| Main | |||
| Part Number | LC1DT40BDC | LC1DT40FDC | LC1DT40M7C | 
| Product Series | TeSys Deca | TeSys Deca | TeSys Deca | 
| Product Series | TeSys Deca | TeSys Deca | TeSys Deca | 
| product type | Contactor | Contactor | Contactor | 
| product short name | LC1D | LC1D | LC1D | 
| Application field of contactor | Applied to AC loads with power factor greater than or equal to 0.95 Applied to non-inductive or slightly inductive loads, resistance furnaces | Applied to AC loads with power factor greater than or equal to 0.95 Applied to non-inductive or slightly inductive loads, resistance furnaces | Applied to AC loads with power factor greater than or equal to 0.95 Applied to non-inductive or slightly inductive loads, resistance furnaces | 
| use category | AC-3AC -1 | AC-1AC -3 | AC-1AC -3 | 
| number of poles | 4P | 4P | 4P | 
| Rated working voltage [Ue] | Power circuit: <= 690 V AC 25…400 Hz Power circuit: <= 300 V DC | Power circuit: <= 690 V AC 25…400 Hz Power circuit: <= 300 V DC | Power circuit: <= 690 V AC 25…400 Hz Power circuit: <= 300 V DC | 
| Rated operating current [Ie] | 40 A 60 °C) at <= 440 V AC AC-1 for power circuits 25 A 60 °C) at <= 440 V AC AC-3 for power circuits | 40 A 60 °C) at <= 440 V AC AC-1 for power circuits 25 A 60 °C) at <= 440 V AC AC-3 for power circuits | 40 A 60 °C) at <= 440 V AC AC-1 for power circuits 25 A 60 °C) at <= 440 V AC AC-3 for power circuits | 
| [Uc] control circuit voltage | 24 V DC | 110V DC | 230V AC 50/60Hz | 
| Additional information | |||
| model | LC1D | LC1D | LC1D | 
| Loop contact type | 4 NO | 4 NO | 4 NO | 
| protection cap | None | None | None | 
| Conventional thermal current [Ith] | 10 A at <60 °C for signal circuits 40 A at <60 °C for power circuits | 10 A at <60 °C for signal circuits 40 A at <60 °C for power circuits | 10 A at <60 °C for signal circuits 40 A at <60 °C for power circuits | 
| Rated short-time withstand current [Icw] | 240 A at <40 °C – 10 s for power circuit 380 A at <40 °C – 1 s for power circuit 50 A at <40 °C – 10 min for power circuit 120 A at <40 °C – 1 minute for power circuit 100 A – 1 s for signal circuit 120 A – 500 ms for signal circuit 140 A – 100 ms for signal circuit | 240 A at <40 °C – 10 s for power circuit 380 A at <40 °C – 1 s for power circuit 50 A at <40 °C – 10 min for power circuit 120 A at <40 °C – 1 minute for power circuit 100 A – 1 s for signal circuit 120 A – 500 ms for signal circuit 140 A – 100 ms for signal circuit | 240 A at <40 °C – 10 s for power circuit 380 A at <40 °C – 1 s for power circuit 50 A at <40 °C – 10 min for power circuit 120 A at <40 °C – 1 minute for power circuit 100 A – 1 s for signal circuit 120 A – 500 ms for signal circuit 140 A – 100 ms for signal circuit | 
| Fuses for use with relays | 10 A gG for signal circuits according to IEC 60947-5-1 63 A gG at <= 690 V for power circuits type 1 40 A gG for power circuits for type 2 at <= 690 V | 10 A gG for signal circuits according to IEC 60947-5-1 63 A gG at <= 690 V for power circuits type 1 40 A gG for power circuits for type 2 at <= 690 V | 10 A gG for signal circuits according to IEC 60947-5-1 63 A gG at <= 690 V for power circuits type 1 40 A gG for power circuits for type 2 at <= 690 V | 
| average impedance | 2 mΩ – Ith 40 A 50 Hz for power circuits | 2 mΩ – Ith 40 A 50 Hz for power circuits | 2 mΩ – Ith 40 A 50 Hz for power circuits | 
| Rated insulation voltage [Ui] | Power circuit: 690 V conforming to IEC 60947-4-1 Signal circuit: 690 V conforming to IEC 60947-1 | Power circuit: 690 V conforming to IEC 60947-4-1 Signal circuit: 690 V conforming to IEC 60947-1 | Power circuit: 690 V conforming to IEC 60947-4-1 Signal circuit: 690 V conforming to IEC 60947-1 | 
