power factor greater than or equal to 0.95 | Applied to non-inductive or micro-inductive loads, and resistance furnaces to AC loads with a power factor greater than or equal to 0.95 | Applied to AC loads with power factor greater than or equal to 0.95 Applied to non-inductive or slightly inductive loads, resistance furnaces | Applied to AC loads with power factor greater than or equal to 0.95 Applied to non-inductive or slightly inductive loads, resistance furnaces | 
| use category | AC-4 AC-1 AC-3 AC-3e | AC-4 AC-1 AC-3 AC-3e | AC-4 AC-1 AC-3 AC-3e | AC-4 AC-1 AC-3 AC-3e | 
| number of poles | 3P | 3P | 3P | 3P | 
| Rated working voltage [Ue] | Power circuit: <= 690 V AC 25…400 Hz Power circuit: <= 300 V DC | Power circuit: <= 690 V AC 25…400 Hz Power circuit: <= 300 V DC | Power circuit: <= 690 V AC 25…400 Hz Power circuit: <= 300 V DC | Power circuit: <= 690 V AC 25…400 Hz Power circuit: <= 300 V DC | 
| Rated operating current [Ie] | 25 A 60 °C) at <= 440 V AC AC-1 for power circuit 12 A 60 °C) at <= 440 V AC AC-3 for power circuit 12 A 60 °C) at< = 440 V AC AC-3e for power circuit | 25 A 60 °C) at <= 440 V AC AC-1 for power circuit 12 A 60 °C) at <= 440 V AC AC-3 for power circuit 12 A 60 °C) at< = 440 V AC AC-3e for power circuit | 25 A 60 °C) at <= 440 V AC AC-1 for power circuit 12 A 60 °C) at <= 440 V AC AC-3 for power circuit 12 A 60 °C) at< = 440 V AC AC-3e for power circuit | 25 A 60 °C) at <= 440 V AC AC-1 for power circuit 12 A 60 °C) at <= 440 V AC AC-3 for power circuit 12 A 60 °C) at< = 440 V AC AC-3e for power circuit | 
| [Uc] control circuit voltage | 110V AC 50/60Hz | 110V DC | 230V AC 50/60Hz | 380 V AC 50/60 Hz | 
| Additional information | ||||
| Motor power (kW) | 7.5 kW at 500 V AC 50/60 Hz (AC-3) 3 kW at 220/240 V AC 50/60 Hz (AC-3) 5.5 kW at 380/400 V AC 50/60 Hz (AC-3) 5.5 kW at 415/440 V AC 50/60 Hz (AC-3) 7.5 kW at 660/690 V AC 50/60 Hz (AC-3) 7.5 kW at 500 V AC 50/60 Hz (AC-3e) 3 kW at 220/240 V AC 50/60 Hz (AC-3e) 5.5 kW at 380/400 V AC 50/60 Hz (AC-3e) 5.5 kW at 415/440 V AC 50/60 Hz (AC-3e) 7.5 kW at 660/690 V AC 50/60 Hz (AC-3e) | 7.5 kW at 500 V AC 50/60 Hz (AC-3) 3 kW at 220/240 V AC 50/60 Hz (AC-3) 5.5 kW at 380/400 V AC 50/60 Hz (AC-3) 5.5 kW at 415/440 V AC 50/60 Hz (AC-3) 7.5 kW at 660/690 V AC 50/60 Hz (AC-3) 7.5 kW at 500 V AC 50/60 Hz (AC-3e) 3 kW at 220/240 V AC 50/60 Hz (AC-3e) 5.5 kW at 380/400 V AC 50/60 Hz (AC-3e) 5.5 kW at 415/440 V AC 50/60 Hz (AC-3e) 7.5 kW at 660/690 V AC 50/60 Hz (AC-3e) | 7.5 kW at 500 V AC 50/60 Hz (AC-3) 3 kW at 220/240 V AC 50/60 Hz (AC-3) 5.5 kW at 380/400 V AC 50/60 Hz (AC-3) 5.5 kW at 415/440 V AC 50/60 Hz (AC-3) 7.5 kW at 660/690 V AC 50/60 Hz (AC-3) 3.7 kW at 400 V AC 50/60 Hz (AC-4) 7.5 kW at 500 V AC 50/60 Hz (AC-3e) 3 kW at 220/240 V AC 50/60 Hz (AC-3e) 5.5 kW at… at 380/400 V AC 50/60 Hz (AC-3e) 5.5 kW at 415/440 V AC 50/60 Hz (AC-3e) 7.5 kW at 660/690 V AC 50/60 Hz (AC -3e) | 7.5 kW at 500 V AC 50/60 Hz (AC-3) 3 kW at 220/240 V AC 50/60 Hz (AC-3) 5.5 kW at 380/400 V AC 50/60 Hz (AC-3) 5.5 kW at 415/440 V AC 50/60 Hz (AC-3) 7.5 kW at 660/690 V AC 50/60 Hz (AC-3) 3.7 kW at 400 V AC 50/60 Hz (AC-4) 7.5 kW at 500 V AC 50/60 Hz (AC-3e) 3 kW at 220/240 V AC 50/60 Hz (AC-3e) 5.5 kW at… at 380/400 V AC 50/60 Hz (AC-3e) 5.5 kW at 415/440 V AC 50/60 Hz (AC-3e) 7.5 kW at 660/690 V AC 50/60 Hz (AC -3e) | 
| model | LC1D | LC1D | LC1D | LC1D | 
| Loop contact type | 3 NO | 3 NO | 3 NO | 3 NO | 
| protection cap | None | None | None | None | 
