| Main | |||
| Part Number | LC1D17000F7C | LC1D17000M7C | LC1D17000Q7C | 
| Product Series | TeSys Deca | TeSys Deca | TeSys Deca | 
| Product Series | TeSys Deca | TeSys Deca | TeSys Deca | 
| product type | Contactor | Contactor | Contactor | 
| product short name | LC1D | LC1D | LC1D | 
| Application field of contactor | Applied to AC loads with power factor greater than or equal to 0.95 Applied to non-inductive or slightly inductive loads, resistance furnaces | Applied to non-inductive or micro-inductive loads, and resistance furnaces to AC loads with a power factor greater than or equal to 0.95 | Applied to non-inductive or micro-inductive loads, and resistance furnaces to AC loads with a power factor greater than or equal to 0.95 | 
| use category | AC-1 AC-3 AC-3e | AC-1 AC-3 AC-3e | AC-1 AC-3 AC-3e | 
| number of poles | 3P | 3P | 3P | 
| Rated working voltage [Ue] | Power circuit: <= 300 V DC Power circuit: <= 1000 V AC 25…400 Hz | Power circuit: <= 300 V DC Power circuit: <= 1000 V AC 25…400 Hz | Power circuit: <= 300 V DC Power circuit: <= 1000 V AC 25…400 Hz | 
| Rated operating current [Ie] | 200 A 60 °C) at <= 440 V AC AC-1 for power circuits 170 A 60 °C) at <= 440 V AC AC-3 for power circuits | 200 A 60 °C) at <= 440 V AC AC-1 for power circuits 170 A 60 °C) at <= 440 V AC AC-3 for power circuits | 200 A 60 °C) at <= 440 V AC AC-1 for power circuits 170 A 60 °C) at <= 440 V AC AC-3 for power circuits | 
| [Uc] control circuit voltage | 110V AC 50/60Hz | 230V AC 50/60Hz | 380 V AC 50/60 Hz | 
| Additional information | |||
| Motor power (kW) | 55 kW at 220/240 V AC 50/60 Hz (AC-3) 90 kW at 380/400 V AC 50/60 Hz (AC-3) 100 kW at 415/440 V AC 50/ 60 Hz (AC-3) 110 kW at 500 V AC 50/60 Hz (AC-3) 110 kW at 660/690 V AC 50/60 Hz (AC-3) 100 kW at 1000 V AC 50/60Hz (AC-3) | 55 kW at 220/240 V AC 50/60 Hz (AC-3) 90 kW at 380/400 V AC 50/60 Hz (AC-3) 100 kW at 415/440 V AC 50/ 60 Hz (AC-3) 110 kW at 500 V AC 50/60 Hz (AC-3) 110 kW at 660/690 V AC 50/60 Hz (AC-3) 100 kW at 1000 V AC 50/60Hz (AC-3) | 55 kW at 220/240 V AC 50/60 Hz (AC-3) 90 kW at 380/400 V AC 50/60 Hz (AC-3) 100 kW at 415/440 V AC 50/ 60 Hz (AC-3) 110 kW at 500 V AC 50/60 Hz (AC-3) 110 kW at 660/690 V AC 50/60 Hz (AC-3) 100 kW at 1000 V AC 50/60Hz (AC-3) | 
| model | LC1D | LC1D | LC1D | 
| Loop contact type | 3 NO | 3 NO | 3 NO | 
| protection cap | None | None | None | 
| Conventional thermal current [Ith] | 200 A at <60 °C for power circuits | 200 A at <60 °C for power circuits | 200 A at <60 °C for power circuits | 
| Rated short-time withstand current [Icw] | 250 A at <40 °C – 10 min for power circuit 1400 A at <40 °C – 1 s for power circuit 1200 A at <40 °C – 10 s for power circuit 580 A at <40 °C – 1 minute for power circuit | 250 A at <40 °C – 10 min for power circuit 1400 A at <40 °C – 1 s for power circuit 1200 A at <40 °C – 10 s for power circuit 580 A at <40 °C – 1 minute for power circuit | 250 A at <40 °C – 10 min for power circuit 1400 A at <40 °C – 1 s for power circuit 1200 A at <40 °C – 10 s for power circuit 580 A at <40 °C – 1 minute for power circuit | 
| Fuses for use with relays | 315 A gG at <= 690 V with type 1 suitable power circuit 250 A gG at <= 690 V with type 2 suitable power circuit | 315 A gG at <= 690 V with type 1 suitable power circuit 250 A gG at <= 690 V with type 2 suitable power circuit | 315 A gG at <= 690 V with type 1 suitable power circuit 250 A gG at <= 690 V with type 2 suitable power circuit | 
