Ground modular terminal block, connection method: Screw connection, number of connections: 2, cross section: 0.2 mm² – 10 mm², AWG: 24 – 8, width: 8.2 mm, height: 46.9 mm, color: green-yellow, mounting type: NS 35/7,5, NS 35/15
| Article Number | 3044157 | 
|---|---|
| Number of levels | 1 | 
| Number of connections | 2 | 
| Nominal cross section | 6 mm² | 
| Color | green-yellow | 
| Insulating material | PA | 
| Flammability rating according to UL 94 | V0 | 
| Area of application | Railway industry | 
| Machine building | |
| Plant engineering | |
| Process industry | |
| Mounting type | NS 35/7,5 | 
| Rated surge voltage | 8 kV | 
| Degree of pollution | 3 | 
| Overvoltage category | III | 
| Insulating material group | I | 
| Open side panel | Yes | 
| Shock protection test specification | DIN EN 50274 (VDE 0660-514):2002-11 | 
| Back of the hand protection | Not guaranteed | 
| Finger protection | Not guaranteed | 
| Test specification, oscillation, broadband noise | DIN EN 50155 (VDE 0115-200):2018-05 | 
| Test spectrum | Service life test category 2, bogie-mounted | 
| Test frequency | f1 = 5 Hz to f2 = 250 Hz | 
| ASD level | 6.12 (m/s²)²/Hz | 
| Acceleration | 3.12g | 
| Test duration per axis | 5 h | 
| Test directions | X-, Y- and Z-axis | 
| Shock form | Half-sine | 
| Acceleration | 30g | 
| Shock duration | 18 ms | 
| Number of shocks per direction | 3 | 
| Test directions | X-, Y- and Z-axis (pos. and neg.) | 
| Relative insulation material temperature index (Elec., UL 746 B) | 130 °C | 
| Temperature index of insulation material (DIN EN 60216-1 (VDE 0304-21)) | 125 °C | 
| Static insulating material application in cold | -60 °C | 
| Surface flammability NFPA 130 (ASTM E 162) | passed | 
| Specific optical density of smoke NFPA 130 (ASTM E 662) | passed | 
| Calorimetric heat release NFPA 130 (ASTM E 1354) | 27,5 MJ/kg | 
| Smoke gas toxicity NFPA 130 (SMP 800C) | passed | 
| Fire protection for rail vehicles (DIN EN 45545-2) R22 | HL 1 – HL 3 | 
| Fire protection for rail vehicles (DIN EN 45545-2) R23 | HL 1 – HL 3 | 
| Fire protection for rail vehicles (DIN EN 45545-2) R24 | HL 1 – HL 3 | 
| Fire protection for rail vehicles (DIN EN 45545-2) R26 | HL 1 – HL 3 | 
| Width | 8.2 mm | 
|---|---|
| End cover width | 2.2 mm | 
| Length | 47.7 mm | 
| Height | 46.9 mm | 
| Height NS 35/7,5 | 47.5 mm | 
| Height NS 35/15 | 55 mm | 
| Note | Please observe the current carrying capacity of the DIN rails. | 
|---|---|
| Connection method | Screw connection | 
| Screw thread | M4 | 
| Stripping length | 10 mm | 
| Tightening torque, min | 1.5 Nm | 
| Tightening torque max | 1.8 Nm | 
| Connection in acc. with standard | IEC 60947-7-2 | 
| Note | Note: Product releases, connection cross sections and notes on connecting aluminum cables can be found in the download area. | 
| Conductor cross section solid min. | 0.2 mm² | 
| Conductor cross section solid max. | 10 mm² | 
| Conductor cross section AWG min. | 24 | 
| Conductor cross section AWG max. | 8 | 
| Conductor cross section flexible min. | 0.2 mm² | 
| Conductor cross section flexible max. | 10 mm² | 
| Min. AWG conductor cross section, flexible | 24 | 
| Max. AWG conductor cross section, flexible | 8 | 
| Conductor cross section flexible, with ferrule without plastic sleeve min. | 0.25 mm² | 
| Conductor cross section flexible, with ferrule without plastic sleeve max. | 6 mm² | 
| Conductor cross section flexible, with ferrule with plastic sleeve min. | 0.25 mm² | 
| Conductor cross section flexible, with ferrule with plastic sleeve max. | 6 mm² | 
| 2 conductors with same cross section, solid min. | 0.2 mm² | 
| 2 conductors with same cross section, solid max. | 2.5 mm² | 
| 2 conductors with same cross section, stranded min. | 0.2 mm² | 
| 2 conductors with same cross section, stranded max. | 2.5 mm² | 
| Two conductors with the same cross section, flexible, with TWIN ferrules, with plastic sleeve, minimum | 0.5 mm² | 
| Two conductors with the same cross section, flexible, with TWIN ferrules, with plastic sleeve, maximum | 4 mm² | 
| Two conductors with the same cross section stranded, with ferrule and without plastic sleeve, minimum | 0.25 mm² | 
| Two conductors with the same cross section stranded, with ferrule and without plastic sleeve, maximum | 1.5 mm² | 
| Internal cylindrical gage | A5 | 
| Operating temperature | -60 °C … 105 °C (max. short-term operating temperature 130°C) | 
|---|---|
| Ambient temperature (storage/transport) | -25 °C … 60 °C (for a short time, not exceeding 24 h, -60 °C to +70 °C) | 
| Permissible humidity (storage/transport) | 30 % … 70 % | 
| Ambient temperature (assembly) | -5 °C … 70 °C | 
| Ambient temperature (actuation) | -5 °C … 70 °C | 
| Connection in acc. with standard | CSA | 
|---|---|
| IEC 60947-7-2 | |
| Flammability rating according to UL 94 | V0 | 
| China RoHS | Environmentally Friendly Use Period = 50 years | 
|---|---|
| For details about hazardous substances go to tab “Downloads”, Category “Manufacturer’s declaration” |