| Main | ||
| Part Number | LP1K090085MD | LP1K09008MD | 
| Product Series | TeSys K | TeSys K | 
| Product Series | TeSys | TeSys K | 
| product type | Contactor | Contactor | 
| product short name | LP1K | LP1K | 
| Application field of contactor | Applied to non-inductive or micro-inductive load, resistance furnace | Applied to non-inductive or micro-inductive load, resistance furnace | 
| use category | AC-1 | AC-1 | 
| number of poles | 4P | 4P | 
| Loop contact type | 2 NO + 2 NC | 2 NO + 2 NC | 
| Rated operating current [Ie] | 20 A 50 °C) at <= 440 V AC AC-1 for power circuits 16 A 70 °C) at 690 V AC AC-1 for power circuits | 20 A 50 °C) at <= 440 V AC AC-1 for power circuits 16 A 70 °C) at 690 V AC AC-1 for power circuits | 
| Additional information | ||
| Control voltage limit | Operating: 0.8…1.15 Uc 50 °C) Release: 0.1…0.75 Uc 50 °C) | Operating: 0.8…1.15 Uc 50 °C) Release: 0.1…0.75 Uc 50 °C) | 
| Rated insulation voltage [Ui] | Power circuit: 600 V conforming to UL 508 Power circuit: 690 V conforming to IEC 60947-4-1 Power circuit: 600 V conforming to CSA C22.2 No 14 | Power circuit: 600 V conforming to UL 508 Power circuit: 690 V conforming to IEC 60947-4-1 Power circuit: 600 V conforming to CSA C22.2 No 14 | 
| Rated impulse withstand voltage [Uimp] | 8kV | 8kV | 
| Overvoltage category | III | III | 
| installation method | Printed circuit | DIN rail installation base plate installation | 
| flame retardant | V1 Conforms to UL 94 requirements2 Conforms to NF F 16-101 requirements2 Conforms to NF F 16-102 | V1 Conforms to UL 94 requirements2 Conforms to NF F 16-101 requirements2 Conforms to NF F 16-102 | 
| Rated working voltage [Ue] | Power circuit: 690 V AC 50/60 Hz | Power circuit: 690 V AC 50/60 Hz | 
| Conventional thermal current [Ith] | 20 A at <50 °C for power circuits | 20 A at <50 °C for power circuits | 
| Rated making capacity [Irms] | 110 A AC for power circuits according to NF C 63-110 110 A AC for power circuits according to IEC 60947 | 110 A AC for power circuits according to NF C 63-110 110 A AC for power circuits according to IEC 60947 | 
| Rated breaking capacity | 110 A at 415 V conforming to IEC 60947 110 A at 440 V conforming to IEC 60947 80 A at 500 V conforming to IEC 60947 110 A at 220…230 V conforming to IEC 60947 110 A at 380 …400 V conforming to IEC 60947 70 A at 660…690 V conforming to IEC 60947 | 110 A at 415 V conforming to IEC 60947 110 A at 440 V conforming to IEC 60947 80 A at 500 V conforming to IEC 60947 110 A at 220…230 V conforming to IEC 60947 110 A at 380 …400 V conforming to IEC 60947 70 A at 660…690 V conforming to IEC 60947 | 
| Fuses for use with relays | 25 A gG at <= 440 V for power circuits 25 A aM for power circuits | 25 A gG at <= 440 V for power circuits 25 A aM for power circuits | 
| average impedance | 3 mΩ – Ith 20 A 50 Hz for power circuits | 3 mΩ – Ith 20 A 50 Hz for power circuits | 
| Surge power (W) | 3W (20°C) | 3W (20°C) | 
| Holding power consumption(W) | 3 W at 20 °C | 3 W at 20 °C | 
| action time | 30…40 ms coil energizing and NO contact closing 10 ms coil discharging and NO opening 25…35 ms coil energizing and NC contact opening 15 ms coil de-energizing and NC closing | 30…40 ms coil energizing and NO contact closing 10 ms coil discharging and NO opening 25…35 ms coil energizing and NC contact opening 15 ms coil de-energizing and NC closing | 
| Safety and reliability level | B10d = Contactor for 1369863 nominal loads according to EN/ISO 13849-1 B10d = Contactor for 20000000 mechanical loads according to EN/ISO 13849-1 | B10d = Contactor for 1369863 nominal loads according to EN/ISO 13849-1 B10d = Contactor for 20000000 mechanical loads according to EN/ISO 13849-1 | 
| Mechanical life | 10 Mcycles | 10 Mcycles | 
| operating frequency | 3600 times/hour | 3600 times/hour | 
| high | 58 mm | 58 mm | 
| width | 45 mm | 45 mm | 
| depth | 57 mm | 57 mm | 
| Product Weight | 0.225 kg | 0.225 kg | 
| environment | ||
| certified product | UL CSA UKCA | UL CSA UKCA | 
| operating temperature | -25…50°C | -25…50°C | 
| storage environment temperature | -50…80 °C | -50…80 °C | 
| working altitude | 2000 meters without | 2000 meters without | 
| packaging unit | ||
| Unit Type of Package 1 | PCE | PCE | 
| Number of Units in Package 1 | 1 | 1 | 
| Package 1 Height | 4.5cm | 4.8cm | 
| Package 1 Width | 6.0cm | 6.0cm | 
| Package 1 Length | 6.5cm | 6.5cm | 
| Package 1 Weight | 236.0g | 213.0g | 
| Unit Type of Package 2 | S02 | S02 | 
| Number of Units in Package 2 | 40 | 40 | 
| Package 2 Height | 15.0cm | 15.0cm | 
| Package 2 Width | 30.0cm | 30.0cm | 
| Package 2 Length | 40.0cm | 40.0cm | 
| Package 2 Weight | 9.673kg | 8.909kg | 
| Unit Type of Package 3 | P06 | |
| Number of Units in Package 3 | 640 | |
| Package 3 Height | 75.0cm | |
| Package 3 Width | 80.0cm | |
| Package 3 Length | 60.0cm | |
| Package 3 Weight | 162.768kg | |
| contract warranty | ||
| Warranty | 18 months | 18 months | 
| Weight | N/A | 
|---|---|
| Dimensions | N/A |