Axmatic – Your Trusted Phoenix Contact Distributor
Axmatic proudly stands as one of the largest distributors of Phoenix Contact products, offering a comprehensive range of terminal blocks, interface modules, power supplies, and relays.
Series Models: PT Series, ST Series, TB Series, UT Series, and UK Series, PTV Series, UKH Series, Micro Series.
Discover industry-leading Phoenix Contact power supplies, such as:
Get Your Phoenix Contact Catalog Today
Need detailed product information? Contact us at sales@axmatic.com to request your Phoenix Contact catalog.
QUINT DC/DC converter with maximum functionality
DC/DC converters alter the voltage level, regenerate the voltage at the end of long cables or enable the creation of independent supply systems by means of electrical isolation.
QUINT DC/DC converters magnetically and therefore quickly trip circuit breakers with six times the nominal current, for selective and therefore cost-effective system protection. The high level of system availability is additionally ensured, thanks to preventive function monitoring, as it reports critical operating states before errors occur.
| Item dimensions | |
| Width | 50 mm | 
| Height | 130 mm | 
| Depth | 125 mm | 
| Item dimensions with alternative mounting | |
| Width | 122 mm | 
| Height | 130 mm | 
| Depth | 53 mm | 
| Installation dimensions | |
| Installation distance right/left (active) | 15 mm / 15 mm (≤ 70 °C) | 
| Installation distance right/left (passive) | 0 mm / 0 mm (≤ 70 °C) | 
| Installation distance top/bottom (active) | 50 mm / 50 mm (≤ 70 °C) | 
| Installation distance top/bottom (passive) | 50 mm / 50 mm (≤ 70 °C) | 
| Degree of protection | IP20 | 
| Ambient temperature (operation) | -40 °C … 70 °C (> 60 °C Derating: 2,5 %/K) | 
| Ambient temperature (storage/transport) | -40 °C … 85 °C | 
| Maximum altitude | ≤ 5000 m (> 2000 m, observe derating) | 
| Climatic class | 3K3 (EN 60721) | 
| Max. permissible relative humidity (operation) | ≤ 100 % (at 25 °C, non-condensing) | 
| Shock | 18 ms, 30g, in each space direction (according to IEC 60068-2-27) | 
| Vibration (operation) | 5 Hz … 100 Hz resonance search 2.3g, 90 min., resonance frequency 2.3g, 90 min. (according to DNV GL Class C) | 
| Temp code | T4 (-40 … +70 °C; > 60 °C, Derating: 2,5 %/K) | 
| Nominal input voltage range | 24 V DC | 
| Input voltage range | 24 V DC -25 % … +40 % | 
| Wide-range input | no | 
| Electric strength, max. | 35 V DC (60 s) | 
| Inrush current | typ. 1.5 A | 
| Inrush current integral (I2t) | < 0.02 A2s | 
| Inrush current limitation | 1.5 A (after 1 ms) | 
| Mains buffering time | typ. 11 ms (24 V DC) | 
| Current consumption | 13.8 A (24 V DC) | 
| Typical response time | 300 ms (from SLEEP MODE) | 
| Switch-on time | < 1 s | 
| Input fuse | 30 A (slow-blow, internal) | 
| Recommended breaker for input protection | 16 A … 32 A (Characteristic B, C, D, K or comparable) | 
| Efficiency | typ. 93.3 % (24 V DC) | 
| Output characteristic | U/I Advanced | 
| Smart HICCUP | |
| FUSE MODE | |
| Nominal output voltage | 24 V DC | 
| Setting range of the output voltage (USet) | 24 V DC … 28 V DC (> 24 V DC, constant capacity) | 
| Nominal output current (IN) | 10 A | 
| Static Boost (IStat.Boost) | 12.5 A | 
| Dynamic Boost (IDyn.Boost) | 20 A (5 s) | 
