| DC operation | |
| Input voltage | 24 V DC |
| Input voltage range | 100 V DC … 350 V DC |
| Voltage type of supply voltage | DC |
| Inrush current | < 34 A (< 1.1 A2s) |
| Inrush current integral (I2t) | < 1.1 A2s |
| Mains buffering time | see diagram |
| Buffer period | 20 min. (2 A) |
| Rotary selector switch | Can be set to: 0.5 min; 1 min; 2 min; 3 min; 5 min; 10 min; 15 min; 20 min; 30 min; permanent |
| Current consumption | 0.6 A |
| 0.85 A (230 V AC) | |
| 1.1 A | |
| 1.5 A (120 V AC) | |
| Protective circuit | Varistor |
| Power factor (cos phi) | approx. 0.5 |
| Typical response time | 100 ms |
| Input fuse | 3.15 A (slow-blow, internal) |
| Permissible backup fuse | B6 B10 B16 |
| Recommended breaker for input protection | 6 A … 16 A (Characteristics B, C, D, K) |
| AC operation | |
| Nominal input voltage range | 100 V AC … 240 V AC |
| Input voltage range | 85 V AC … 264 V AC |
| Voltage type of supply voltage | AC |
| Efficiency | > 83 % |
| Nominal output voltage | 24 V DC (AC input voltage available: 22.5 to 29.5 V DC, AC input voltage not available: 27.9 to 19.2 V DC) |
| Setting range of the output voltage (USet) | 22.5 V DC … 29.5 V DC (normal mode; in the buffer mode, dependent on a battery voltage of 27.9 V DC … 19.2 V DC) |
| Nominal output current (IN) | 2 A |
| Output current limit | max. 3 A |
| Bridging time | 1200 s |
| Derating | 60 °C … 70 °C (2.5%/K) |
| Feedback voltage resistance | 35 V DC |
| Protection against overvoltage at the output (OVP) | < 35 V DC |
| Max. capacitive load | unlimited |
| Control deviation | < 1 % (change in load, static 10 % … 90 %) |
| Residual ripple | < 50 mVPP |
| Output power | 48 W |
| Peak switching voltages nominal load | < 100 mVPP |
| Maximum no-load power dissipation | 3.8 W |
| Power loss nominal load max. | 15 W |
| Power dissipation | 3.8 W |
| 10.1 W | |
| 2.1 W | |
| Rise time | < 100 ms |
| Connection in parallel | yes |
| Connection in series | No |
| Mains operation | |
| Nominal output voltage | 24 V DC |
| Output voltage range | 22.5 V DC … 29.5 V DC |
| Nominal output current (IN) | 2 A |
| Battery operation | |
| Nominal output voltage | 24 V DC |
| Output voltage range | 19.2 V DC … 27.6 V DC (UOUT = UBAT – 0,5 V DC) |
| Nominal output current (IN) | 2 A |
| Signal: Active (high = buffer module is loaded) | |
| Output description | Power Good |
| Maximum switching voltage | ≤ 24 V |
| Output voltage | + 24 V |
| Continuous load current | ≤ 20 mA |
| Signal: Alarm | |
| Output description | Relay output |
| Maximum switching voltage | ≤ 24 V |
| Output voltage | 24 V |
| Continuous load current | ≤ 200 mA |
| Signal: Battery charge | |
| Output description | Relay output |
| Maximum switching voltage | ≤ 24 V |
| Output voltage | 24 V |
| Continuous load current | ≤ 200 mA |
| Signal: Battery mode | |
| Output description | Relay output |
| Maximum switching voltage | ≤ 24 V |
| Output voltage | 24 V |
| Continuous load current | ≤ 200 mA |
| Input | |
| Connection method | Pluggable COMBICON screw connections |
| Conductor cross section, rigid min. | 0.2 mm² |
| Conductor cross section, rigid max. | 2.5 mm² |
| Conductor cross section flexible min. | 0.2 mm² |
| Conductor cross section flexible max. | 2.5 mm² |
| Conductor cross section AWG min. | 24 |
| Conductor cross section AWG max. | 12 |
| Stripping length | 8 mm |
| Screw thread | M3 |
| Tightening torque, min | 0.5 Nm |
| Tightening torque max | 0.6 Nm |
| Output | |
| Connection method | Pluggable COMBICON screw connections |
| Conductor cross section, rigid min. | 0.2 mm² |
| Conductor cross section, rigid max. | 2.5 mm² |
| Conductor cross section flexible min. | 0.2 mm² |
| Conductor cross section flexible max. | 2.5 mm² |
| Conductor cross section AWG min. | 24 |
| Conductor cross section AWG max. | 12 |
| Stripping length | 8 mm |
| Screw thread | M3 |
| Tightening torque, min | 0.5 Nm |
| Tightening torque max | 0.6 Nm |
| Signal | |
| Conductor cross section, rigid min. | 0.2 mm² |
| Conductor cross section, rigid max. | 2.5 mm² |
| Conductor cross section flexible min. | 0.2 mm² |
| Conductor cross section flexible max. | 2.5 mm² |
| Conductor cross section AWG min. | 24 |
| Conductor cross section AWG max. | 12 |
| Screw thread | M3 |
| Tightening torque, min | 0.5 Nm |
| Tightening torque max | 0.6 Nm |
| Width | 67.5 mm |
| Height | 99 mm |
| Depth | 107 mm |
| Item number | 2866640 |
| Packing unit | 1 pc |
| Minimum order quantity | 1 pc |
| Sales Key | CM20 |
| Product Key | CMUM13 |
| Catalog Page | Page 350 (C-4-2019) |
| GTIN | 4046356113533 |
| Weight per Piece (including packing) | 496 g |
| Weight per Piece (excluding packing) | 447 g |
| Customs tariff number | 85371091 |
| Country of origin | CN |
| Degree of protection | IP20 |
| Ambient temperature (operation) | -25 °C … 70 °C (> 60 °C Derating: 2,5 %/K) |
| Ambient temperature (storage/transport) | -40 °C … 85 °C |
| Climatic class | 3K3 (in acc. with EN 60721) |
| Max. permissible relative humidity (operation) | 95 % (at 25 °C, non-condensing) |
| Shock | 18 ms, 30g, in each space direction (according to IEC 60068-2-27) |
| Vibration (operation) | < 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6) |
| 15 Hz … 150 Hz, 2.3g, 90 min. |
| Weight | 0.447 kg |
|---|---|
| Dimensions | 10.7 × 6.75 × 9.9 cm |