| Conventional thermal current [Ith] | 25 A at <60 °C for power circuits 10 A at <60 °C for signal circuits | 25 A at <60 °C for power circuits 10 A at <60 °C for signal circuits | 25 A at <60 °C for power circuits 10 A at <60 °C for signal circuits | 25 A at <60 °C for power circuits 10 A at <60 °C for signal circuits | 
| Rated short-time withstand current [Icw] | 105 A at <40 °C – 10 s for power circuit 210 A at <40 °C – 1 s for power circuit 30 A at <40 °C – 10 min for power circuit 61 A at <40 °C – 1 minute for power circuit 100 A – 1 s for signal circuit 120 A – 500 ms for signal circuit 140 A – 100 ms for signal circuit | 105 A at <40 °C – 10 s for power circuit 210 A at <40 °C – 1 s for power circuit 30 A at <40 °C – 10 min for power circuit 61 A at <40 °C – 1 minute for power circuit 100 A – 1 s for signal circuit 120 A – 500 ms for signal circuit 140 A – 100 ms for signal circuit | 105 A at <40 °C – 10 s for power circuit 210 A at <40 °C – 1 s for power circuit 30 A at <40 °C – 10 min for power circuit 61 A at <40 °C – 1 minute for power circuit 100 A – 1 s for signal circuit 120 A – 500 ms for signal circuit 140 A – 100 ms for signal circuit | 105 A at <40 °C – 10 s for power circuit 210 A at <40 °C – 1 s for power circuit 30 A at <40 °C – 10 min for power circuit 61 A at <40 °C – 1 minute for power circuit 100 A – 1 s for signal circuit 120 A – 500 ms for signal circuit 140 A – 100 ms for signal circuit | 
| Fuses for use with relays | 10 A gG for signal circuits according to IEC 60947-5-1 40 A gG at <= 690 V for power circuits type 1 25 A gG for power circuits for type 2 at <= 690 V | 10 A gG for signal circuits according to IEC 60947-5-1 40 A gG at <= 690 V for power circuits type 1 25 A gG for power circuits for type 2 at <= 690 V | 10 A gG for signal circuits according to IEC 60947-5-1 40 A gG at <= 690 V for power circuits type 1 25 A gG for power circuits for type 2 at <= 690 V | 10 A gG for signal circuits according to IEC 60947-5-1 40 A gG at <= 690 V for power circuits type 1 25 A gG for power circuits for type 2 at <= 690 V | 
| average impedance | 2.5 mΩ – Ith 25 A 50 Hz for power loop | 2.5 mΩ – Ith 25 A 50 Hz for power loop | 2.5 mΩ – Ith 25 A 50 Hz for power loop | 2.5 mΩ – Ith 25 A 50 Hz for power loop | 
| Rated insulation voltage [Ui] | Power circuit: 690 V conforming to IEC 60947-4-1 Signal circuit: 690 V conforming to IEC 60947-1 | Power circuit: 690 V conforming to IEC 60947-4-1 Signal circuit: 690 V conforming to IEC 60947-1 | Power circuit: 690 V conforming to IEC 60947-4-1 Signal circuit: 690 V conforming to IEC 60947-1 | Power circuit: 690 V conforming to IEC 60947-4-1 Signal circuit: 690 V conforming to IEC 60947-1 | 
| Overvoltage category | III | III | III | III | 
| pollution level | 3 | 3 | 3 | 3 | 
| Rated impulse withstand voltage [Uimp] | 6 kV according to IEC 60947 | 6 kV according to IEC 60947 | 6 kV according to IEC 60947 | 6 kV according to IEC 60947 | 
| Safety and reliability level | B10d = Contactor for 1369863 nominal loads according to EN/ISO 13849-1 B10d = Contactor for 20000000 mechanical loads according to EN/ISO 13849-1 | B10d = Contactor for 1369863 nominal loads according to EN/ISO 13849-1 B10d = Contactor for 20000000 mechanical loads according to EN/ISO 13849-1 | B10d = Contactor for 1369863 nominal loads according to EN/ISO 13849-1 B10d = Contactor for 20000000 mechanical loads according to EN/ISO 13849-1 | B10d = Contactor for 1369863 nominal loads according to EN/ISO 13849-1 B10d = Contactor for 20000000 mechanical loads according to EN/ISO 13849-1 | 