| Selective Fuse Breaking (ISFB) | 60 A (15 ms) | 
| Magnetic circuit breaker tripping | A1…A6 / B2…B6 / C1…C3 / Z1…Z6 | 
| Short-circuit-proof | yes | 
| No-load proof | yes | 
| Output power (PN) | 240 W | 
| Output power (PStat. Boost) | 300 W | 
| Output power (PDyn. Boost) | 480 W (5 s) | 
| Feedback voltage resistance | ≤ 35 V DC | 
| Protection against overvoltage at the output (OVP) | ≤ 30 V DC | 
| Residual ripple | < 50 mVPP | 
| Control deviation static | < 1 % (change in load, static 10 % … 90 %) | 
| Control deviation dynamic | < 1 % (change in load, static 10 % … 90 %) | 
| Control deviation Input voltage change | < 1 % (change in load, static 10 % … 90 %) | 
| Rise time | < 1 s (UOUT (10 % … 90 %)) | 
| Connection in series | yes | 
| Maximum no-load power dissipation | < 5 W | 
| Power loss nominal load max. | < 16 W | 
| Power dissipation SLEEP MODE | < 2 W | 
| Connection in parallel | yes, for redundancy and increased capacity | 
| Item number | 2910133 | 
| Packing unit | 1 pc | 
| Minimum order quantity | 1 pc | 
| Sales key | CMD | 
| Product key | CMDI43 | 
| GTIN | 4055626537429 | 
| Weight per piece (including packing) | 1,043 g | 
| Weight per piece (excluding packing) | 910 g | 
| Customs tariff number | 85044095 | 
| Country of origin | TH | 
| Input | |
| Position | 1.x | 
| Conductor connection | |
| Connection method | Push-in connection | 
| rigid | 0.2 mm² … 6 mm² | 
| flexible | 0.2 mm² … 6 mm² | 
| flexible with ferrule without plastic sleeve | 0.2 mm² … 4 mm² | 
| flexible with ferrule with plastic sleeve | 0.2 mm² … 4 mm² | 
| rigid (AWG) | 24 … 10 | 
| Stripping length | 10 mm | 
| Output | |
| Position | 2.x | 
| Conductor connection | |
| Connection method | Push-in connection | 
| rigid | 0.2 mm² … 6 mm² | 
| flexible | 0.2 mm² … 6 mm² | 
| flexible with ferrule without plastic sleeve | 0.2 mm² … 4 mm² | 
| flexible with ferrule with plastic sleeve | 0.2 mm² … 4 mm² | 
| rigid (AWG) | 24 … 10 | 
| Stripping length | 10 mm | 
| Signal | |
| Position | 3.x | 
| Conductor connection | |
| Connection method | Push-in connection | 
| rigid | 0.2 mm² … 1 mm² | 
| flexible | 0.2 mm² … 1.5 mm² | 
| flexible with ferrule without plastic sleeve | 0.2 mm² … 1.5 mm² | 
| flexible with ferrule with plastic sleeve | 0.2 mm² … 0.75 mm² | 
| rigid (AWG) | 24 … 16 | 
| Stripping length | 8 mm | 
| LED signaling | |
| Types of signaling | LED | 
| Floating signal contact | |
| Active signal output Out1 (digital, configurable) | |
| Active signal output Out2 (analog, configurable) | |
| Remote contact | |
| Signal ground SGnd | |
| Signal threshold | > 100 % (LED lights up yellow, output power > 240 W) | 
| > 75 % (LED lights up green, output power > 180 W) | |
| > 50 % (LED lights up green, output power > 120 W) | |
| > 0.9 x USet (LED lights up green) | |
| < 0.9 x USet (LED flashes green) | |
| > 0.8 x UInNom (LED off) | |
| < 0.8 x UInNom (LED lights up yellow) | |
| Signal input Remote (configurable) | |
| Connection labeling | 3.3 + | 
| Function | Output power ON/OFF (remote) | 
| Default | Output power ON (>40 kΩ/24 V DC/open bridge between REM and SGnd) | 
| Signal output Out 1 (configurable) | |
| Connection labeling | 3.5 + | 
| Digital | 0 V DC | 
| 24 V DC | |