| Overvoltage category | III | III | III | 
| pollution level | 3 | 3 | 3 | 
| Rated impulse withstand voltage [Uimp] | 6 kV according to IEC 60947 | 6 kV according to IEC 60947 | 6 kV according to IEC 60947 | 
| Safety and reliability level | B10d = Contactor for 1369863 nominal loads according to EN/ISO 13849-1 B10d = Contactor for 20000000 mechanical loads according to EN/ISO 13849-1 | B10d = Contactor for 1369863 nominal loads according to EN/ISO 13849-1 B10d = Contactor for 20000000 mechanical loads according to EN/ISO 13849-1 | B10d = Contactor for 1369863 nominal loads according to EN/ISO 13849-1 B10d = Contactor for 20000000 mechanical loads according to EN/ISO 13849-1 | 
| Mechanical life | 30 Mcycles | 30 Mcycles | 15 Mcycles | 
| Electrical life | 1.4 Mcycles <= 440 V at 40 A AC-1 Ue | 1.4 Mcycles <= 440 V at 40 A AC-1 Ue | 1.4 Mcycles <= 440 V at 40 A AC-1 Ue | 
| Control loop characteristics | DC standard | DC standard | AC at 50/60 Hz | 
| Surge Suppression Module | Built-in bidirectional peak current limiting diode | Built-in bidirectional peak current limiting diode | No built-in surge suppression module | 
| Control voltage limit | 0.1…0.25 Uc -40…60 °C release 0.7…1.25 Uc -40…60 °C run | 0.1…0.25 Uc -40…60 °C release 0.7…1.25 Uc -40…60 °C run | 0.3…0.6 Uc -40…60 °C release 50/60 Hz 0.8…1.1 Uc -40…60 °C run 50 Hz 0.85…1.1 Uc -40…60 °C run 60 Hz | 
| Surge power (W) | 5.4W (20°C) | 5.4W (20°C) | |
| Holding power consumption(W) | 5.4 W at 20 °C | 5.4 W at 20 °C | |
| Rated operating power (W) | 5.4W | 5.4W | |
| action time | 55 ms to close, 20 ms to break | 55 ms to close, 20 ms to break | 12…22 ms close 4…19 ms break | 
| time constant | 28ms | 28ms | |
| operating frequency | 3600 cycles/h at <60 °C | 3600 cycles/h at <60 °C | 3600 cycles/h at <60 °C | 
| Wiring capacity | Control circuit: Bolt fastening1 1…4 mm² Cable selection: Flexible cord without wire terminals Control circuit: Bolt fastening2 1…4 mm² Cable selection: Flexible cord without wire terminal Control circuit: Bolt fastening 1 1…4 mm² cable option: flexible cable with cable terminals control circuit: screw fastened2 1…2.5 mm² cable option: flexible cable with cable terminal control circuit: screw cable option1 1…4 mm² cable option : Solid without wire terminals Control circuit: Bolt fastening2 1…4 mm² Cable selection: Solid without wire terminals Power circuit: Terminal 1 2.5…10 mm² Lug outer diameter Ø: 8 mm Cable selection Type: Flexible cord without wire terminals Power circuit: Terminal 2 2.5…10 mm² Lug Ø: 8 mm Cable selection: Flexible cord without wire terminals Power circuit: Terminal 1 2.5…10 mm² Lug Outer diameter Ø: 8 mm Cable option: Flexible cord with wire terminals Power circuit: Terminal 2 2.5…10 mm² Lug outer diameter Ø: 8 mm Cable option: Flexible cord with bar terminals Power circuit: Terminal 1 2.5…16 mm² O.D. lug Ø: 8 mm Cable option: Solid without cable terminals Power circuit: Terminal 2 2.5…16 mm² Ø Lug: 8 mm Cable option: Solid without cable Wire terminal power circuit: screw connection | Control circuit: Bolt fastening1 1…4 mm² Cable selection: Flexible cord without wire terminals Control circuit: Bolt fastening2 1…4 mm² Cable selection: Flexible cord without wire terminal Control circuit: Bolt fastening 1 1…4 mm² cable option: flexible cable with cable terminals control circuit: screw fastened2 1…2.5 mm² cable option: flexible cable with cable terminal control circuit: screw cable option1 1…4 mm² cable option : Solid without wire terminals Control circuit: Bolt fastening2 1…4 mm² Cable selection: Solid without wire terminals Power circuit: Terminal 1 2.5…10 mm² Lug outer diameter Ø: 8 mm Cable selection Type: Flexible cord without wire terminals Power circuit: Terminal 2 