Inosaki is one of the largest Phoenix Contact Distributors to provide terminal block, interface module, power supply and relay. And our best offer for terminal block types are Feed-through, Fuse Modular, Spring Cage, Double Level, and Multi-level, hence the series model references to  PT Series, ST Series, TB Series, UT Series, UK Series. In additional for power supply are QUINT Power, STEP Power, Trio Power, and UNO Power. Please email us for catalog: sales@inosaki.my

Product Description

QUINT POWER power supply units for plant and special engineering reliably start heavy loads with high inrush currents using the POWER BOOST. Thanks to the wide-range input and extensive package of approvals, they can be used in all sectors of industry the world over. The switching output or floating relay contact are used for remote diagnostics.

Dimensions

[fusion_table fusion_table_type=”1″ fusion_table_rows=”” fusion_table_columns=”” margin_top=”1ps” margin_right=”” margin_bottom=”” margin_left=”” hide_on_mobile=”small-visibility,medium-visibility,large-visibility” class=”” id=”” animation_type=”” animation_direction=”left” animation_color=”” hue=”” saturation=”” lightness=”” alpha=”” animation_speed=”0.3″ animation_delay=”0″ animation_offset=””]

Width 157 mm
Height 130 mm
Depth 125 mm
Alternative assembly
Width 122 mm
Height 130 mm
Depth 160 mm

[/fusion_table]

Input data

[fusion_table fusion_table_type=”1″ fusion_table_rows=”” fusion_table_columns=”” margin_top=”1ps” margin_right=”” margin_bottom=”” margin_left=”” hide_on_mobile=”small-visibility,medium-visibility,large-visibility” class=”” id=”” animation_type=”” animation_direction=”left” animation_color=”” hue=”” saturation=”” lightness=”” alpha=”” animation_speed=”0.3″ animation_delay=”0″ animation_offset=””]

AC operation
Nominal input voltage range 100 V AC … 240 V AC
Input voltage range 85 V AC … 264 V AC
90 V DC … 350 V DC
Input voltage range AC 85 V AC … 264 V AC
Input voltage range DC 90 V DC … 350 V DC
Voltage type of supply voltage AC/DC
Inrush current < 15 A (typical)
Inrush current integral (I2t) < 3.2 A2s
AC frequency range 45 Hz … 65 Hz
Frequency range DC 0 Hz
Mains buffering time > 25 ms (120 V AC)
> 25 ms (230 V AC)
Current consumption approx. 4.76 A (120 V AC)
approx. 2.3 A (230 V AC)
Nominal power consumption 524 W
Protective circuit Transient surge protection; Varistor
Typical response time < 1 s
Input fuse 12 A (slow-blow, internal)
Permissible DC backup fuse DC: Connect a suitable fuse upstream
Recommended breaker for input protection 10 A … 16 A (Characteristics B, C, D, K)

[/fusion_table]

Output data

[fusion_table fusion_table_type=”1″ fusion_table_rows=”” fusion_table_columns=”” margin_top=”1ps” margin_right=”” margin_bottom=”” margin_left=”” hide_on_mobile=”small-visibility,medium-visibility,large-visibility” class=”” id=”” animation_type=”” animation_direction=”left” animation_color=”” hue=”” saturation=”” lightness=”” alpha=”” animation_speed=”0.3″ animation_delay=”0″ animation_offset=””]

Efficiency > 92 %
Nominal output voltage 24 V DC ±1 %
Setting range of the output voltage (USet) 22.5 V DC … 28.5 V DC
Nominal output current (IN) 20 A (up to 60 °C)
POWER BOOST (IBoost) 26 A
Derating 60 °C … 70 °C (2.5%/K)
Feedback voltage resistance 35 V DC
Protection against overvoltage at the output (OVP) ≤ 35 V DC
Max. capacitive load unlimited
Active current limitation Approx. IBOOST = 26 A (for short-circuit)
Control deviation < 1 % (change in load, static 10 % … 90 %)
< 2 % (change in load, dynamic 10 % … 90 %)
< 0.1 % (change in input voltage ±10 %)
Residual ripple < 10 mVPP (with nominal values)
Output power 480 W
Peak switching voltages nominal load < 30 mVPP (20 MHz)
Maximum no-load power dissipation < 3 W
Power loss nominal load max. < 44 W
Rise time < 2 ms (UOUT (10 % … 90 %))
Connection in parallel yes, for redundancy and increased capacity
Connection in series yes
Signal: DC OK active
Output description UOUT > 0.9 x UN: High signal
Maximum switching voltage ≤ 24 V
Output voltage + 24 V DC (Signal)
Maximum inrush current ≤ 40 mA
Continuous load current ≤ 40 mA
Signal: DC OK floating
Output description Relay contact, UOUT > 0.9 x UN: Contact closed
Maximum switching voltage ≤ 30 V AC/DC
Maximum inrush current ≤ 1 A
Continuous load current ≤ 1 A
Signal: DC OK active
Output description UOUT > 0.9 x UN: High signal
Maximum switching voltage ≤ 24 V
Output voltage + 24 V DC (Signal)
Maximum inrush current ≤ 40 mA
Continuous load current ≤ 40 mA
Signal: DC OK floating
Output description Relay contact, UOUT > 0.9 x UN: Contact closed
Maximum switching voltage ≤ 30 V AC/DC
Maximum inrush current ≤ 1 A
Continuous load current ≤ 1 A

[/fusion_table]

General

[fusion_table fusion_table_type=”1″ fusion_table_rows=”” fusion_table_columns=”” margin_top=”1ps” margin_right=”” margin_bottom=”” margin_left=”” hide_on_mobile=”small-visibility,medium-visibility,large-visibility” class=”” id=”” animation_type=”” animation_direction=”left” animation_color=”” hue=”” saturation=”” lightness=”” alpha=”” animation_speed=”0.3″ animation_delay=”0″ animation_offset=””]

Item number 2938620
Packing unit 1 pc
Minimum order quantity 1 pc
Sales Key CMP
Product Key CMPP13
Catalog Page Page 481 (IF-2007)
GTIN 4017918890544
Weight per Piece (including packing) 3,061 g
Weight per Piece (excluding packing) 2,500 g
Customs tariff number 85044030
Country of origin TH

[/fusion_table]

Weight 3.061 kg
Dimensions 12.5 × 15.7 × 13.0 cm