E5DC / E5DC-B – General-purpose – Omron Temperature Controllers

Product Description

Models with Screw Terminal Blocks

List of Models

Control
output
No. of
auxiliary
outputs
Options Model Model
HB alarm
and
HS alarm
No. of
event
inputs
Commu-
nications
Power supply voltage Power supply voltage
100 to 240 VAC 24 VAC/DC
Relay output RS-485 E5DC-RX0ASM-015 E5DC-RX0DSM-015
E5DC-RX0AUM-015 E5DC-RX0DUM-015
2 E5DC-RX2ASM-000 E5DC-RX2DSM-000
E5DC-RX2AUM-000 E5DC-RX2DUM-000
Detection for
single-phase
heater
RS-485 E5DC-RX2ASM-002 E5DC-RX2DSM-002
E5DC-RX2AUM-002 E5DC-RX2DUM-002
1 E5DC-RX2ASM-017 E5DC-RX2DSM-017
E5DC-RX2AUM-017 E5DC-RX2DUM-017
Voltage output
(for driving SSR)
RS-485 E5DC-QX0ASM-015 E5DC-QX0DSM-015
E5DC-QX0AUM-015 E5DC-QX0DUM-015
2 E5DC-QX2ASM-000 E5DC-QX2DSM-000
E5DC-QX2AUM-000 E5DC-QX2DUM-000
Detection for
single-phase
heater
RS-485 E5DC-QX2ASM-002 E5DC-QX2DSM-002
E5DC-QX2AUM-002 E5DC-QX2DUM-002
1 E5DC-QX2ASM-017 E5DC-QX2DSM-017
E5DC-QX2AUM-017 E5DC-QX2DUM-017
Linear current
output
RS-485 E5DC-CX0ASM-015 E5DC-CX0DSM-015
E5DC-CX0AUM-015 E5DC-CX0DUM-015
2 E5DC-CX2ASM-000 E5DC-CX2DSM-000
E5DC-CX2AUM-000 E5DC-CX2DUM-000
RS-485 E5DC-CX2ASM-015 E5DC-CX2DSM-015
E5DC-CX2AUM-015 E5DC-CX2DUM-015
1 E5DC-CX2ASM-016 E5DC-CX2DSM-016
E5DC-CX2AUM-016 E5DC-CX2DUM-016

 

Ratings

Power supply voltage A in model number: 100 to 240 VAC, 50/60 Hz
D in model number: 24 VAC, 50/60 Hz; 24 VDC
Operating voltage range 85 to 110% of rated supply voltage
Power consumption 4.9 VA max. at 100 to 240 VAC, and 2.8 VA max. at 24 VDC or 1.5 W max. at 24 VDC
Sensor input Temperature input
Thermocouple: K, J, T, E, L, U, N, R, S, B, C/W, or PL II
Platinum resistance thermometer: Pt100 or JPt100
Infrared temperature sensor (ES1B): 10 to 70°C, 60 to 120°C, 115 to 165°C, or 140 to
260°C
Analog input
Current input: 4 to 20 mA or 0 to 20 mA
Voltage input: 1 to 5 V, 0 to 5 V, or 0 to 10 V
Input impedance Current input: 150 Ω max., Voltage input: 1 MΩ min.
(Use a 1:1 connection when connecting the ES2-HB-N/THB-N.)
Control method ON/OFF control or 2-PID control (with auto-tuning)
Control
output
Relay output SPST-NO, 250 VAC, 3 A (resistive load), electrical life: 100,000 operations, minimum
applicable load: 5 V, 10 mA (reference value)
Voltage output
(for driving SSR)
Output voltage 12 VDC ±20% (PNP), max. Load current: 21 mA, with short-circuit
protection circuit
Linear current
output
4 to 20 mA DC/0 to 20 mA DC, load: 500 Ω max., resolution: Approx. 10,000
Auxiliary
output
Number of outputs 2 (depends on model)
Output
specifications
SPST-NO relay outputs: 250 VAC, 2 A (resistive load),
Electrical life: 100,000 operations, Minimum applicable load: 10 mA at 5 V (reference
value)
Event
input
*1
Number of inputs 1 (depends on model)
External contact
input
specifications
Contact input ON: 1 kΩ max., OFF: 100 kΩ min.
Non-contact input ON: Residual voltage 1.5 V max.; OFF: Leakage current 0.1 mA max.
Current flow: approx. 7 mA per contact
Setting method Digital setting using front panel keys
Indication method 11-segment digital displays and individual indicators
Character height: PV: 8.5 mm, SV: 8.0 mm
Multi SP Up to eight set points (SP0 to SP7) can be saved and selected using the event inputs,
key operations, or serial communications. *2
Bank switching None
Other functions Manual output, heating/cooling control, loop burnout alarm, SP ramp, other alarm
functions, heater burnout (HB) alarm (including SSR failure (HS) alarm), 40% AT,
100% AT, MV limiter, input digital filter, self tuning, robust tuning, PV input shift, run/
stop, protection functions, extraction of square root, MV change rate limit, logic
operations, temperature status display, simple programming, moving average of input
value, display brightness setting, simple transferoutput, *3 and work bit message *3
Ambient operating
temperature
-10 to 55°C (with no condensation or icing), For 3-year warranty: -10 to 50°C with
standard mounting (with no condensation or icing)
Ambient operating humidity 25 to 85%
Storage temperature -25 to 65°C (with no condensation or icing)
Altitude 2,000 m max.
Recommended fuse T2A, 250 VAC, time-lag, low-breaking capacity
Installation environment Overvoltage category II, Pollution Degree 2 (EN/IEC/UL 61010-1)