| Mechanical life | 15 Mcycles | 30 Mcycles | 15 Mcycles | 15 Mcycles | 
| Electrical life | 2 Mcycles 12 A AC-3 Ue <= 440 V 0.8 Mcycles 25 A AC-1 Ue <= 440 V 2.2 Mcycles 9 A AC-3 Ue 660/690 V 2 Mcycles 12 A AC-3e Ue <= 440 V at 2.2 Mcycles 9 A AC-3e at 660/690 V at Ue | 2 Mcycles 12 A AC-3 Ue <= 440 V 0.8 Mcycles 25 A AC-1 Ue <= 440 V 2.2 Mcycles 9 A AC-3 Ue 660/690 V 2 Mcycles 12 A AC-3e Ue <= 440 V at 2.2 Mcycles 9 A AC-3e at 660/690 V at Ue | 2 Mcycles 12 A AC-3 Ue <= 440 V 0.8 Mcycles 25 A AC-1 Ue <= 440 V 2.2 Mcycles 9 A AC-3 Ue 660/690 V 2 Mcycles 12 A AC-3e Ue <= 440 V at 2.2 Mcycles 9 A AC-3e at 660/690 V at Ue | 2 Mcycles 12 A AC-3 Ue <= 440 V 0.8 Mcycles 25 A AC-1 Ue <= 440 V 2.2 Mcycles 9 A AC-3 Ue 660/690 V 2 Mcycles 12 A AC-3e Ue <= 440 V at 2.2 Mcycles 9 A AC-3e at 660/690 V at Ue | 
| Control loop characteristics | AC at 50/60 Hz | DC standard | AC at 50/60 Hz | AC at 50/60 Hz | 
| Surge Suppression Module | No built-in surge suppression module | Built-in bidirectional peak current limiting diode | No built-in surge suppression module | No built-in surge suppression module | 
| Control voltage limit | 0.3…0.6 Uc -40…60 °C release 50/60 Hz 0.8…1.1 Uc -40…60 °C run 50 Hz 0.85…1.1 Uc -40…60 °C run 60 Hz | 0.1…0.25 Uc -40…60 °C release 0.7…1.25 Uc -40…60 °C run | 0.3…0.6 Uc -40…60 °C release 50/60 Hz 0.8…1.1 Uc -40…60 °C run 50 Hz 0.85…1.1 Uc -40…60 °C run 60 Hz | 0.3…0.6 Uc -40…60 °C release 50/60 Hz 0.8…1.1 Uc -40…60 °C run 50 Hz 0.85…1.1 Uc -40…60 °C run 60 Hz | 
| (~50Hz pickup) power consumption (VA) | 70 VA 60 Hz 0.75 20 °C) 70 VA 50 Hz 0.75 20 °C) | 70 VA 60 Hz 0.75 20 °C) 70 VA 50 Hz 0.75 20 °C) | 70 VA 60 Hz 0.75 20 °C) 70 VA 50 Hz 0.75 20 °C) | |
| (~50Hz hold) power consumption (VA) | 7.5 VA 60 Hz 0.3 20 °C) 7 VA 50 Hz 0.3 20 °C) | 7.5 VA 60 Hz 0.3 20 °C) 7 VA 50 Hz 0.3 20 °C) | 7.5 VA 60 Hz 0.3 20 °C) 7 VA 50 Hz 0.3 20 °C) | |
| heat dissipation | 2…3 W at 50/60 Hz | 2…3 W at 50/60 Hz | 2…3 W at 50/60 Hz | |
| action time | 12…22 ms close 4…19 ms break | 55 ms to close, 20 ms to break | 12…22 ms close 4…19 ms break | 12…22 ms close 4…19 ms break | 
| operating frequency | 3600 cycles/h at <60 °C | 3600 cycles/h at <60 °C | 3600 cycles/h at <60 °C | 3600 cycles/h at <60 °C | 
| Wiring capacity | Power circuit: screw fastening1 1…4 mm² Lug O.D. Ø: 8 mm Cable option: flexible cord without wire terminal Power Circuit: screw fastening2 1…4 mm² Lug O.D. Ø: 8 mm Cable Selection: flexible cord without wire terminals Power circuit: screw fastening1 1…4 mm² Lug outer diameter Ø: 8 mm Cable selection: flexible cord with wire terminal Power circuit: screw fastening2 1…2.5 mm² Lug outer diameter Ø: 8 mm Cable option: flexible with wire terminals Power circuit: screw fastening1 1…4 mm² Lug outer diameter Ø: 8 mm Cable option: Solid without wire terminals Power circuit : Bolt fastening2 1…4 mm² Lug O.D. Ø: 8 mm Cable option: Rigid without wire terminals Control circuit: Bolt tight1 1…4 mm² Cable option: Flexible wire without wire terminals Control circuit: screw-on2 1…4 mm² Cable option: flexible without cable terminals Control circuit: screw-on1 1…4 mm² cable option: flexible with cable terminals Control circuit: screw-on2 1…2.5 mm² cable selection: flexible wire with wire terminals control circuit: screw fastened1 1…4 mm² cable selection: rigid without wire terminal control circuit: screw fastened2 1…4 mm² cable selection : Hard wire without wire terminal | Power circuit: screw fastening1 1…4 mm² Lug O.D. Ø: 8 mm Cable