| Relay: Enabling current path |
| Output description |
1 N/O contact, without delay, floating |
| Number of outputs |
1 (safety-related N/O contacts: 13/14) |
| Contact type |
1 enabling current path |
| Contact material |
AgSnO2 |
| Switching voltage |
min. 12 V AC/DC |
| max. 250 V AC/DC (Observe the load curve) |
| Switching capacity |
min. 60 mW |
| Inrush current |
min. 3 mA |
| max. 6 A |
| Switching capacity in accordance with IEC 60947-5-1 |
4 A (24 V (DC13)) |
| 5 A (250 V (AC15)) |
| Limiting continuous current |
6 A (High demand) |
| 4 A (Low demand) |
| Sq. Total current |
36 A2 (observe derating) |
| Switching frequency |
max. 1 Hz |
| Mechanical service life |
10x 106 cycles |
| Output fuse |
6 A gL/gG |
| 4 A gL/gG (for low-demand applications) |
| Relay: Confirmation current path |
| Output description |
1 N/C contact, without delay, not floating (reference ground: A2) |
| Number of outputs |
1 (safety-related N/C contacts: 21/22) |
| Contact type |
1 confirmation current path |
| Contact material |
AgCuNi, + Au |
| Switching voltage |
min. 20.4 V DC |
| max. 26.4 V DC |
| Switching capacity |
min. 20 mW |
| Inrush current |
min. 1 mA |
| max. 100 mA |
| Limiting continuous current |
100 mA |
| Switching frequency |
max. 1 Hz |
| Mechanical service life |
10x 106 cycles |
| Output fuse |
150 mA Fast-blow |
| Signal: M1 |
| Output description |
PNP |
| Number of outputs |
1 (non-safety-related) |
| Voltage |
approx. 22 V DC (UD – 2 V) |
| Current |
max. 100 mA |
| Maximum inrush current |
500 mA (Δt = 1 ms at Us) |
| Short-circuit protection |
no |
| Output fuse |
150 mA fast blow |