Item | Specifications | ||
---|---|---|---|
Model | CJ1W-PA205R | CJ1W-PA205C | CJ1W-PA202 |
Supply voltage | 100 to 240 V AC (wide-range), 50/60 Hz | ||
Operating voltage and frequency ranges |
85 to 264 V AC, 47 to 63 Hz | ||
Power consumption | 100 VA max. | 50 VA max. | |
Inrush current *1 | At 100 to 120 V AC: 15 A/8 ms max. for cold start at room temperature At 200 to 240 V AC: 30 A/8 ms max. for cold start at room temperature |
At 100 to 120 V AC: 20 A/8 ms max. for cold start at room temperature At 200 to 240 V AC: 40 A/8 ms max. for cold start at room temperature |
|
Output capacity *7 | 5.0 A, 5 V DC (including supply to CPU Unit) | 2.8 A, 5 V DC (including supply to CPU Unit) |
|
0.8 A, 24 V DC | 0.4 A, 24 V DC | ||
Total: 25 W max. | Total: 14 W max. | ||
Output terminal (service supply) |
Not provided. | ||
RUN output *2 | Contact configuration: SPST-NO Switch capacity: 250 V AC, 2 A (resistive load) 120 V AC, 0.5 A (inductive load), 24 V DC, 2A (resistive load) 24 V DC, 2 A (inductive load) |
Not provided. | |
Replacement notification function |
Not provided. | With Alarm output (open- collector output) 30 V DC max., 50 mA max. |
Not provided. |
Insulation resistance | 20 MΩ min. (at 500 V DC) between AC external and GR terminals *3 |
20 MΩ min. (at 500 V DC) between all external terminals and GR terminal *3, and between all alarm output terminals. 20 MΩ 1 min. (at 250 V DC) between all alarm output terminals and GR terminal *3. |
20 MΩ min. (at 500 V DC) between AC external and GR terminals *3 |
Dielectric strength *4 | 2,300 V AC 50/60 Hz for 1 min between AC external and GR terminals *3 Leakage current: 10 mA max. |
2,300 VAC, 50/60 Hz for 1 min between all external terminals and GR terminal *3 and between all alarm output terminals with a leakage current of 10 mA max. 1,000 V AC, 50/60 Hz for 1 min between all alarm output terminals and GR terminal *3 with a leakage current of 10 mA max. |
2,300 V AC 50/60 Hz for 1 min between AC external and GR terminals *3 Leakage current: 10 mA max. |
1,000 V AC, 50/60 Hz for 1 minute between DC external and GR terminals *3 Leakage current: 10 mA max. |
|||
Noise immunity | 2 kV on power supply line (conforming to IEC61000-4-4) | ||
Vibration resistance | Conforms to IEC60068-2-6 5 to 8.4 Hz with 3.5-mm amplitude, 8.4 to 150 Hz Acceleration of 9.8 m/s2 for 100 min in X, Y, and Z directions (10 sweeps of 10 min each = 100 min) |
||
Shock resistance | Conforms to IEC60068-2-27 147 m/s2, 3 times in X, Y, and Z directions (100 m/s2 for Relay Output Units) |
||
Ambient operating temperature |
0 to 55 °C | ||
Ambient operating humidity |
10% to 90% (with no condensation) |
10% to 90% (with no condensation) *5 |
10% to 90% (with no condensation) |
Atmosphere | Must be free from corrosive gases. | ||
Ambient storage temperature |
– 20 to 70 °C (excluding battery) |
– 20 to 75 °C *5 | – 20 to 75 °C (excluding battery) |
Grounding | Less than 100 Ω | ||
Enclosure | Mounted in a panel. | ||
Weight | 350 g max. | 400 g max. | 200 g max. |
CPU Rack dimensions |
90.7 to 466.7 × 90 × 65 mm (W × H × D) (not including cables) Note: W = a + b + 20 × n + 31 × m + 14.7 a: Power Supply Unit: PA205R and PA205C = 80; PA202 = 45; PD025 = 60; PD022=27 b: CPU Unit: CJ1-H or CJ1 = 62; CJ1M-CPU1[] = 31 *8; CJ1M-CPU2[] = 49 *8 The total width is given by the following: W = 156.7 + n × 20 + m × 31, where n is the number of 32-point I/O Units or I/O Control Units and m is the number of other Units. |
||
Safety measures | Conforms to cULus and EC Directives. |
[/fusion_table]
Item | Specifications | |
---|---|---|
Model | CJ1W-PD025 | CJ1W-PD022 |
Supply voltage | 24 VDC | |
Operating voltage and frequency ranges |
19.2 to 28.8 V DC | 21.6 to 26.4 V DC |
Power consumption | 50 W max. | 35 W max. |
Inrush current *1 | At 24 V DC: 30 A/20 ms max. for cold start | |
Output capacity *7 | 5.0 A, 5 V DC (including supply to CPU Unit) | 2.0 A, 5 V DC (including supply to CPU Unit) |
0.8 A, 24 V DC | 0.4 A, 24 V DC | |
Total: 25 W max. | Total: 19.6 W max. | |
Output terminal (service supply) |
Not provided. | |
RUN output *2 | Not provided. | |
Replacement notification function |
Not provided. | |
Insulation resistance | 20 MΩ min. (at 500 V DC) between DC external and GR terminals *3 |
— *6 |
Dielectric strength *4 | 1,000 V AC, 50/60 Hz for 1 min between DC external and GR terminals *3 Leakage current: 10 mA max. |
— *6 |