option: flexible cord without wire terminal Power Circuit: screw fastening2 1…4 mm² Lug O.D. Ø: 8 mm Cable Selection: flexible cord without wire terminals Power circuit: screw fastening1 1…4 mm² Lug outer diameter Ø: 8 mm Cable selection: flexible cord with wire terminal Power circuit: screw fastening2 1…2.5 mm² Lug outer diameter Ø: 8 mm Cable option: flexible with wire terminals Power circuit: screw fastening1 1…4 mm² Lug outer diameter Ø: 8 mm Cable option: Solid without wire terminals Power circuit : Bolt fastening2 1…4 mm² Lug O.D. Ø: 8 mm Cable option: Rigid without wire terminals Control circuit: Bolt tight1 1…4 mm² Cable option: Flexible wire without wire terminals Control circuit: screw-on2 1…4 mm² Cable option: flexible without cable terminals Control circuit: screw-on1 1…4 mm² cable option: flexible with cable terminals Control circuit: screw-on2 1…2.5 mm² cable selection: flexible wire with wire terminals control circuit: screw fastened1 1…4 mm² cable selection: rigid without wire terminal control circuit: screw fastened2 1…4 mm² cable selection : Hard wire without wire terminal | Power circuit: screw fastening1 1…4 mm² Lug O.D. Ø: 8 mm Cable option: flexible cord without wire terminal Power Circuit: screw fastening2 1…4 mm² Lug O.D. Ø: 8 mm Cable Selection: flexible cord without wire terminals Power circuit: screw fastening1 1…4 mm² Lug outer diameter Ø: 8 mm Cable selection: flexible cord with wire terminal Power circuit: screw fastening2 1…2.5 mm² Lug outer diameter Ø: 8 mm Cable option: flexible with wire terminals Power circuit: screw fastening1 1…4 mm² Lug outer diameter Ø: 8 mm Cable option: Solid without wire terminals Power circuit : Bolt fastening2 1…4 mm² Lug O.D. Ø: 8 mm Cable option: Rigid without wire terminals Control circuit: Bolt tight1 1…4 mm² Cable option: Flexible wire without wire terminals Control circuit: screw-on2 1…4 mm² Cable option: flexible without cable terminals Control circuit: screw-on1 1…4 mm² cable option: flexible with cable terminals Control circuit: screw-on2 1…2.5 mm² cable selection: flexible wire with wire terminals control circuit: screw fastened1 1…4 mm² cable selection: rigid without wire terminal control circuit: screw fastened2 1…4 mm² cable selection : Hard wire without wire terminal | Power circuit: screw fastening1 1…4 mm² Lug O.D. Ø: 8 mm Cable option: flexible cord without wire terminal Power Circuit: screw fastening2 1…4 mm² Lug O.D. Ø: 8 mm Cable Selection: flexible cord without wire terminals Power circuit: screw fastening1 1…4 mm² Lug outer diameter Ø: 8 mm Cable selection: flexible cord with wire terminal Power circuit: screw fastening2 1…2.5 mm² Lug outer diameter Ø: 8 mm Cable option: flexible with wire terminals Power circuit: screw fastening1 1…4 mm² Lug outer diameter Ø: 8 mm Cable option: Solid without wire terminals Power circuit : Bolt fastening2 1…4 mm² Lug O.D. Ø: 8 mm Cable option: Rigid without wire terminals Control circuit: Bolt tight1 1…4 mm² Cable option: Flexible wire without wire terminals Control circuit: screw-on2 1…4 mm² Cable option: flexible without cable terminals Control circuit: screw-on1 1…4 mm² cable option: flexible with cable terminals Control circuit: screw-on2 1…2.5 mm² cable selection: flexible wire with wire terminals control circuit: screw fastened1 1…4 mm² cable selection: rigid without wire terminal control circuit: screw fastened2 1…4 mm² cable selection : Hard wire without wire terminal | 