| 20 mA | |
| Default | UIN input voltage OK | 
| Signal option | Output voltage | 
| Output current | |
| Output power | |
| Operating hours | |
| Early warning of high temperatures | |
| OVP voltage limitation active | |
| Signal output Out 2 (configurable) | |
| Connection labeling | 3.6 + | 
| Digital | 0 V DC | 
| 24 V DC | |
| 20 mA | |
| Default | Output power | 
| Signal option | Output voltage | 
| Output current | |
| Operating hours | |
| Early warning of high temperatures | |
| OVP voltage limitation active | |
| Analog | 4 mA … 20 mA ±5 % (Load ≤400 Ω) | 
| Signal option | Output voltage | 
| Output current | |
| Output power | |
| Signal output Relay 13/14 (configurable) | |
| Connection labeling | 3.1, 3.2 | 
| Switch contact (floating) | floating | 
| Digital | 24 V DC | 
| 1 A | |
| 30 V AC | |
| 0.5 A | |
| Default | Output voltage | 
| Signal option | Output current | 
| Output power | |
| Operating hours | |
| Early warning of high temperatures | |
| OVP voltage limitation active | |
| UIN input voltage OK | |
| Signal ground SGnd | |
| Connection labeling | 3.4 + | 
| Function | Signal ground | 
| Reference potential | to OUT1, OUT2, REM | 
| Number of phases | 1.00 | 
| Insulation voltage input/output | 4 kV DC (type test) | 
| 2 kV DC (routine test) | |
| Switching frequency | 190.00 kHz … 220.00 kHz (Auxiliary converter stage) | 
| 67.00 kHz … 135.00 kHz (Main converter stage) | 
| Product type | DC/DC converters | 
| Product family | QUINT POWER | 
| MTBF (IEC 61709, SN 29500) | > 1380000 h (25 °C) | 
| > 800000 h (40 °C) | |
| > 340000 h (60 °C) | |
| Insulation characteristics | |
| Protection class | Special with SELV input and output | 
| Degree of pollution | 2 | 
| Life expectancy (electrolytic capacitors) | |
| Current | 5 A | 
| Temperature | 40 °C | 
| Time | 367721 h | 
| Additional text | 24 V DC | 
| Life expectancy (electrolytic capacitors) | |
| Current | 10 A | 
| Temperature | 40 °C | 
| Time | 183860 h | 
| Additional text | 24 V DC | 
| Life expectancy (electrolytic capacitors) | |
| Current | 10 A | 
| Temperature | 30 °C | 
| Time | 422400 h | 
| Additional text | 24 V DC | 
| Mounting type | DIN rail mounting | 
| Assembly note | alignable: PN ≥50%, 5 mm horizontally, 15 mm next to active components, 50 mm vertically alignable: PN <50%, 0 mm horizontally, 40 mm vertically top, 20 mm vertically bottom | 
| With protective coating | yes | 
| Flammability rating according to UL 94 (housing / terminal blocks) | V0 | 
| Housing material | Metal | 
| Hood version | Stainless steel X6Cr17 | 
| Side element version | Aluminum | 
| Overvoltage category | |
| EN 61010-1 | II | 
| EN 62477-1 | III | 
| Fire protection in rail vehicles | |
| Standard designation | Fire protection in rail vehicles | 
| Standards/specifications | EN 45545-2 (HL3) | 
| Safety for measurement, control, and laboratory equipment | |
| Standard designation | Electrical safety (of control and regulation devices) | 
| Standards/specifications | IEC 61010-1 | 
| Protective extra-low voltage | |
| Standard designation | Protective extra-low voltage | 
| Standards/specifications | EN 61010-1 (SELV) | 
| IEC 61010-2-201 (PELV) | |
| Explosive atmospheres | |
| Standard designation | Explosive atmospheres | 