2.5…10 mm² Lug Ø: 8 mm Cable selection: Flexible cord without wire terminals Power circuit: Terminal 1 2.5…10 mm² Lug Outer diameter Ø: 8 mm Cable option: Flexible cord with wire terminals Power circuit: Terminal 2 2.5…10 mm² Lug outer diameter Ø: 8 mm Cable option: Flexible cord with bar terminals Power circuit: Terminal 1 2.5…16 mm² O.D. lug Ø: 8 mm Cable option: Solid without cable terminals Power circuit: Terminal 2 2.5…16 mm² Ø Lug: 8 mm Cable option: Solid without cable Wire terminal power circuit: screw connection | Control circuit: Bolt fastening1 1…4 mm² Cable selection: Flexible cord without wire terminals Control circuit: Bolt fastening2 1…4 mm² Cable selection: Flexible cord without wire terminal Control circuit: Bolt fastening 1 1…4 mm² cable option: flexible cable with cable terminals control circuit: screw fastened2 1…2.5 mm² cable option: flexible cable with cable terminal control circuit: screw cable option1 1…4 mm² cable option : Solid without wire terminals Control circuit: Bolt fastening2 1…4 mm² Cable selection: Solid without wire terminals Power circuit: Terminal 1 2.5…10 mm² Lug outer diameter Ø: 8 mm Cable selection Type: Flexible cord without wire terminals Power circuit: Terminal 2 2.5…10 mm² Lug Ø: 8 mm Cable selection: Flexible cord without wire terminals Power circuit: Terminal 1 2.5…10 mm² Lug Outer diameter Ø: 8 mm Cable option: Flexible cord with wire terminals Power circuit: Terminal 2 2.5…10 mm² Lug outer diameter Ø: 8 mm Cable option: Flexible cord with bar terminals Power circuit: Terminal 1 2.5…16 mm² O.D. lug Ø: 8 mm Cable option: Solid without cable terminals Power circuit: Terminal 2 2.5…16 mm² Ø Lug: 8 mm Cable option: Solid without cable Wire terminal power circuit: screw connection | 
| Tightening torque | Control circuit: 1.7 Nm via screwdriver Ø 6 flat control circuit: 1.7 Nm via screwdriver No 2 Phillips screw power circuit: 1.8 Nm via screwdriver Ø 6 flat power circuit: 1.8 Nm via screw Screwdriver No. 2 for fastening Phillips screw Power circuit: 1.8 Nm Screwdriver Ø 6 flat-blade screw via cable connector: M3.5 Power circuit: 1.8 Nm Phillips screw driver No. 2 via cable connector Screw: M3.5 Control circuit: 1.7 Nm Fastening by bolts with screwdriver pozidriv No 2 | Control circuit: 1.7 Nm via screwdriver Ø 6 flat control circuit: 1.7 Nm via screwdriver No 2 Phillips screw power circuit: 1.8 Nm via screwdriver Ø 6 flat power circuit: 1.8 Nm via screw Screwdriver No. 2 for fastening Phillips screw Power circuit: 1.8 Nm Screwdriver Ø 6 flat-blade screw via cable connector: M3.5 Power circuit: 1.8 Nm Phillips screw driver No. 2 via cable connector Screw: M3.5 Control circuit: 1.7 Nm Fastening by bolts with screwdriver pozidriv No 2 | Control circuit: 1.7 Nm via screwdriver Ø 6 flat control circuit: 1.7 Nm via screwdriver No 2 Phillips screw power circuit: 1.8 Nm via screwdriver Ø 6 flat power circuit: 1.8 Nm via screw Screwdriver No. 2 for fastening Phillips screw Power circuit: 1.8 Nm Screwdriver Ø 6 flat-blade screw via cable connector: M3.5 Power circuit: 1.8 Nm Phillips screw driver No. 2 via cable connector Screw: M3.5 Control circuit: 1.7 Nm Fastening by bolts with screwdriver pozidriv No 2 | 
| Auxiliary contact type | 1 NO + 1 NC | 1 NO + 1 NC | 1 NO + 1 NC | 
| Auxiliary contact type | Type Mechanical connection 1 NO + 1 NC conforming to IEC 60947-5-1 Type mirrored with main contact status 1 NC conforming to IEC 60947-4-1 | 1 NO + 1 NC | 1 NO + 1 NC | 
| Signal loop frequency | 25…400Hz | 25…400Hz | 25…400Hz | 
| Minimum switching current [Imin] | 5 mA for signal loop | 5 mA for signal loop | 5 mA for signal loop | 
| Insulation resistance | > 10 MΩ for signal loops | > 10 MΩ for signal loops | > 10 MΩ for signal loops | 