| Tightening torque | Power circuit: 1.7 Nm via screwdriver Ø 6 flat power circuit: 1.7 Nm via screwdriver No 2 Phillips screw control circuit: 1.7 Nm via screwdriver Ø 6 flat control circuit: 1.7 Nm via screw Screwdriver No. 2 for fastening Phillips screw Power circuit: 1.7 Nm Screwdriver Ø 6 flat-blade screw via cable connector: M3.5 Power circuit : 1.7 Nm Phillips screw driver No. 2 via cable connector Screw: M3.5 Control circuit: 1.7 Nm Screwdriver pozidriv No 2 for screw tightening Power circuit: 1.7 Nm Screwdriver pozidriv No 2 for screw tightening | Power circuit: 1.7 Nm via screwdriver Ø 6 flat power circuit: 1.7 Nm via screwdriver No 2 Phillips screw control circuit: 1.7 Nm via screwdriver Ø 6 flat control circuit: 1.7 Nm via screw Screwdriver No. 2 for fastening Phillips screw Power circuit: 1.7 Nm Screwdriver Ø 6 flat-blade screw via cable connector: M3.5 Power circuit : 1.7 Nm Phillips screw driver No. 2 via cable connector Screw: M3.5 Control circuit: 1.7 Nm Screwdriver pozidriv No 2 for screw tightening Power circuit: 1.7 Nm Screwdriver pozidriv No 2 for screw tightening | Power circuit: 1.7 Nm via screwdriver Ø 6 flat power circuit: 1.7 Nm via screwdriver No 2 Phillips screw control circuit: 1.7 Nm via screwdriver Ø 6 flat control circuit: 1.7 Nm via screw Screwdriver No. 2 for fastening Phillips screw Power circuit: 1.7 Nm Screwdriver Ø 6 flat-blade screw via cable connector: M3.5 Power circuit : 1.7 Nm Phillips screw driver No. 2 via cable connector Screw: M3.5 Control circuit: 1.7 Nm Screwdriver pozidriv No 2 for screw tightening Power circuit: 1.7 Nm Screwdriver pozidriv No 2 for screw tightening | Power circuit: 1.7 Nm via screwdriver Ø 6 flat power circuit: 1.7 Nm via screwdriver No 2 Phillips screw control circuit: 1.7 Nm via screwdriver Ø 6 flat control circuit: 1.7 Nm via screw Screwdriver No. 2 for fastening Phillips screw Power circuit: 1.7 Nm Screwdriver Ø 6 flat-blade screw via cable connector: M3.5 Power circuit : 1.7 Nm Phillips screw driver No. 2 via cable connector Screw: M3.5 Control circuit: 1.7 Nm Screwdriver pozidriv No 2 for screw tightening Power circuit: 1.7 Nm Screwdriver pozidriv No 2 for screw tightening | 
| Auxiliary contact type | 1 NO + 1 NC | 1 NO + 1 NC | 1 NO + 1 NC | 1 NO + 1 NC | 
| Auxiliary contact type | Type Mechanical connection 1 NO + 1 NC conforming to IEC 60947-5-1 Type mirrored with main contact status 1 NC conforming to IEC 60947-4-1 | 1 NO + 1 NC | 1 NO + 1 NC | 1 NO + 1 NC | 
| Signal loop frequency | 25…400Hz | 25…400Hz | 25…400Hz | 25…400Hz | 
| Minimum switching voltage | 17 V for signal return | 17 V for signal return | 17 V for signal return | 17 V for signal return | 
| Minimum switching current [Imin] | 5 mA for signal loop | 5 mA for signal loop | 5 mA for signal loop | 5 mA for signal loop | 
| Insulation resistance | > 10 MΩ for signal loops | > 10 MΩ for signal loops | > 10 MΩ for signal loops | > 10 MΩ for signal loops | 
| non-overlapping time | 1.5 ms between de-energized NC and NO contacts 1.5 ms between energized NC and NO contacts | 1.5 ms between de-energized NC and NO contacts 1.5 ms between energized NC and NO contacts | 1.5 ms between de-energized NC and NO contacts 1.5 ms between energized NC and NO contacts | 1.5 ms between de-energized NC and NO contacts 1.5 ms between energized NC and NO contacts | 
| installation method | DIN rail installation base plate installation | DIN rail installation base plate installation | Chassis mounting rail installation | DIN rail installation base plate installation | 
| environment | ||||