| Standards/specifications | IEC 60079-0 | 
| IEC 60079-7 | |
| IEC 60079-11 | |
| IEC 60079-15 | |
| Mains voltage dips | |
| Standard designation | Mains variation/undervoltage | 
| Standards/specifications | EN 61000-4-29 | 
| UL | |
| Identification | UL Listed UL 61010-1 | 
|  II 3 G Ex ec ic nC IIC T4 Gc | |
| UL | |
| Identification | UL Listed UL 61010-2-201 | 
| Ex ec ic nC IIC T4 Gc | |
| UL | |
| Identification | UL 121201 & CSA C22.2 No. 213-17 Class I, Division 2, Groups A, B, C, D T4 (Hazardous Location) | 
| CSA | |
| Identification | CAN/CSA-C22.2 No. 61010-1-12 | 
| CSA | |
| Identification | CAN/CSA-IEC 61010-2-201:14 | 
| SIQ | |
| Identification | Type tested (type approved) | 
| SIQ | |
| Identification | CB scheme (IEC 61010-1, IEC 61010-2-201) | 
| Shipbuilding | |
| Identification | DNV GL | 
| Shipbuilding | |
| Identification | ABS | 
| ATEX | |
| Identification | SIQ 21 ATEX 025 X | 
|  II 3 G Ex ec ic nC IIC T4 Gc | |
| IECEx | |
| Identification | IECEx SIQ 19.0001X | 
| Ex ec ic nC IIC T4 Gc | |
| Electromagnetic compatibility | Conformance with EMC Directive 2014/30/EU | 
| Low Voltage Directive | Conformance with Low Voltage Directive 2014/35/EC | 
| EMC requirements for noise emission | EN 61000-6-3 | 
| EN 61000-6-4 | |
| EMC requirements for noise immunity | EN 61000-6-1 | 
| EN 61000-6-2 | |
| EMC requirements, power plant | IEC 61850-3 | 
| EN 61000-6-5 | |
| Conducted noise emission | |
| Standards/regulations | EN 55016 | 
| EN 61000-6-3 (Class B) | |
| Noise emission | |
| Standards/regulations | Additional basic standard EN 61000-6-5 (immunity in power station), IEC/EN 61850-3 (energy supply) | 
| Noise emission | |
| Standards/regulations | EN 55016 | 
| EN 61000-6-3 (Class B) | |
| DNV GL conducted noise emissions | |
| DNV | Class B | 
| Additional text | Bridge and deck area | 
| DNV GL noise radiation | |
| DNV | Class B | 
| Additional text | Bridge and deck area | 
| Electrostatic discharge | |
| Standards/regulations | EN 61000-4-2 | 
| Electrostatic discharge | |
| Contact discharge | 8 kV (Test Level 4) | 
| Discharge in air | 15 kV (Test Level 4) | 
| Comments | Criterion A | 
| Electromagnetic HF field | |
| Standards/regulations | EN 61000-4-3 | 
| Electromagnetic HF field | |
| Frequency range | 80 MHz … 1 GHz | 
| Test field strength | 20 V/m (Test Level 3) | 
| Frequency range | 1 GHz … 6 GHz | 
| Test field strength | 10 V/m (Test Level 3) | 
| Frequency range | 1 GHz … 6 GHz | 
| Test field strength | 10 V/m (Test Level 3) | 
| Comments | Criterion A | 
| Fast transients (burst) | |
| Standards/regulations | EN 61000-4-4 | 
| Fast transients (burst) | |
| Input | 4 kV (Test Level 3 – asymmetrical) | 
| Output | 4 kV (Test Level 3 – asymmetrical) | 
| Signal | 4 kV (Test Level 4 – asymmetrical) | 
| Comments | Criterion A | 
| Surge voltage load (surge) | |
| Standards/regulations | EN 61000-4-5 | 
| Surge voltage load (surge) | |
| Input | 1 kV (Test Level 3 – symmetrical) | 
| 2 kV (Test Level 3 – asymmetrical) | |
| Output | 1 kV (Test Level 3 – symmetrical) | 
| 2 kV (Test Level 3 – asymmetrical) | |
| Signal | 2 kV (Test Level 3 – asymmetrical) | 
| Comments | Criterion A | 
| Conducted interference | |
| Standards/regulations | EN 61000-4-6 | 
