Phoenix Contact develops terminal blocks, power supplies, relays, connectors, signal conditioners, controllers & PLCs, I/O systems, Industrial Ethernet, controller system cabling, PCB terminal blocks & connectors, and surge suppression.
Item number | 2901999 |
Packing unit | 1 pc |
Minimum order quantity | 1 pc |
Product key | DK1121 |
Catalog page | Page 76 (C-5-2019) |
GTIN | 4046356649506 |
Weight per piece (including packing) | 105.9 g |
Weight per piece (excluding packing) | 91.03 g |
Customs tariff number | 85437090 |
Country of origin | DE |
Utilization restriction | |
EMC note | EMC: class A product, see manufacturer’s declaration in the download area |
Product type | Signal conditioner |
Product family | MINI Analog Pro |
No. of channels | 1 |
Type | Signal conditioner |
Insulation characteristics: GB Standard | |
Overvoltage category | II |
Pollution degree | 2 |
Electrical isolation | 3-way isolation |
Electrical isolation between input and output | yes |
Limit frequency (3 dB) | 30 Hz |
Protective circuit | Transient protection |
Signal transmission behavior | In = Out |
Step response (10-90%) | 10 ms |
Maximum temperature coefficient | 0.01 %/K |
Temperature coefficient, typical | 0.01 %/K |
Maximum transmission error | 0.1 % (of final value) |
Electrical isolation Input/output/power supply | |
Rated insulation voltage | 300 Vrms |
Test voltage | 3 kV AC (50 Hz, 60 s) |
Insulation | Reinforced insulation according to IEC/EN 61010-1 |
Supply | |
Nominal supply voltage | 24 V DC |
Supply voltage range | 9.6 V DC … 30 V DC (The DIN rail connector (ME 6,2 TBUS-2 1,5/5-ST-3,81 GN, item no. 2869728) can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail in accordance with EN 60715) |
Typical current consumption | 25 mA (24 V DC) |
54 mA (12 V DC) | |
Power consumption | ≤ 800 mW (at 9.6 V DC) |
Signal: Current | |
Number of inputs | 1 |
Configurable/programmable | no |
Current input signal | 0 mA … 20 mA |
4 mA … 20 mA | |
Input resistance current input | approx. 63 Ω (+0.7 V for test diode) |
Signal: Current | |
Number of outputs | 1 |
Configurable/programmable | no |
Non-load voltage | < 17 V |
Current output signal | 0 mA … 20 mA |
4 mA … 20 mA | |
Max. current output signal | 22 mA |
Load/output load current output | ≤ 600 Ω (at 20 mA) |
Ripple | < 20 mVPP (at 600 Ω) |
Connection method | Push-in connection |
Stripping length | 10 mm |
Conductor cross section rigid | 0.2 mm² … 2.5 mm² (with ferrule) |
0.14 mm² … 2.5 mm² (without ferrule) | |
Conductor cross section flexible | 0.14 mm² … 2.5 mm² |
Conductor cross section AWG | 24 … 12 (flexible) |
Ex installation (EPL) | Gc |
Div. 2 |
Status display | Green LED (supply voltage) |
Width | 6.2 mm |
Height | 109.81 mm |
Depth | 119.2 mm |
Color | gray (RAL 7042) |
Housing material | PBT |
Fire protection for rail vehicles (DIN EN 45545-2) R22 | HL 1 – HL 2 |
Fire protection for rail vehicles (DIN EN 45545-2) R23 | HL 1 – HL 2 |
Fire protection for rail vehicles (DIN EN 45545-2) R24 | HL 1 – HL 2 |
Ambient conditions | |
Degree of protection | IP20 (not assessed by UL) |
Ambient temperature (operation) | -40 °C … 70 °C |
Ambient temperature (storage/transport) | -40 °C … 85 °C |
Permissible humidity (operation) | 5 % … 95 % (non-condensing) |
CE | |
Certificate | CE-compliant |
ATEX | |
Identification | II 3 G Ex ec IIC T4 Gc |
Certificate | BVS 19 ATEX E 047 X |
IECEx | |
Identification | Ex ec IIC T4 Gc |
Certificate | IECEx BVS 19.0041X |
CCC / China-Ex | |
Identification | Ex ec IIC T4 Gc |
UL, USA/Canada | |
Identification | UL 508 Listed |
Class I, Div. 2, Groups A, B, C, D T6 | |
Class I, Zone 2, Group IIC T6 | |
Shipbuilding approval | |
Certificate | DNV GL TAA00002UA |
EAC Ex | |
Identification | 2Ex ec IIC T4 Gc |
Certificate | BY/112 02.01 TP012 103.01 00079 |
Shipbuilding data | |
Temperature | B |
Humidity | B |
Vibration | A |
EMC | A |
Enclosure | Required protection according to the Rules shall be provided upon installation on board |
Electromagnetic compatibility | Conformance with EMC directive |
Noise immunity | EN 61000-6-2 |
Note | When being exposed to interference, there may be minimal deviations. |
Noise emission | |
Standards/regulations | EN 61000-6-4 |
Electrostatic discharge | |
Standards/regulations | EN 61000-4-2 |
Electrostatic discharge | |
Comments | Safety measures must be taken to prevent electrostatic discharge. |
Electromagnetic HF field | |
Designation | Electromagnetic RF field |
Standards/regulations | EN 61000-4-3 |
Fast transients (burst) | |
Designation | Fast transients (burst) |
Standards/regulations | EN 61000-4-4 |
Surge current load (surge) | |
Standards/regulations | EN 61000-4-5 |
Conducted interference | |
Designation | Conducted interferences |
Standards/regulations | EN 61000-4-6 |
Electrical isolation | 3-way isolation |
GB Standard | |
Standards/regulations | GB/T 3836.1 |
GB/T 3836.3 | |
GB/T 3836.4 |
Mounting type | DIN rail mounting |
Assembly note | The DIN rail connector can be used for bridging the supply voltage. It can be snapped onto a 35 mm EN 60715 DIN rail. |
Mounting position | any |
Weight | 0.1059 kg |
---|---|