Specifications

[fusion_table fusion_table_type=”1″ fusion_table_rows=”” fusion_table_columns=”” margin_top=”1 ps” margin_right=”1 ps” margin_bottom=”1 ps” margin_left=”1 ps” hide_on_mobile=”small-visibility,medium-visibility,large-visibility” class=”” id=”” animation_type=”” animation_direction=”left” animation_color=”” hue=”” saturation=”” lightness=”” alpha=”” animation_speed=”0.3″ animation_delay=”0″ animation_offset=””]

Item Specifications
Product Number AFP7HSC4T
Part Number AFP7HSC4T
Input:Insulation method Photocoupler insulation
Input:Rated input voltage 12 to 24 V DC / 3.5 to 5 V DC
Input:Input impedance:24 V DC 3.0 kOhm approx.
Input:Input impedance:5 V DC 390 Ohm (5 V DC) approx.
Input:Usage voltage range:24 V DC 10.8 to 26.4 V DC
Input:Usage voltage range:5 V DC 3.5 to 5.25 V DC
Input:Min. ON voltage / Min. ON current:24 V DC 10 V DC / 4 mA
Input:Min. ON voltage / Min. ON current:5 V DC 3.0 V DC / 4 mA
Input:Min. OFF voltage / Min. OFF current:24 V DC 2.0 V DC / 2 mA
Input:Min. OFF voltage / Min. OFF current:5 V DC 1.0 V DC / 0.5 mA
Input:Input time constant setting None, 0.1 micro s, 0.2 micro s, 0.5 micro s, 1.0 micro s, 2.0 micro s and 10.0 micro s
Count function:No. of counters 4ch
Count function:Counter type Linear counter / Ring counter
Count function:Counting range Signed 32-bit (-2,147,483,648 to +2,147,483,647)
Count function:Max. input frequency 4 MHz / 8 MHz for individual input (phases A and B) (Duty ratio 50 plus or minus 10 %), 4 MHz / 8 MHz for direction discrimination input (Duty ratio 50 plus or minus 10 %), 4 MHz / 8 MHz /16 MHz for 2-phase input (Duty ratio 50 plus or minus 10 %, Phase shifting below 5 %)
Count function:Input signal Phases A, B and Z
Count function:External I/O Control signal input: 8 points (2 points/ch), External output: 8 points (2 points/ch)
Count function:Counter input type Individual input (Phases A and B): 1 multiple, 2-multiple
Direction discrimination input: 1 multiple, 2-multiple
2-phase input: 1 multiple, 2-multiple, 4-multiple
Measurement function:Frequency measurement function Measures the intervals between the variations of count values, and calculates the frequency.
Comparison function:Target value match function Depending on the count direction, sets or resets the output when the counter value reaches the target value.
External output:Comparison result output function Outputs the result of comparison function.
Other functions:Capture function Acquires the current count value from the edges of input signals, and stores it in the capture 0 register or capture 1 register. The value of the specified capture register will be overwritten by a new value and the old value will be discarded every time a counter value is captured.
Other functions:Interrupt input function Available (2 points/ch, Max. 8 points/unit)
(Note) The interrupt input function can be used for 8 points per unit and for a maximum of 8 units (max. 64 points) in the whole system. However, the entire scan time slows down as more interrupt programs are used. Minimize the use of interrupt programs.
(Note) The priority order for interrupt inputs is as follows; In a unit, from the smallest interrupt bit. In the whole system, from the smallest unit number.

[/fusion_table]

 

COMMON GENERAL SPECIFICATIONS

[fusion_table fusion_table_type=”1″ fusion_table_rows=”” fusion_table_columns=”” margin_top=”1 ps” margin_right=”1 ps” margin_bottom=”1 ps” margin_left=”1 ps” hide_on_mobile=”small-visibility,medium-visibility,large-visibility” class=”” id=”” animation_type=”” animation_direction=”left” animation_color=”” hue=”” saturation=”” lightness=”” alpha=”” animation_speed=”0.3″ animation_delay=”0″ animation_offset=””]

Item Specifications
Ambient temperature 0 to +55 ℃ +32 to +131 ℉, Storage: -40 to +70 ℃ -40 to +158 ℉
Ambient humidity 10 to 95 % RH (at +25 ℃ +77 ℉, no condensation), Storage: 10 to 95 % RH (at +25 ℃ +77 ℉, no condensation)
Vibration resistance 5 to 8.4 Hz, single amplitude of 3.5 mm 0.138 in, 1 sweep/min. (IEC 61131-2) ; 8.4 to 150 Hz, constant acceleration of 9.8 m/s2, 1 sweep/min. (IEC 61131-2), 10 times each in X, Y, and Z directions
Shock resistance 147 m/s2 or more , 3 times each in X, Y, and Z directions (IEC61131-2)
Noise immunity 1,000 V [p-p] with pulse width 50 ns and 1 micro s (using a noise simulator)
Operating condition Free from corrosive gasses and excessive dust

[/fusion_table]

 

INDIVIDUAL GENERAL SPECIFICATIONS

[fusion_table fusion_table_type=”1″ fusion_table_rows=”” fusion_table_columns=”” margin_top=”1 ps” margin_right=”1 ps” margin_bottom=”1 ps” margin_left=”1 ps” hide_on_mobile=”small-visibility,medium-visibility,large-visibility” class=”” id=”” animation_type=”” animation_direction=”left” animation_color=”” hue=”” saturation=”” lightness=”” alpha=”” animation_speed=”0.3″ animation_delay=”0″ animation_offset=””]

Item Specifications
Rated voltage range
Current consumption 65 mA or less
Net weight 130 g approx.

[/fusion_table]