Commercial Data

Item number 2901999
Packing unit 1 pc
Minimum order quantity 1 pc
Product key DK1121
Catalog page Page 76 (C-5-2019)
GTIN 4046356649506
Weight per piece (including packing) 105.9 g
Weight per piece (excluding packing) 91.03 g
Customs tariff number 85437090
Country of origin DE

Notes

Utilization restriction
EMC note EMC: class A product, see manufacturer’s declaration in the download area

Product Properties

Product type Signal conditioner
Product family MINI Analog Pro
No. of channels 1
Type Signal conditioner
Insulation characteristics: GB Standard
Overvoltage category II
Pollution degree 2

Electrical Properties

Electrical isolation 3-way isolation
Electrical isolation between input and output yes
Limit frequency (3 dB)  30 Hz
Protective circuit Transient protection
Signal transmission behavior In = Out
Step response (10-90%)  10 ms
Maximum temperature coefficient 0.01 %/K
Temperature coefficient, typical 0.01 %/K
Maximum transmission error 0.1 % (of final value)
Electrical isolation Input/output/power supply
Rated insulation voltage 300 Vrms
Test voltage 3 kV AC (50 Hz, 60 s)
Insulation Reinforced insulation according to IEC/EN 61010-1
Supply
Nominal supply voltage 24 V DC
Supply voltage range 9.6 V DC … 30 V DC (The DIN rail connector (ME 6,2 TBUS-2 1,5/5-ST-3,81 GN, item no. 2869728) can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail in accordance with EN 60715)
Typical current consumption 25 mA (24 V DC)
54 mA (12 V DC)
Power consumption ≤ 800 mW (at 9.6 V DC)

Input Data

Signal: Current
Number of inputs 1
Configurable/programmable no
Current input signal 0 mA … 20 mA
4 mA … 20 mA
Input resistance current input approx. 63 Ω (+0.7 V for test diode)

Output Data

Signal: Current
Number of outputs 1
Configurable/programmable no
Non-load voltage < 17 V
Current output signal 0 mA … 20 mA
4 mA … 20 mA
Max. current output signal 22 mA
Load/output load current output ≤ 600 Ω (at 20 mA)
Ripple < 20 mVPP (at 600 Ω)

Connection Data

Connection method Push-in connection
Stripping length 10 mm
Conductor cross section rigid 0.2 mm² … 2.5 mm² (with ferrule)
0.14 mm² … 2.5 mm² (without ferrule)
Conductor cross section flexible 0.14 mm² … 2.5 mm²
Conductor cross section AWG 24 … 12 (flexible)

Ex Data

Ex installation (EPL) Gc
Div. 2

Signaling

Status display Green LED (supply voltage)

Dimension

Width 6.2 mm
Height 109.81 mm
Depth 119.2 mm

Material Specifications

Color gray (RAL 7042)
Housing material PBT
Fire protection for rail vehicles (DIN EN 45545-2) R22 HL 1 – HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R23 HL 1 – HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R24 HL 1 – HL 2

Environmental and real-life conditions 

Ambient conditions
Degree of protection IP20 (not assessed by UL)
Ambient temperature (operation) -40 °C … 70 °C
Ambient temperature (storage/transport) -40 °C … 85 °C
Permissible humidity (operation) 5 % … 95 % (non-condensing)

Approvals

CE
Certificate CE-compliant
ATEX
Identification  II 3 G Ex ec IIC T4 Gc
Certificate BVS 19 ATEX E 047 X
IECEx
Identification Ex ec IIC T4 Gc
Certificate IECEx BVS 19.0041X
CCC / China-Ex
Identification Ex ec IIC T4 Gc
UL, USA/Canada
Identification UL 508 Listed
Class I, Div. 2, Groups A, B, C, D T6
Class I, Zone 2, Group IIC T6
Shipbuilding approval
Certificate DNV GL TAA00002UA
EAC Ex
Identification  2Ex ec IIC T4 Gc
Certificate BY/112 02.01 TP012 103.01 00079
Shipbuilding data
Temperature B
Humidity B
Vibration A
EMC A
Enclosure Required protection according to the Rules shall be provided upon installation on board

EMC Data

Electromagnetic compatibility Conformance with EMC directive
Noise immunity EN 61000-6-2
Note When being exposed to interference, there may be minimal deviations.
Noise emission
Standards/regulations EN 61000-6-4
Electrostatic discharge
Standards/regulations EN 61000-4-2
Electrostatic discharge
Comments Safety measures must be taken to prevent electrostatic discharge.
Electromagnetic HF field
Designation Electromagnetic RF field
Standards/regulations EN 61000-4-3
Fast transients (burst)
Designation Fast transients (burst)
Standards/regulations EN 61000-4-4
Surge current load (surge)
Standards/regulations EN 61000-4-5
Conducted interference
Designation Conducted interferences
Standards/regulations EN 61000-4-6

Standard And Resolutions

Electrical isolation 3-way isolation
GB Standard
Standards/regulations GB/T 3836.1
GB/T 3836.3
GB/T 3836.4

Mounting

Mounting type DIN rail mounting
Assembly note The DIN rail connector can be used for bridging the supply voltage. It can be snapped onto a 35 mm EN 60715 DIN rail.
Mounting position any

Additional information

Weight 0.1059 kg
Dimensions 11.92 × 0.62 × 10.981 cm

Related Products

IDS USB 3
IDS_Miscellaneous Cables_1007830
Omron_Memory_Cassette_CP1W-ME05M
MPHC-03M-150(F)
BX700-DFR
IDS_camera_GV-50C0CP_1
Select your currency