| standard | GB 14048.4 IEC 60947-4-1 | IEC 60947-4-1 GB 14048.4 | GB 14048.4 IEC 60947-4-1 | GB 14048.4 IEC 60947-4-1 | 
| certified product | CCC CE UKCA | CCC CE UKCA | CCC CE UKCA | CCC CE UKCA | 
| IP protection class | IP2x front panel for main circuits conforming to IEC 60529 IP2x front panel for coil circuits conforming to IEC 60529 | IP2x front panel for main circuits conforming to IEC 60529 IP2x front panel for coil circuits conforming to IEC 60529 | IP2x front panel for main circuits conforming to IEC 60529 IP2x front panel for coil circuits conforming to IEC 60529 | IP2x front panel for main circuits conforming to IEC 60529 IP2x front panel for coil circuits conforming to IEC 60529 | 
| Protective measures | TH conforms to IEC 60068-2-30 | TH conforms to IEC 60068-2-30 | TH conforms to IEC 60068-2-30 | TH conforms to IEC 60068-2-30 | 
| ambient air temperature | -40…60 °C operation 60…70 °C with derating -60…80 °C storage | -40…60 °C operation 60…70 °C with derating -60…80 °C storage | -40…60 °C operation 60…70 °C with derating -60…80 °C storage | -40…60 °C operation 60…70 °C with derating -60…80 °C storage | 
| working altitude | 3000 m None | 3000 m None | 3000 m None | 3000 m None | 
| Fire resistance and abnormal high temperature resistance | 850 °C conforming to IEC 60695-2-11 | 850 °C conforming to IEC 60695-2-11 | 850 °C conforming to IEC 60695-2-11 | 850 °C conforming to IEC 60695-2-11 | 
| Shock and vibration resistance | Shock resistance with contacts open (2 gn (5…300 Hz)) conforming to IEC 60068-2-6 Shock resistance with contacts closed ( 4 gn (5…300 Hz)) conforming to IEC 60068-2-6 Shock performance 11 ms with contacts open (10 gn) conforming to IEC 60068-2-27 Shock resistance 11 ms with contacts closed (15 gn) conforming to IEC 60068-2-27 | Shock resistance with contacts open (2 gn (5…300 Hz)) conforming to IEC 60068-2-6 Shock resistance with contacts closed ( 4 gn (5…300 Hz)) conforming to IEC 60068-2-6 Shock performance 11 ms with contacts open (10 gn) conforming to IEC 60068-2-27 Shock resistance 11 ms with contacts closed (15 gn) conforming to IEC 60068-2-27 | Shock resistance with contacts open (2 gn (5…300 Hz)) conforming to IEC 60068-2-6 Shock resistance with contacts closed ( 4 gn (5…300 Hz)) conforming to IEC 60068-2-6 Shock performance 11 ms with contacts open (10 gn) conforming to IEC 60068-2-27 Shock resistance 11 ms with contacts closed (15 gn) conforming to IEC 60068-2-27 | Shock resistance with contacts open (2 gn (5…300 Hz)) conforming to IEC 60068-2-6 Shock resistance with contacts closed ( 4 gn (5…300 Hz)) conforming to IEC 60068-2-6 Shock performance 11 ms with contacts open (10 gn) conforming to IEC 60068-2-27 Shock resistance 11 ms with contacts closed (15 gn) conforming to IEC 60068-2-27 | 
| high | 77 mm | 77 mm | 77 mm | 77 mm | 
| width | 45 mm | 45 mm | 45 mm | 45 mm | 
| depth | 86 mm | 95 mm | 86 mm | 86 mm | 
| Product Weight | 0.325 kg | 0.325 kg | 0.325 kg | 0.325 kg | 
| packaging unit | ||||
| Unit Type of Package 1 | PCE | PCE | PCE | PCE | 
| Number of Units in Package 1 | 1 | 1 | 1 | 1 | 
| Package 1 Height | 5.108 cm | 5.402 cm | 5.05cm | 4.893 cm | 
| Package 1 Width | 8.0cm | 7.925 cm | 7.93cm | 7.759 cm | 
| Package 1 Length | 9.477 cm | 10.333 cm | 9.19 cm | 9.158 cm | 
| Package 1 Weight | 341.0g | 510.0g | 345.0g | 350.3g | 
| Unit Type of Package 2 | S02 | S02 | S02 | CAR | 
| Number of Units in Package 2 | Twenty four | Twenty one | Twenty four | Twenty four | 
| Package 2 Height | 15.0cm | 15.0cm | 15.0cm | 14.5cm | 