 

*1. This function is not supported by the E5DC-B. Refer to Model Number Legend.
*2. Only two set points are selectable for event inputs.
*3. Usage is possible for the Digital Temperature Controllers manufactured in July 2014 or later.

 

Analog input

Input type Current Voltage
Input specification 4 to 20 mA 0 to 20 mA 1 to 5 V 0 to 5 V 0 to 10 V
Setting range Usable in the following ranges by scaling:
-1999 to 9999, -199.9 to 999.9,
-19.99 to 99.99 or -1.999 to 9.999
Set value 25 26 27 28 29

 

Characteristics

Indication accuracy
(when mounted
individually, ambient
temperature of 23°C)
Thermocouple: (±0.3 % of indication value or ±1°C, whichever is greater) ±1 digit max. *1
Platinum resistance thermometer: (±0.2 % of indication value or ±0.8°C, whichever is
greater) ±1 digit max.
Analog input: ±0.2% FS ±1 digit max.
CT input: ±5% FS ±1 digit max.
Simple transfer output
accuracy
±0.3% FS max.*2
Influence of
temperature *3
Thermocouple input (R, S, B, C/W, PL II): (±1% of indication value or ±10°C, whichever is
greater) ±1 digit max.
Other thermocouple input: (±1% of indication value or ±4°C, whichever is greater) ±1 digit
max. *4
Platinum resistance thermometer: (±1% of indication value or ±2°C, whichever is greater) ±1
digit max.
Analog input: ±1% FS ±1 digit max.
CT input: ±5% FS ±1 digit max.
Influence of voltage *3
Influence of EMS.
(at EN 61326-1)
Installation influence
(E5DC only)
R, S, B, W, or PLII thermocouple: (±1% of PV or ±10°C, whichever is greater) ±1 digit max.
Other thermocouple: (±1% of PV or ±4°C, whichever is greater) ±1 digit max. *4
Input sampling period 50 ms
Hysteresis Temperature input: 0.1 to 999.9°C or °F (in units of 0.1°C or °F)
Analog input: 0.01% to 99.99% FS (in units of 0.01% FS)
Proportional band (P) Temperature input: 0.1 to 999.9°C or °F (in units of 0.1°C or °F)
Analog input: 0.1% to 999.9% FS (in units of 0.1% FS)
Integral time (I) 0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *5
Derivative time (D) 0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *5
Proportional band (P)
for cooling
Temperature input: 0.1 to 999.9°C or °F (in units of 0.1°C or °F)
Analog input: 0.1% to 999.9% FS (in units of 0.1% FS)
Integral time (I) for
cooling
0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *5
Derivative time (D) for
cooling
0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *5
Control period 0.1, 0.2, 0.5, 1 to 99 s (in units of 1 s)
Manual reset value 0.0% to 100.0% (in units of 0.1%)
Alarm setting range -1,999 to 9,999 (decimal point position depends on input type)
Influence of signal
source resistance
Thermocouple: 0.1°C/Ω max. (100 Ω max.),
Platinum resistance thermometer: 0.1°C/Ω max. (10 Ω max.)
Insulation resistance 20 MΩ min. (at 500 VDC)
Dielectric strength 3,000 VAC, 50/60 Hz for 1 min between terminals of different charge
