Contact Us:
sales@inosaki.com

TTC-6P-1X2-M-24DC-UT-I – 2906738 – Surge Protection Device – Phoenix Contact Surge Protection

$ 138.00

SKU Phoenix Contact 2906738 Category

Phoenix Contact develops terminal blocks, power supplies, relays, connectors, signal conditioners, controllers & PLCs, I/O systems, Industrial Ethernet, controller system cabling, PCB terminal blocks & connectors, and surge suppression.

Commercial Data

Item number 2906738
Packing unit 1 pc
Minimum order quantity 1 pc
Product key CL2161
Catalog page Page 116 (C-4-2019)
GTIN 4055626134703
Weight per piece (including packing) 57 g
Weight per piece (excluding packing) 54.8 g
Customs tariff number 85363010
Country of origin DE

Product Properties

Product type Surge protection for MCR technology
Product family TERMITRAB complete
IEC test classification C1
C2
C3
D1
Type DIN rail module, two-section, divisible
Wire pairs per module 1
Insulation characteristics
Overvoltage category III
Pollution degree 2

Electrical Properties

Nominal voltage UN 24 V DC

Ex Data

Maximum input current 600 mA (T4 / ≤ 30 °C)
500 mA (T4 / > 30 °C … ≤ 50 °C)
400 mA (T4 / > 50 °C … ≤ 70 °C)
Maximum input voltage 30 V DC
Altitude ≤ 2000 m (amsl)
Ambient temperature (operation) -40 °C … 70 °C (T4)

Connection Data

Connection method Screw connection
Screw thread M3
Tightening torque 0.5 Nm … 0.6 Nm
Conductor cross section flexible 0.2 mm² … 2.5 mm²
Conductor cross section rigid 0.2 mm² … 4 mm²
Conductor cross section AWG 24 … 12

Dimension

Width 6.2 mm +0.1 mm
Height 105.8 mm
Depth 100 mm (incl. DIN rail 7.5 mm)

Material Specifications

Color (Base element) gray (RAL 7042)
Color (Male connector) light gray (RAL 7035)
Flammability rating according to UL 94 V-0
Insulating material PBT
Housing material PBT

Mechanical Properties

Mechanical data
Open side panel No

Protective Circuit

Direction of action Line-Line & Line-Signal Ground/Shield & optional Signal Ground/Shield-Earth Ground
Maximum continuous voltage UC 30 V DC
21 V AC
Rated current 600 mA (56 °C)
Operating effective current IC at UC ≤ 5 µA
Residual current IPE ≤ 1 µA
Nominal discharge current In (8/20) µs (line-line) 5 kA
Nominal discharge current In (8/20) µs (line-ground) 5 kA
Pulse discharge current Iimp (10/350) µs (line-line) 0.5 kA
Pulse discharge current Iimp (10/350) µs (line-earth) 0.5 kA
Total discharge current Itotal (8/20) µs 10 kA
Voltage protection level Up (line-line) ≤ 200 V (C1 – 1 kV / 500 A)
≤ 320 V (C2 – 10 kV / 5 kA)
≤ 50 V (C3 – 25 A)
≤ 55 V (C3 – 100 A)
Voltage protection level Up (line-earth) ≤ 750 V (C1 – 1 kV / 500 A)
≤ 750 V (C2 – 10 kV / 5 kA)
≤ 700 V (C3 – 25 A)
≤ 750 V (C3 – 100 A)
Voltage protection level Up static (line-line) ≤ 50 V (C1 – 1 kV / 500 A)
≤ 120 V (C2 – 10 kV / 5 kA)
Voltage protection level Up static (line-earth) ≤ 750 V (C1 – 1 kV / 500 A)
≤ 750 V (C2 – 10 kV / 5 kA)
Response time tA (line-line) ≤ 1 ns
Response time tA (line-earth) ≤ 100 ns
Input attenuation aE, sym. typ. 0.3 dB (≤ 250 kHz / 150 Ω)
Cut-off frequency fg (3 dB), sym. in 150 Ω system typ. 940 kHz
Capacity (Core-Core) typ. 2.2 nF
Resistance per path 1.65 Ω ±20 %
Surge protection fault message optical
Max. required back-up fuse 630 mA (FF)
Impulse durability (line-line) C1 – 1 kV / 500 A
C2 – 10 kV / 5 kA
C3 – 100 A
Impulse durability (line-earth) C1 – 1 kV / 500 A
C2 – 10 kV / 5 kA
C3 – 100 A
D1 – 500 A
Pulse reset time (line-line) ≤ 700 ms
Pulse reset time (line-earth) ≤ 1500 ms
Additional technical data
Max. total discharge current I total max (8/20) µs 20 kA (1x – non Ex)

Environmental and real-life conditions 

Ambient conditions
Degree of protection IP20
Ambient temperature (operation) -40 °C … 85 °C
Ambient temperature (storage/transport) -40 °C … 85 °C
Altitude ≤ 6000 m (amsl)
Permissible humidity (operation) 5 % … 95 %

Approvals

Conformity/Approvals
UL, USA / Canada Class I, Div. 2, Groups A, B, C, D T4A

Standards And Regulations

Standards/specifications IEC 61643-21
Note 2000 + corrigendum 2001 + A1:2008, modified + A2:2012
EN 61643-21
Standards/specifications EN 61643-21
Note 2001 + A1:2009 + A2:2013
Standards/specifications IEC 60079-0
Note 2017
Standards/specifications IEC 60079-7
Note 2017
Standards/specifications EN IEC 60079-0
Note 2018
Standards/specifications EN IEC 60079-7
Note 2015 + A1:2018

Mounting

Mounting type DIN rail: TH 35 – 7.5 mm

Additional information