| Package 2 Width | 30.0cm | 30.0cm | 30.0cm | 29.4 cm | 
| Package 2 Length | 40.0cm | 40.0cm | 40.0cm | 39.4 cm | 
| Package 2 Weight | 8.86kg | 11.181kg | 8.79kg | 9.0 kg | 
| Unit Type of Package 3 | PAL | PAL | PAL | PAL | 
| Number of Units in Package 3 | 384 | 336 | 384 | 384 | 
| Package 3 Height | 60.0cm | 60.0cm | 60.0cm | 60.0cm | 
| Package 3 Width | 80.0cm | 80.0cm | 80.0cm | 80.0cm | 
| Package 3 Length | 75.0cm | 75.0cm | 75.0cm | 75.0cm | 
| Package 3 Weight | 152.927 kg | 171.41kg | 140.698kg | 152.577 kg | 
| contract warranty | ||||
| Warranty | 18 months | 18 months | 18 months | 18 months | 
| Main | |
| Part Number | LC1D12M7 | 
| Range of product | TeSys Deca | 
| Product or component type | Contactor | 
| device short name | LC1D | 
| Contactor application | Resistive load | 
| Motor control | |
| Utilisation category | AC-4 | 
| AC-1 | |
| AC-3 | |
| AC-3e | |
| Poles description | 3P | 
| [Ue] rated operational voltage | Power circuit: <= 690 V AC 25…400 Hz | 
| Power circuit: <= 300 V DC | |
| [Ie] rated operational current | 25 A (at <60 °C) at <= 440 V AC AC-1 for power circuit | 
| 12 A (at <60 °C) at <= 440 V AC AC-3 for power circuit | |
| 12 A (at <60 °C) at <= 440 V AC AC-3e for power circuit | |
| [Uc] control circuit voltage | 220 V AC 50/60 Hz | 
| Complementary | |
| Motor power kW | 3 kW at 220…230 V AC 50/60 Hz (AC-3) | 
| 5.5 kW at 380…400 V AC 50/60 Hz (AC-3) | |
| 5.5 kW at 415…440 V AC 50/60 Hz (AC-3) | |
| 7.5 kW at 500 V AC 50/60 Hz (AC-3) | |
| 7.5 kW at 660…690 V AC 50/60 Hz (AC-3) | |
| 3.7 kW at 400 V AC 50/60 Hz (AC-4) | |
| 3 kW at 220…230 V AC 50/60 Hz (AC-3e) | |
| 5.5 kW at 380…400 V AC 50/60 Hz (AC-3e) | |
| 5.5 kW at 415…440 V AC 50/60 Hz (AC-3e) | |
| 7.5 kW at 500 V AC 50/60 Hz (AC-3e) | |
| 7.5 kW at 660…690 V AC 50/60 Hz (AC-3e) | |
| Motor power hp | 0.5 hp at 115 V AC 50/60 Hz for 1 phase motors | 
| 2 hp at 230/240 V AC 50/60 Hz for 1 phase motors | |
| 3 hp at 200/208 V AC 50/60 Hz for 3 phases motors | |
| 3 hp at 230/240 V AC 50/60 Hz for 3 phases motors | |
| 7.5 hp at 460/480 V AC 50/60 Hz for 3 phases motors | |
| 10 hp at 575/600 V AC 50/60 Hz for 3 phases motors | |
| Compatibility code | LC1D | 
| Pole contact composition | 3 NO | 
| Contact compatibility | M2 | 
| Protective cover | With | 
| [Ith] conventional free air thermal current | 25 A (at 60 °C) for power circuit | 
| 10 A (at 60 °C) for signalling circuit | |
| Irms rated making capacity | 250 A at 440 V for power circuit conforming to IEC 60947 | 
| 140 A AC for signalling circuit conforming to IEC 60947-5-1 | |
| 250 A DC for signalling circuit conforming to IEC 60947-5-1 | |
| Rated breaking capacity | 250 A at 440 V for power circuit conforming to IEC 60947 | 
| [Icw] rated short-time withstand current | 105 A 40 °C – 10 s for power circuit | 
| 210 A 40 °C – 1 s for power circuit | |
| 30 A 40 °C – 10 min for power circuit | |
| 61 A 40 °C – 1 min for power circuit | |
| 100 A – 1 s for signalling circuit | |
| 120 A – 500 ms for signalling circuit | |
| 140 A – 100 ms for signalling circuit | |
| Associated fuse rating | 10 A gG for signalling circuit conforming to IEC 60947-5-1 | 
| 40 A gG at <= 690 V coordination type 1 for power circuit | |
| 25 A gG at <= 690 V coordination type 2 for power circuit | |
| Average impedance | 2.5 mOhm – Ith 25 A 50 Hz for power circuit | 
| Power dissipation per pole | 0.36 W AC-3 | 
| 1.56 W AC-1 | |
| 0.36 W AC-3e | |