Noise immunity | 2 kV on power supply line (conforming to IEC61000-4-4) | |
Vibration resistance | Conforms to IEC60068-2-6 5 to 8.4 Hz with 3.5-mm amplitude, 8.4 to 150 Hz Acceleration of 9.8 m/s2 for 100 min in X, Y, and Z directions (10 sweeps of 10 min each = 100 min) |
|
Shock resistance | Conforms to IEC60068-2-27 147 m/s2, 3 times in X, Y, and Z directions (100 m/s2 for Relay Output Units) |
|
Ambient operating temperature |
0 to 55 °C | |
Ambient operating humidity |
10% to 90% (with no condensation) | |
Atmosphere | Must be free from corrosive gases. | |
Ambient storage temperature |
– 20 to 75 °C (excluding battery) | |
Grounding | Less than 100 Ω | |
Enclosure | Mounted in a panel. | |
Weight | 335 g max. | 130 g max. |
CPU Rack dimensions |
90.7 to 466.7 × 90 × 65 mm (W × H × D) (not including cables) Note: W = a + b + 20 × n + 31 × m + 14.7 a: Power Supply Unit: PA205R and PA205C = 80; PA202 = 45; PD025 = 60; PD022=27 b: CPU Unit: CJ1-H or CJ1 = 62; CJ1M-CPU1[] = 31 *8; CJ1M-CPU2[] = 49 *8 The total width is given by the following: W = 156.7 + n × 20 + m × 31, where n is the number of 32-point I/O Units or I/O Control Units and m is the number of other Units. |
|
Safety measures | Conforms to cULus and EC Directives. |
[/fusion_table]
*1. Disconnect the Power Supply Units LG terminal from the GR terminal when testing insulation and dielectric strength.
Testing the insulation and dielectric strength with the LG terminal and the GR terminals connected will damage
internal circuits in the CPU Unit.
*2. Supported only when mounted to CPU Rack.
*3. The inrush current is given for a cold start at room temperature. The inrush control circuit uses a thermistor element
with a low-temperature current control characteristic. If the ambient temperature is high or the PLC is hot-started, the
thermistor will not be sufficiently cool, and the inrush currents given in the table may be exceeded by up to twice the
given values. When selecting fuses or breakers for external circuits, allow sufficient margin in shut-off performance.
*4. Maintain an ambient storage temperature of −25 to 30°C and relative humidity of 25% to 70% when storing the Unit for
longer than 3 months to keep the replacement notification function in optimum working condition.
*5. Change the applied voltage gradually using the adjuster on the Tester. If the full dielectric strength voltage is applied
or turned OFF using the switch on the Tester, the generated impulse voltage may damage the Power Supply Unit.
*6. CJ1W-PD022 is not insulated between the primary DC power and secondary DC power.
*7. Internal components in the Power Supply Unit will deteriorate or be damaged if the Power Supply Unit is used for an
extended period of time exceeding the power supply output capacity or if the outputs are shorted.
*8. Final order entry date for CJ1M :The end of March, 2021
Testing the insulation and dielectric strength with the LG terminal and the GR terminals connected will damage
internal circuits in the CPU Unit.
*2. Supported only when mounted to CPU Rack.
*3. The inrush current is given for a cold start at room temperature. The inrush control circuit uses a thermistor element
with a low-temperature current control characteristic. If the ambient temperature is high or the PLC is hot-started, the
thermistor will not be sufficiently cool, and the inrush currents given in the table may be exceeded by up to twice the
given values. When selecting fuses or breakers for external circuits, allow sufficient margin in shut-off performance.
*4. Maintain an ambient storage temperature of −25 to 30°C and relative humidity of 25% to 70% when storing the Unit for
longer than 3 months to keep the replacement notification function in optimum working condition.
*5. Change the applied voltage gradually using the adjuster on the Tester. If the full dielectric strength voltage is applied
or turned OFF using the switch on the Tester, the generated impulse voltage may damage the Power Supply Unit.
*6. CJ1W-PD022 is not insulated between the primary DC power and secondary DC power.
*7. Internal components in the Power Supply Unit will deteriorate or be damaged if the Power Supply Unit is used for an
extended period of time exceeding the power supply output capacity or if the outputs are shorted.
*8. Final order entry date for CJ1M :The end of March, 2021
Model | CJ1W-PA202, CJ1W-PA205C, CJ1W-PA205R, CJ1W-PD022, CJ1W-PD025 |
---|