| Conducted interference | |
| Input/output/signal | asymmetrical | 
| Frequency range | 0.15 MHz … 80 MHz | 
| Comments | Criterion A | 
| Voltage | 10 V (Test Level 3) | 
| Power frequency magnetic field | |
| Standards/regulations | EN 61000-4-8 | 
| Frequency | 16.7 Hz | 
| 50 Hz | |
| 60 Hz | |
| Test field strength | 100 A/m | 
| Additional text | 60 s | 
| Comments | Criterion A | 
| Frequency | 50 Hz | 
| 60 Hz | |
| Frequency range | 50 Hz … 60 Hz | 
| Test field strength | 1 kA/m | 
| Additional text | 3 s | 
| Comments | Criterion A | 
| Frequency | 0 Hz | 
| Test field strength | 300 A/m | 
| Additional text | DC, 60 s | 
| Comments | Criterion A | 
| Voltage dips | |
| Standards/regulations | EN 61000-4-29 | 
| Voltage | 24 V DC | 
| Voltage dip | 70 % | 
| Time | 100 ms | 
| Additional text | Test Level 2 | 
| Comments | Criterion A | 
| Voltage dip | 40 % | 
| Time | 100 ms | 
| Additional text | Test Level 2 | 
| Comments | Criterion B | 
| Voltage dip | 0 % | 
| Time | 50 ms | 
| Additional text | Test Level 2 | 
| Comments | Criterion B | 
| Pulse-shape magnetic field | |
| Standards/regulations | EN 61000-4-9 | 
| Test field strength | 1000 A/m | 
| Comments | Criterion A | 
| Asymmetrical conducted disturbance variables | |
| Standards/regulations | EN 61000-4-16 | 
| Test level 1 | 15 Hz 150 Hz (Test Level 4) | 
| Voltage | 30 V 3 V | 
| Test level 2 | 150 Hz 1.5 kHz (Test Level 4) | 
| Voltage | 3 V | 
| Test level 3 | 1.5 kHz 15 kHz (Test Level 4) | 
| Voltage | 0 V 3 V | 
| Test level 4 | 15 kHz 150 kHz (Test Level 4) | 
| Voltage | 30 V | 
| Test level 5 | 16.7 Hz 50 Hz 60 Hz 150 Hz 180 Hz (Test Level 4) | 
| Voltage | 30 V (Permanent) | 
| Test level 6 | 0 Hz 16.7 Hz 50 Hz 60 Hz (Test Level 4) | 
| Voltage | 300 V (1 s) | 
| Comments | Criterion A | 
| Alternating component of direct voltage | |
| Standards/regulations | EN 61000-4-17 | 
| Alternating component | 10 % (UN) | 
| Frequency | 50 Hz | 
| 100 Hz | |
| 150 Hz | |
| 300 Hz | |
| Comments | Criterion A | 
| Attenuated oscillating wave | |
| Standards/regulations | EN 61000-4-18 | 
| Input, output (test level 1) | 100 kHz 1 MHz (Test Level 3 – symmetrical) | 
| Voltage | 1 kV | 
| Input, output (test level 2) | 100 kHz 1 MHz (Test Level 3 – asymmetrical) | 
| Voltage | 2.5 kV | 
| Input, output (test level 3) | 10 MHz (Test Level 3 – asymmetrical) | 
| Voltage | 2 kV | 
| Signals (test level 1) | 100 kHz 1 MHz (Test Level 2 – symmetrical) | 
| Voltage | 1 kV | 
| Signals (test level 2) | 100 kHz 1 MHz (Test Level 3 – asymmetrical) | 
| Voltage | 2.5 kV | 
| Comments | Criterion A | 
| Attenuated oscillating magnetic field | |
| Standards/regulations | EN 61000-4-10 | 
| Test field strength | 100 A/m | 
| Test level 1 | 100 kHz | 
| Test field strength | 100 A/m | 
| Test level 2 | 1 MHz | 
| Comments | Criterion A | 
| Criteria | |
| Criterion A | Normal operating behavior within the specified limits. | 
| Criterion B | Temporary impairment to operational behavior that is corrected by the device itself. | 
| Criterion C | Temporary adverse effects on the operating behavior, which the device corrects automatically or which can be restored by actuating the operating elements. | 
| Weight | 1.043 kg | 
|---|---|
| Dimensions | 12.5 × 5 × 13 cm |