| [Ui] rated insulation voltage | Power circuit: 690 V conforming to IEC 60947-4-1 | 
| Power circuit: 600 V CSA certified | |
| Power circuit: 600 V UL certified | |
| Signalling circuit: 690 V conforming to IEC 60947-1 | |
| Signalling circuit: 600 V CSA certified | |
| Signalling circuit: 600 V UL certified | |
| Overvoltage category | III | 
| Pollution degree | 3 | 
| [Uimp] rated impulse withstand voltage | 6 kV conforming to IEC 60947 | 
| Safety reliability level | B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1 | 
| B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1 | |
| Mechanical durability | 15 Mcycles | 
| Electrical durability | 2 Mcycles 12 A AC-3 at Ue <= 440 V | 
| 0.8 Mcycles 25 A AC-1 at Ue <= 440 V | |
| 2 Mcycles 12 A AC-3e at Ue <= 440 V | |
| Control circuit type | AC at 50/60 Hz standard | 
| Coil technology | Without built-in suppressor module | 
| Control circuit voltage limits | 0.3…0.6 Uc (-40…70 °C):drop-out AC 50/60 Hz | 
| 0.8…1.1 Uc (-40…60 °C):operational AC 50 Hz | |
| 0.85…1.1 Uc (-40…60 °C):operational AC 60 Hz | |
| 1…1.1 Uc (60…70 °C):operational AC 50/60 Hz | |
| Inrush power in VA | 70 VA 60 Hz cos phi 0.75 (at 20 °C) | 
| 70 VA 50 Hz cos phi 0.75 (at 20 °C) | |
| Hold-in power consumption in VA | 7.5 VA 60 Hz cos phi 0.3 (at 20 °C) | 
| 7 VA 50 Hz cos phi 0.3 (at 20 °C) | |
| Heat dissipation | 2…3 W at 50/60 Hz | 
| Operating time | 12…22 ms closing | 
| 4…19 ms opening | |
| Maximum operating rate | 3600 cyc/h 60 °C | 
| Connections – terminals | Power circuit: screw clamp terminals 1 1…4 mm² – cable stiffness: flexible without cable end | 
| Power circuit: screw clamp terminals 2 1…4 mm² – cable stiffness: flexible without cable end | |
| Power circuit: screw clamp terminals 1 1…4 mm² – cable stiffness: flexible with cable end | |
| Power circuit: screw clamp terminals 2 1…2.5 mm² – cable stiffness: flexible with cable end | |
| Power circuit: screw clamp terminals 1 1…4 mm² – cable stiffness: solid without cable end | |
| Power circuit: screw clamp terminals 2 1…4 mm² – cable stiffness: solid without cable end | |
| Control circuit: screw clamp terminals 1 1…4 mm² – cable stiffness: flexible without cable end | |
| Control circuit: screw clamp terminals 2 1…4 mm² – cable stiffness: flexible without cable end | |
| Control circuit: screw clamp terminals 1 1…4 mm² – cable stiffness: flexible with cable end | |
| Control circuit: screw clamp terminals 2 1…2.5 mm² – cable stiffness: flexible with cable end | |
| Control circuit: screw clamp terminals 1 1…4 mm² – cable stiffness: solid without cable end | |
| Control circuit: screw clamp terminals 2 1…4 mm² – cable stiffness: solid without cable end | |
| Tightening torque | Power circuit: 1.7 N.m – on screw clamp terminals – with screwdriver flat Ø 6 mm | 
| Power circuit: 1.7 N.m – on screw clamp terminals – with screwdriver Philips No 2 | |
| Control circuit: 1.7 N.m – on screw clamp terminals – with screwdriver flat Ø 6 mm | |
| Control circuit: 1.7 N.m – on screw clamp terminals – with screwdriver Philips No 2 | |
| Control circuit: 1.7 N.m – on screw clamp terminals – with screwdriver pozidriv No 2 | |
| Power circuit: 1.7 N.m – on screw clamp terminals – with screwdriver pozidriv No 2 | |
| Auxiliary contact composition | 1 NO + 1 NC | 
| Auxiliary contacts type | Type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1 | 
| type mirror contact 1 NC conforming to IEC 60947-4-1 | |
| Signalling circuit frequency | 25…400 Hz | 
| Weight | N/A | 
|---|---|
| Dimensions | N/A |