Vibration Malfunction 10 to 55 Hz, 20 m/s2 for 10 min each in X, Y and Z directions
Resistance 10 to 55 Hz, 20 m/s2 for 2 hr each in X, Y, and Z directions
Shock Malfunction 100 m/s2, 3 times each in X, Y, and Z directions
Resistance 300 m/s2, 3 times each in X, Y, and Z directions
Weight Main unit: Approx. 80 g, Models with Screw Terminal Unit: Approx. 40 g,
Models with Push-In Plus Terminal Unit: Approx. 40 g
Degree of protection Main unit: IP20, Terminal unit: IP00
Memory protection Non-volatile memory (number of writes: 1,000,000 times)
Setup Tool CX-Thermo version 4.6 or higher
Setup Tool port E5DC/E5DC-B bottom panel: An E58-CIFQ2 USB-Serial Conversion Cable is used to
connect a USB port on the computer. *6
E5DC/E5DC-B front panel: An E58-CIFQ2 USB-Serial Conversion Cable and E58-CIFQ2-E
Conversion Cable are used together to connect a USB port on the computer. *6
Standards Approved
standards
cULus: UL 61010-1/CSA C22.2 No.61010-1, Korean wireless regulations (Radio law: KC Mark)
(Some models only.) *7, Lloyd’s standards (E5DC only) *8
Conformed
standards
EN 61010-1 (IEC 61010-1), RCM
EMC EMI: EN61326-1 *9
Radiated Interference Electromagnetic Field Strength: EN55011 Group 1, class A
Noise Terminal Voltage: EN55011 Group 1, class A
EMS: EN61326-1 *9
ESD Immunity: EN61000-4-2
Electromagnetic Field Immunity: EN61000-4-3
Burst Noise Immunity: EN61000-4-4
Conducted Disturbance Immunity: EN61000-4-6
Surge Immunity: EN61000-4-5
Voltage Dip/Interrupting Immunity: EN61000-4-11

 

*1. The indication accuracy of K thermocouples in the -200 to 1,300°C range, T and N thermocouples at a temperature of
−100°C max., and U and L thermocouples at any temperature is ±2°C ±1 digit max. The indication accuracy of B
thermocouples at a temperature of 400°C max. is not specified. The indication accuracy of B thermocouples at a
temperature of 400 to 800°C is ±3°C max.
The indication accuracy of R and S thermocouples at a temperature of 200°C max. is ±3°C ±1 digit max. The
indication accuracy of C/W thermocouples is (±0.3% of PV or ±3°C, whichever is greater) ±1 digit max.
The indication accuracy of PLII thermocouples is (±0.3% of PV or ±2°C, whichever is greater) ±1 digit max.
*2. However, the precision between 0 and 4 mA for a 0 to 20 mA output is ±1% FS max.
*3. Ambient temperature: −10°C to 23°C to 55°C, Voltage range: −15% to 10% of rated voltage
*4. K thermocouple at −100°C max.: ±10°C max.
*5. The unit is determined by the setting of the Integral/Derivative Time Unit parameter.
*6. External serial communications (RS-485) and USB-Serial Conversion Cable communications can be used at the
same time.
*7. Refer to your OMRON website for the most recent information on applicable models.
*8. Refer to information on maritime standards in Shipping Standards on Data Sheet for compliance with Lloyd’s
Standards.
*9. Industrial electromagnetic environment (EN/IEC 61326-1 Table 2)

 

 