| Main | 
| Part Number | LR9D5367 | 
| Product Series | TeSys | 
| product name | TeSys LRD | 
| TeSys Deca | 
| product type | Electronic Thermal Overload Relay | 
| product short name | LR9D | 
| Relay application | Motor protection | 
| The scope of products | LC1D115 | 
| LC1D150 | 
| NSX circuit breaker | 
| Network Type | AC | 
| Thermal release drag rating | Class 10 conforming to IEC 60947-4-1 | 
| Signal indication function | Call the police | 
| Relay setting range | 60…100A | 
| Rated insulation voltage [Ui] | Power circuit: 1000 V conforming to IEC 60947-4-1 | 
| Power circuit: 600 V conforming to CSA | 
| Power circuit: 600 V conforming to UL | 
| Additional information | 
| Network frequency | 50…60Hz | 
| Rated supply voltage [Us] | 24 V DC | 
| Power supply voltage range | 17…32V | 
| installation method | DIN rail installation under the contactor | 
| Trip threshold | 1.05 +/- 0.06 In Alarm per IEC 60947-4-1 | 
| 1.12 +/- 0.06 In Power off per IEC 60947-4-1 | 
| Auxiliary contact type | 1 NO + 1 NC | 
| Conventional thermal current [Ith] | 5 A for signal circuits | 
| Rated working voltage [Ue] | 690 V AC 0…400 Hz for power circuits according to IEC 60947-4-1 | 
| Fuses for use with relays | 4 A gG for signal circuit | 
| 4 A BS for signal circuit | 
| Rated impulse withstand voltage [Uimp] | 6 kV according to IEC 60947-1 | 
| phase loss sensitivity | Trip within 4 s +/- 20 % according to IEC 60947-4-1 | 
| control type | Red (push) button: stop (make N/C contact act, not affect N/O contact) | 
| blue (push) button: reset | 
| Temperature compensation | -20…60°C | 
| Switching capacity (mA) | 0…150mA | 
| maximum voltage drop | <2.5 V closed state | 
| Wiring capacity | Power circuit: terminal post | 
| control circuit: screw-on1 cable 0.5…1.5 mm² flexible without | 
| control circuit: screw-on2 cable 0.5…1.5 mm² flexible without | 
| alarm circuit: screw-on1 cable 0.5…1.5 mm² flexible line without | 
| Tightening torque | Alarm circuit: 0.45 Nm | 
| Power circuit: 18 Nm via terminal screw: M8 | 
| Control circuit: 1.2 Nm | 
| high | 118 mm | 
| width | 115 mm | 
| depth | 125 mm | 
| Product Weight | 0.885 kg | 
| environment | 
| climate tolerance | Conforms to IACS E10 | 
| IP protection class | IP20 conforming to IEC 60529 | 
| ambient temperature | -20…60 °C without derating according to IEC 60947-4-1 | 
| storage environment temperature | -60…70°C | 
| working altitude | <= 2000 m without derating | 
| Shock and vibration resistance | Shock resistance: 2 gn (5…300 Hz) conforming to IEC 60068-2-6 | 
| Shock resistance: 13 gn (11 ms) conforming to IEC 60068-2-7 | 
| Insulation properties | 1.89 kV at 50 Hz conforming to IEC 60947-1 | 
| Standards compliant | EN/IEC 60947-4-1 | 
| EN/IEC 60947-5-1 | 
| UL 60947-4-1 | 
| UL 60947-5-1 | 
| DIN 3852-Y | 
| CSA C22.2 No 60947-5-1 | 
| GB/T 14048.4 | 
| GB/T 14048.5 | 
| certified product | UL | 
| CSA | 
| CCC | 
| UKCA | 
| packaging unit | 
| Unit Type of Package 1 | PCE | 
| Number of Units in Package 1 | 1 | 
| Package 1 Height | 15.0cm | 
| Package 1 Width | 16.0cm | 
| Package 1 Length | 13.0cm | 
| Package 1 Weight | 934.0g | 
| Unit Type of Package 2 | S04 | 
| Number of Units in Package 2 | 12 | 
| Package 2 Height | 30.0cm | 
| Package 2 Width | 40.0cm | 
| Package 2 Length | 60.0cm | 
| Package 2 Weight | 11.978kg | 
| contract warranty | 
| Warranty | 18 months |