Phoenix Contact develops terminal blocks, power supplies, relays, connectors, signal conditioners, controllers & PLCs, I/O systems, Industrial Ethernet, controller system cabling, PCB terminal blocks & connectors, and surge suppression.
| Item number | 2865625 | 
| Packing unit | 1 pc | 
| Minimum order quantity | 1 pc | 
| Product key | DK111Z | 
| Catalog page | Page 175 (C-5-2019) | 
| GTIN | 4046356324618 | 
| Weight per piece (including packing) | 162.8 g | 
| Weight per piece (excluding packing) | 162.8 g | 
| Customs tariff number | 85437090 | 
| Country of origin | DE | 
| Product type | Feed-in module | 
| Product family | MACX Analog | 
| Electrical isolation | |
| Overvoltage category | II | 
| Pollution degree | 2 | 
| Electrical isolation Input/switching output | |
| Rated insulation voltage | 50 V AC/DC | 
| Supply | |
| Nominal supply voltage | 24 V DC | 
| Signal | |
| Voltage input signal | 19.2 V DC … 30 V DC (24 V DC, -20 % … +25 %) | 
| Fuse | 5 A (replaceable), slow-blow 250 V AC | 
| Polarization and surge protection | Yes | 
| Switching: Relay | |
| Contact switching type | 1 changeover contact | 
| Contact material | Gold (Au) | 
| Maximum switching voltage | 50 V AC (2 A) | 
| 30 V DC (2 A) | |
| 50 V DC (0.22 A) | |
| Signal | |
| Max. current output signal | 3.75 A | 
| Output voltage | Input voltage – max 0.8 V at 3.75 A | 
| Connection method | Screw connection | 
| Stripping length | 7 mm | 
| Screw thread | M3 | 
| Conductor cross section rigid | 0.2 mm² … 2.5 mm² | 
| Conductor cross section flexible | 0.2 mm² … 2.5 mm² | 
| Conductor cross section AWG | 24 … 14 | 
| Tightening torque | 0.5 Nm … 0.6 Nm | 
| Ex installation (EPL) | Gc | 
| Div. 2 | 
| Status display | 1 x red LED (error) | 
| 2x green LEDs (PWR1 and PWR2) | 
| Width | 17.5 mm | 
| Height | 112.5 mm | 
| Depth | 113.7 mm | 
| Depth NS 35/7,5 | 114.5 mm (Snapped onto DIN rail NS 35/7,5 in accordance with EN 60715) | 
| Color | gray (RAL 7042) | 
| Flammability rating according to UL 94 | V0 (Housing) | 
| Housing material | PA 6.6 | 
| Ambient conditions | |
| Degree of protection | IP20 (not assessed by UL) | 
| Ambient temperature (operation) | -40 °C … 60 °C (Any mounting position) | 
| Ambient temperature (storage/transport) | -40 °C … 80 °C | 
| Permissible humidity (operation) | 5 % … 95 % (non-condensing) | 
| Altitude range (≤ 2000 m) | |
| Altitude | ≤ 2000 m (The technical data refers to altitudes ≤2000 m above mean sea level. For altitudes >2000 m above mean sea level, refer to the data sheet.) | 
| Ambient temperature (operation) | -40 °C … 60 °C | 
| Rated insulation voltage | 50 V AC/DC | 
| Altitude range (≤ 3000 m) | |
| Height range | > 2000 m … 3000 m | 
| Ambient temperature (operation) | -40 °C … 54 °C | 
| Rated insulation voltage | 40 V AC/DC | 
| Altitude range (≤ 4000 m) | |
| Height range | > 3000 m … 4000 m | 
| Ambient temperature (operation) | -40 °C … 48 °C | 
| Rated insulation voltage | 30 V AC/DC | 
| Altitude range (≤ 5000 m) | |
| Height range | > 4000 m … 5000 m | 
| Ambient temperature (operation) | -40 °C … 42 °C | 
| Rated insulation voltage | 30 V AC/DC | 
| CE | |
| Certificate | CE-compliant | 
| ATEX | |
| Identification |  II 3 G Ex ec nC IIC T4 Gc | 
| Certificate | PxCIF08ATEX2865625X | 
| IECEx | |
| Identification | Ex ec nC IIC T4 Gc | 
| Certificate | IECEx IBE 08.0004X | 
| CCC / China-Ex | |
| Identification | Ex ec nC IIC T4 Gc | 
| Certificate | 2021122303114198 | 
| UL, USA/Canada | |
| Identification | UL 61010 Listed | 
| Class I, Div. 2, Groups A, B, C, D T4 | |
| Class I, Zone 2, Group IIC T4 | |
| Shipbuilding approval | |
| Certificate | DNV GL TAA0000AG | 
| Shipbuilding data | |
| Temperature | B | 
| Humidity | B | 
| Vibration | A | 
| EMC | B | 
| Enclosure | Required protection according to the Rules shall be provided upon installation on board | 
| Electromagnetic compatibility | Conformance with EMC directive | 
| Noise immunity | EN 61000-6-2 | 
| Note | When being exposed to interference, there may be minimal deviations. | 
| Noise emission | |
| Standards/regulations | EN 61000-6-4 | 
| Electromagnetic HF field | |
| Designation | Electromagnetic RF field | 
| Standards/regulations | EN 61000-4-3 | 
| Evaluation criterion | A | 
| Fast transients (burst) | |
| Designation | Fast transients (burst) | 
| Standards/regulations | EN 61000-4-4 | 
| Evaluation criterion | A | 
| Conducted interference | |
| Designation | Conducted interferences | 
| Standards/regulations | EN 61000-4-6 | 
| Evaluation criterion | A | 
| GB Standard | |
| Standards/regulations | GB/T 3836.1 | 
| GB/T 3836.3 | |
| GB/T 3836.8 | |
| Mounting type | DIN rail mounting | 
| Weight | 0.1628 kg | 
|---|---|
| Dimensions | 11.45 × 1.75 × 11.25 cm |