| average impedance | 0.6 mΩ – Ith 200 A 50 Hz for power circuits | 0.6 mΩ – Ith 200 A 50 Hz for power circuits | 0.6 mΩ – Ith 200 A 50 Hz for power circuits | 
| Rated insulation voltage [Ui] | Power circuit: 1000 V conforming to IEC 60947-4-1 | Power circuit: 1000 V conforming to IEC 60947-4-1 | Power circuit: 1000 V conforming to IEC 60947-4-1 | 
| Overvoltage category | III | III | III | 
| pollution level | 3 | 3 | 3 | 
| Rated impulse withstand voltage [Uimp] | 8 kV according to IEC 60947 | 8 kV according to IEC 60947 | 8 kV according to IEC 60947 | 
| Mechanical life | 8 Mcycles | 8 Mcycles | 8 Mcycles | 
| Electrical life | 0.6 Mcycles 250 A AC-1 Ue <= 440 V 0.8 Mcycles 150 A AC-3 Ue <= 440 V 1.5 Mcycles 90 A AC-3 Ue 660/690 V | 0.6 Mcycles 250 A AC-1 Ue <= 440 V 0.8 Mcycles 150 A AC-3 Ue <= 440 V 1.5 Mcycles 90 A AC-3 Ue 660/690 V | 0.6 Mcycles 250 A AC-1 Ue <= 440 V 0.8 Mcycles 150 A AC-3 Ue <= 440 V 1.5 Mcycles 90 A AC-3 Ue 660/690 V | 
| Control loop characteristics | AC at 50/60 Hz | AC at 50/60 Hz | AC at 50/60 Hz | 
| Surge Suppression Module | No built-in surge suppression module | No built-in surge suppression module | No built-in surge suppression module | 
| Control voltage limit | 0.3…0.5 Uc -40…55 °C release 50/60 Hz 0.8…1.15 Uc -40…55 °C run 50/60 Hz | 0.3…0.5 Uc -40…55 °C release 50/60 Hz 0.8…1.15 Uc -40…55 °C run 50/60 Hz | 0.3…0.5 Uc -40…55 °C release 50/60 Hz 0.8…1.15 Uc -40…55 °C run 50/60 Hz | 
| (~50Hz pickup) power consumption (VA) | 280…350 VA 50 Hz 0.9 20 °C) 280…350 VA 60 Hz 0.9 20 °C) | 280…350 VA 50 Hz 0.9 20 °C) 280…350 VA 60 Hz 0.9 20 °C) | 280…350 VA 50 Hz 0.9 20 °C) 280…350 VA 60 Hz 0.9 20 °C) | 
| (~50Hz hold) power consumption (VA) | 2…18 VA 50 Hz 0.9 20 °C) 2…18 VA 60 Hz 0.9 20 °C) | 2…18 VA 50 Hz 0.9 20 °C) 2…18 VA 60 Hz 0.9 20 °C) | 2…18 VA 50 Hz 0.9 20 °C) 2…18 VA 60 Hz 0.9 20 °C) | 
| heat dissipation | 3…4.5 W at 50/60 Hz | 3…4.5 W at 50/60 Hz | 3…4.5 W at 50/60 Hz | 
| action time | 20…35 ms closed 40…75 ms open | 20…35 ms closed 40…75 ms open | 20…35 ms closed 40…75 ms open | 
| operating frequency | 1200 cycles/h at <60 °C | 1200 cycles/h at <60 °C | 1200 cycles/h at <60 °C | 
| Wiring capacity | Control circuit: Bolt fastening2 1…2.5 mm² Cable selection: flexible wire with wire terminal Control circuit: screw fastening1 1…2.5 mm² Cable selection: flexible wire with wire terminal Power circuit: bus terminal : Solid busbar cross-section: 5 x 25 mm Power circuit: Terminal 1 10…120 mm² Lug outer diameter Ø: 25 mm Cable selection: Flexible without wire terminals Power circuit: Terminal 2 10…50 mm² Lug outer diameter Ø: 25 mm Cable selection: flexible cord without wire terminals Power circuit: terminal 1 10…120 mm² Lug outer diameter Ø: 25 mm Cable selection: flexible cord with wire terminals Power circuit: Terminal 2 10…50 mm² Lug O.D. Ø: 25 mm Cable Option: Flexible with wire terminal Power Circuit: Terminal 1 10…120 mm² Lug Ø: 25 mm Cable Option: Solid No With wire terminals Power circuit: Terminal 2 10…50 mm² Lug O.D. Ø: 25 mm Cable option: Solid without wire terminals Control circuit: Bolt tight1 1…2.5 mm² Cable option: Flexible Without wire terminal control circuit: bolt fastening2 1…2.5 mm² Cable selection: flexible wire without wire terminal control circuit: screw fastening1 1…2.5 mm² cable selection: rigid wire without wire terminal control Circuit: Bolt-on2 1…2.5 mm² Cable selection: