main information |
|
|
Part Number |
GV2PM08C |
GV2PM14C |
Product Series |
TeSys Deca |
TeSys Deca |
product name |
TeSys GV2 |
TeSys GV2 |
product short name |
GV2PM |
GV2PM |
product type |
Breaker |
Breaker |
Applications |
Motor protection |
Motor protection |
number of poles |
3P |
3P |
Additional information |
|
|
Grid type |
AC |
AC |
Network frequency |
50/60 Hz conforming to IEC 60947-2 |
50/60 Hz conforming to IEC 60947-2 |
control type |
Knob |
Knob |
installation method |
Rail installation |
Rail installation |
installation location |
Vertical |
horizontal vertical |
|
horizontal direction |
|
Motor power (kW) |
0.75 kW at 230 V AC 50/60 Hz |
2.2 kW at 230 V AC 50/60 Hz |
|
1.5 kW at 400 V |
4 kW at 400 V |
|
1.5 kW at 415 V |
4 kW at 415 V |
|
1.5 kW at 440 V AC 50/60 Hz |
4 kW at 440 V AC 50/60 Hz |
Rated current [In] |
4A |
10A |
Trip unit type |
Thermomagnetic |
Thermomagnetic |
Electromagnetic trip current |
51A |
138A |
Thermal overload protection setting range |
2.5…4A |
6…10A |
isolation function |
Applies to IEC 60947-1 § 7-1-6 |
Applies to IEC 60947-1 § 7-1-6 |
Mechanical shock resistance |
0.5 J IK04 |
0.5 J IK04 |
phase loss sensitivity |
Is compliant with IEC 60947-4-1 § 7-2-1-5-2 |
Is compliant with IEC 60947-4-1 § 7-2-1-5-2 |
use category |
Type AC conforms to IEC 60947-2 |
Type AC conforms to IEC 60947-2 |
|
AC-3 conforms to IEC 60947-4-1 |
AC-3 conforms to IEC 60947-4-1 |
Rated working voltage [Ue] |
690 V AC 50/60 Hz conforming to IEC 60947-2 |
690 V AC 50/60 Hz conforming to IEC 60947-2 |
Rated insulation voltage [Ui] |
690 V AC 50/60 Hz conforming to IEC 60947-2 |
690 V AC 50/60 Hz conforming to IEC 60947-2 |
|
600 V AC 50/60 Hz conforming to UL 508 |
600 V AC 50/60 Hz conforming to UL 508 |
|
600 V AC 50/60 Hz conforming to CSA C22.2 No 14 |
600 V AC 50/60 Hz conforming to CSA C22.2 No 14 |
Conventional thermal current [Ith] |
4 A conforming to IEC 60947-4-1 |
9 A conforming to IEC 60947-4-1 |
Rated impulse withstand voltage [Uimp] |
6 kV according to IEC 947-2 |
6 kV according to IEC 947-2 |
power consumption per pole |
2.5W |
2.5W |
Mechanical life |
100000 times |
100000 times |
Electrical life |
100000 cycles for AC-3 at 440 V In |
100000 cycles for AC-3 at 440 V In |
|
100000 cycles for AC-3 at 440 V In/2 |
100000 cycles for AC-3 at 440 V In/2 |
maximum conversions |
25 cyc/h |
25 cyc/h |
specified load |
Continuous according to IEC 60947-4-1 |
Continuous according to IEC 60947-4-1 |
Wiring capacity |
Power circuit: Screw-in terminals 2 1…6 mm² Cable option: Solid without wire terminals Power circuit: |
Power circuit: Screw-in terminals 2 1…6 mm² Cable option: Solid without wire terminals Power circuit: |
|
Screw-in terminals 2 1.5…6 mm² Cable option: Flexible without wire terminals |
Screw-in terminals 2 1.5…6 mm² Cable option: Flexible without wire terminals |
|
Power circuit: Screw-in terminals 2 1…4 mm² Cable selection: Flexible with wire terminals |
Power circuit: Screw-in terminals 2 1…4 mm² Cable selection: Flexible with wire terminals |
Tightening torque |