| non-overlapping time | 1.5 ms between de-energized NC and NO contacts 1.5 ms between energized NC and NO contacts | 1.5 ms between de-energized NC and NO contacts 1.5 ms between energized NC and NO contacts | 1.5 ms between de-energized NC and NO contacts 1.5 ms between energized NC and NO contacts | 
| installation method | Chassis mounting rail installation | Chassis mounting rail installation | DIN rail installation base plate installation | 
| environment | |||
| standard | IEC 60947-4-1 GB 14048.4 | GB 14048.4 IEC 60947-4-1 | GB 14048.4 IEC 60947-4-1 | 
| certified product | CCC CE UKCA | CCC CE UKCA | CCC CE UKCA | 
| IP protection class | IP2x front panel for main circuits conforming to IEC 60529 IP2x front panel for coil circuits conforming to IEC 60529 | IP2x front panel for main circuits conforming to IEC 60529 IP2x front panel for coil circuits conforming to IEC 60529 | IP2x front panel for main circuits conforming to IEC 60529 IP2x front panel for coil circuits conforming to IEC 60529 | 
| Protective measures | TH conforms to IEC 60068-2-30 | TH conforms to IEC 60068-2-30 | TH conforms to IEC 60068-2-30 | 
| ambient air temperature | -40…60 °C operation 60…70 °C with derating -60…80 °C storage | -40…60 °C operation 60…70 °C with derating -60…80 °C storage | -40…60 °C operation 60…70 °C with derating -60…80 °C storage | 
| working altitude | 3000 m None | 3000 m None | 3000 m None | 
| Fire resistance and abnormal high temperature resistance | 850 °C conforming to IEC 60695-2-11 | 850 °C conforming to IEC 60695-2-11 | 850 °C conforming to IEC 60695-2-11 | 
| Shock and vibration resistance | Shock resistance with contacts open (2 gn (5…300 Hz)) conforming to IEC 60068-2-6 Shock resistance with contacts closed ( 4 gn (5…300 Hz)) conforming to IEC 60068-2-6 Shock performance 11 ms with contacts closed (15 gn) conforming to IEC 60068-2-27 Shock resistance 11 ms with contacts open (8 gn) conforming to IEC 60068-2-27 | Shock resistance with contacts open (2 gn (5…300 Hz)) conforming to IEC 60068-2-6 Shock resistance with contacts closed ( 4 gn (5…300 Hz)) conforming to IEC 60068-2-6 Shock performance 11 ms with contacts closed (15 gn) conforming to IEC 60068-2-27 Shock resistance 11 ms with contacts open (8 gn) conforming to IEC 60068-2-27 | Shock resistance with contacts open (2 gn (5…300 Hz)) conforming to IEC 60068-2-6 Shock resistance with contacts closed ( 4 gn (5…300 Hz)) conforming to IEC 60068-2-6 Shock performance 11 ms with contacts closed (15 gn) conforming to IEC 60068-2-27 Shock resistance 11 ms with contacts open (8 gn) conforming to IEC 60068-2-27 | 
| high | 91 mm | 91 mm | 91 mm | 
| width | 45 mm | 45 mm | 45 mm | 
| depth | 107 mm | 107 mm | 99 mm | 
| Product Weight | 0.425 kg | 0.425 kg | 0.425 kg | 
| packaging unit | |||
| Unit Type of Package 1 | PCE | PCE | PCE | 
| Number of Units in Package 1 | 1 | 1 | 1 | 
| Package 1 Height | 9.3 cm | 9.3 cm | 9.3 cm | 
| Package 1 Width | 11.6 cm | 11.6 cm | 11.6 cm | 
| Package 1 Length | 5.2 cm | 5.2 cm | 5.2 cm | 
| Package 1 Weight | 446.63g | 446.63g | 492.38g | 
| Unit Type of Package 2 | CAR | CAR | |
| Number of Units in Package 2 | 16 | 16 | |
| Package 2 Height | 30.0cm | 30.0cm | |
| Package 2 Width | 40.0cm | 40.0cm | |
| Package 2 Length | 15.0cm | 15.0cm | |
| Package 2 Weight | 7.196 kg | 7.928 kg | |
| Unit Type of Package 3 | PAL | PAL | |
| Number of Units in Package 3 | 256 | 256 | |
| Package 3 Height | 60.0cm | 60.0cm | |
| Package 3 Width | 80.0cm | 80.0cm | |
| Package 3 Length | 75.0cm | 75.0cm | |
| Package 3 Weight | 114.536kg | 126.248 kg | |
| contract warranty | |||
| Warranty | 18 months | 18 months | 18 months | 
| Weight | N/A | 
|---|---|
| Dimensions | N/A |