Solid without cable terminals | Control circuit: Bolt fastening2 1…2.5 mm² Cable selection: flexible wire with wire terminal Control circuit: screw fastening1 1…2.5 mm² Cable selection: flexible wire with wire terminal Power circuit: bus terminal : Solid busbar cross-section: 5 x 25 mm Power circuit: Terminal 1 10…120 mm² Lug outer diameter Ø: 25 mm Cable selection: Flexible without wire terminals Power circuit: Terminal 2 10…50 mm² Lug outer diameter Ø: 25 mm Cable selection: flexible cord without wire terminals Power circuit: terminal 1 10…120 mm² Lug outer diameter Ø: 25 mm Cable selection: flexible cord with wire terminals Power circuit: Terminal 2 10…50 mm² Lug O.D. Ø: 25 mm Cable Option: Flexible with wire terminal Power Circuit: Terminal 1 10…120 mm² Lug Ø: 25 mm Cable Option: Solid No With wire terminals Power circuit: Terminal 2 10…50 mm² Lug O.D. Ø: 25 mm Cable option: Solid without wire terminals Control circuit: Bolt tight1 1…2.5 mm² Cable option: Flexible Without wire terminal control circuit: bolt fastening2 1…2.5 mm² Cable selection: flexible wire without wire terminal control circuit: screw fastening1 1…2.5 mm² cable selection: rigid wire without wire terminal control Circuit: Bolt-on2 1…2.5 mm² Cable selection: Solid without cable terminals | Control circuit: Bolt fastening2 1…2.5 mm² Cable selection: flexible wire with wire terminal Control circuit: screw fastening1 1…2.5 mm² Cable selection: flexible wire with wire terminal Power circuit: bus terminal : Solid busbar cross-section: 5 x 25 mm Power circuit: Terminal 1 10…120 mm² Lug outer diameter Ø: 25 mm Cable selection: Flexible without wire terminals Power circuit: Terminal 2 10…50 mm² Lug outer diameter Ø: 25 mm Cable selection: flexible cord without wire terminals Power circuit: terminal 1 10…120 mm² Lug outer diameter Ø: 25 mm Cable selection: flexible cord with wire terminals Power circuit: Terminal 2 10…50 mm² Lug O.D. Ø: 25 mm Cable Option: Flexible with wire terminal Power Circuit: Terminal 1 10…120 mm² Lug Ø: 25 mm Cable Option: Solid No With wire terminals Power circuit: Terminal 2 10…50 mm² Lug O.D. Ø: 25 mm Cable option: Solid without wire terminals Control circuit: Bolt tight1 1…2.5 mm² Cable option: Flexible Without wire terminal control circuit: bolt fastening2 1…2.5 mm² Cable selection: flexible wire without wire terminal control circuit: screw fastening1 1…2.5 mm² cable selection: rigid wire without wire terminal control Circuit: Bolt-on2 1…2.5 mm² Cable selection: Solid without cable terminals | 
| Tightening torque | Control circuit: 1.2 Nm by bolting with screwdriver Ø 6 Flat control circuit: 1.2 Nm by bolting with screwdriver No. 2 Phillips screw power circuit: 12 Nm by bolting hexagonal 4 mm power circuit: 12 Nm by cable connection Hexagonal 13 mm screw: M8 Control circuit: 1.2 Nm Via bolt fastening with screwdriver pozidriv No 2 | Control circuit: 1.2 Nm by bolting with screwdriver Ø 6 Flat control circuit: 1.2 Nm by bolting with screwdriver No. 2 Phillips screw power circuit: 12 Nm by bolting hexagonal 4 mm power circuit: 12 Nm by cable connection Hexagonal 13 mm screw: M8 Control circuit: 1.2 Nm Via bolt fastening with screwdriver pozidriv No 2 | Control circuit: 1.2 Nm by bolting with screwdriver Ø 6 Flat control circuit: 1.2 Nm by bolting with screwdriver No. 2 Phillips screw power circuit: 12 Nm by bolting hexagonal 4 mm power circuit: 12 Nm by cable connection Hexagonal 13 mm screw: M8 Control circuit: 1.2 Nm Via bolt fastening with screwdriver pozidriv No 2 | 