1.7 Nm via screw-in terminal cable 1…4 mm² |
1.7 Nm via screw-in terminal cable 1…4 mm² |
|
1.7 Nm via screw-in terminal cable 1…6 mm² |
1.7 Nm via screw-in terminal cable 1…6 mm² |
|
1.7 Nm via screw-in terminal cable 1.5…6 mm² |
1.7 Nm via screw-in terminal cable 1.5…6 mm² |
Breaking capacity |
Icu: >= 100 kA at 230/240 V AC 50/60 Hz conforming to IEC 60947-2 |
Icu: >= 100 kA at 230/240 V AC 50/60 Hz conforming to IEC 60947-2 |
|
Icu: >= 100 kA at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 |
Icu: >= 100 kA at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 |
|
Icu: >= 100 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 |
Icu: 15 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 |
|
Icu: >= 100 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 |
Icu: 10 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 |
|
Icu: 3 kA at 690 V AC 50/ 60 Hz conforming to IEC 60947-2 |
Icu: 3 kA at 690 V AC 50/60 Hz conforming to IEC 60947-2 |
Rated operating short-circuit breaking capacity [Ics] |
75 % at 690 V AC 50/60 Hz conforming to IEC 60947-2 |
100 % at 440 V AC 50/60 Hz conforming to IEC 60947-2 |
|
|
100 % at 500 V AC 50/60 Hz conforming to IEC 60947-2 |
|
|
75 % at 690 V AC 50/60 Hz conforming to IEC 60947-2 2 |
high |
89mm |
89 mm |
width |
44.5 mm |
44.5 mm |
depth |
91 mm |
91 mm |
product weight |
0.26kg |
0.26kg |
environment |
|
|
Standards compliant |
GB 14048.4 |
GB 14048.4 |
|
IEC 60947-1 |
IEC 60947-1 |
|
IEC 60947-2 |
IEC 60947-2 |
|
IEC 60947-4-1 |
IEC 60947-4-1 |
certified product |
CCC |
CCC |
|
UKCA |
UKCA |
|
CE |
CE |
Protective measures |
TH |
TH |
IP protection class |
IP20 complies with screwed (body) |
IP20 complies with screwed (body) |
Shock and vibration resistance |
Shock resistance 11 ms (30 gn) conforming to IEC 60068-2-27 |
Shock resistance 11 ms (30 gn) conforming to IEC 60068-2-27 |
|
Shock resistance (5 gn (5…150 Hz)) conforming to IEC 60068-2-6 |
Shock resistance (5 gn (5…150 Hz)) conforming to IEC 60068-2-6 |
ambient temperature |
-20…40 °C In cabinet |
-20…40 °C In cabinet |
|
-20…60 °C Body |
-20…60 °C Body |
storage environment temperature |
-40…80°C |
-40…80°C |
Fire resistance and abnormal high temperature resistance |
960 °C conforming to IEC 60695-2-1 |
960 °C conforming to IEC 60695-2-1 |
working altitude |
<= 2000m |
<= 2000m |
packaging unit |
|
|
Unit Type of Package 1 |
PCE |
PCE |
Number of Units in Package 1 |
1 |
1 |
Package 1 Height |
4.93cm |
5.14cm |
Package 1 Width |
9.02 cm |
9.29cm |
Package 1 Length |
9.38cm |
9.78cm |
Package 1 Weight |
282.6g |
299.2g |
Unit Type of Package 2 |
S02 |
S02 |
Number of Units in Package 2 |
20 |
20 |
Package 2 Height |
15.0cm |
15.0cm |
Package 2 Width |
30.0cm |
30.0cm |
Package 2 Length |
40.0cm |
40.0cm |
Package 2 Weight |
6.044 kg |
6.376 kg |
Unit Type of Package 3 |
P06 |
P06 |
Number of Units in Package 3 |
400 |
400 |
Package 3 Height |
90.0cm |
90.0cm |
Package 3 Width |
60.0cm |
60.0cm |
Package 3 Length |
80.0cm |
80.0cm |
Package 3 Weight |
130.88kg |
137.52kg |
contract warranty |
|
|
Warranty |
18 months |
18 months |