| Auxiliary contact type | Does not contain | Does not contain | Does not contain | 
| installation method | DIN rail installation base plate installation | Chassis mounting rail installation | Chassis mounting rail installation | 
| environment | |||
| standard | GB 14048.4 IEC 60947-4-1 | IEC 60947-4-1 GB 14048.4 | IEC 60947-4-1 GB 14048.4 | 
| certified product | CCC CE UKCA | CCC CE UKCA | CCC CE UKCA | 
| IP protection class | IP2x front panel for main circuits conforming to IEC 60529 IP2x front panel for coil circuits conforming to IEC 60529 | IP2x front panel for main circuits conforming to IEC 60529 IP2x front panel for coil circuits conforming to IEC 60529 | IP2x front panel for main circuits conforming to IEC 60529 IP2x front panel for coil circuits conforming to IEC 60529 | 
| Protective measures | TH conforms to IEC 60068-2-30 | TH conforms to IEC 60068-2-30 | TH conforms to IEC 60068-2-30 | 
| ambient air temperature | -40…60 °C operation 60…70 °C with derating -60…80 °C storage | -40…60 °C operation 60…70 °C with derating -60…80 °C storage | -40…60 °C operation 60…70 °C with derating -60…80 °C storage | 
| working altitude | 3000 m None | 3000 m None | 3000 m None | 
| Fire resistance and abnormal high temperature resistance | 850 °C conforming to IEC 60695-2-11 | 850 °C conforming to IEC 60695-2-11 | 850 °C conforming to IEC 60695-2-11 | 
| Shock and vibration resistance | Shock resistance with contacts open (2 gn (5…300 Hz)) conforming to IEC 60068-2-6 Shock resistance with contacts closed ( 4 gn (5…300 Hz)) conforming to IEC 60068-2-6 Shock performance 11 ms with contacts closed (15 gn) conforming to IEC 60068-2-27 Shock resistance 11 ms with contacts open (6 gn) conforming to IEC 60068-2-27 | Shock resistance with contacts open (2 gn (5…300 Hz)) conforming to IEC 60068-2-6 Shock resistance with contacts closed ( 4 gn (5…300 Hz)) conforming to IEC 60068-2-6 Shock performance 11 ms with contacts closed (15 gn) conforming to IEC 60068-2-27 Shock resistance 11 ms with contacts open (6 gn) conforming to IEC 60068-2-27 | Shock resistance with contacts open (2 gn (5…300 Hz)) conforming to IEC 60068-2-6 Shock resistance with contacts closed ( 4 gn (5…300 Hz)) conforming to IEC 60068-2-6 Shock performance 11 ms with contacts closed (15 gn) conforming to IEC 60068-2-27 Shock resistance 11 ms with contacts open (6 gn) conforming to IEC 60068-2-27 | 
| high | 158 mm | 158 mm | 158 mm | 
| width | 120 mm | 120 mm | 120 mm | 
| depth | 136 mm | 136 mm | 136 mm | 
| Product Weight | 2.5 kg | 2.5 kg | 2.5 kg | 
| packaging unit | |||
| Unit Type of Package 1 | PCE | PCE | PCE | 
| Number of Units in Package 1 | 1 | 1 | 1 | 
| Package 1 Height | 16.45cm | 16.876 cm | 16.817 cm | 
| Package 1 Width | 17.82cm | 18.038 cm | 18.006 cm | 
| Package 1 Length | 20.966 cm | 20.683 cm | 20.429 cm | 
| Package 1 Weight | 2428.5g | 2416.2g | 2410.0g | 
| Unit Type of Package 2 | P06 | P06 | P06 | 
| Number of Units in Package 2 | Twenty four | Twenty four | Twenty four | 
| Package 2 Height | 60.0cm | 60.0cm | 60.0cm | 
| Package 2 Width | 60.0cm | 60.0cm | 60.0cm | 
| Package 2 Length | 80.0cm | 80.0cm | 80.0cm | 
| Package 2 Weight | 70.68 kg | 70.38 kg | 70.23 kg | 
| contract warranty | |||
| Warranty | 18 months | 18 months | 18 months | 
| Weight | N/A | 
|---|---|
| Dimensions | N/A |