Article number |
6EP1332-4BA00 |
6EP1333-4BA00 |
Product |
S7-1500 PM1507 |
S7-1500 PM1507 |
Power supply, type |
24 V/3 A |
24 V/8 A |
Input |
|
|
type of the power supply network |
1-phase AC |
1-phase AC |
supply voltage at AC |
|
|
● initial value |
Automatic range selection |
Automatic range selection |
supply voltage |
|
|
● 1 at AC rated value |
120 V |
120 V |
● 2 at AC rated value |
230 V |
230 V |
input voltage |
|
|
● 1 at AC |
85 … 132 V |
85 … 132 V |
● 2 at AC |
170 … 264 V |
170 … 264 V |
design of input wide range input |
No |
No |
overvoltage overload capability |
2.3 × Vin rated, 1.3 ms |
2.3 × Vin rated, 1.3 ms |
operating condition of the mains buffering |
at Vin = 93/187 V |
at Vin = 93/187 V |
buffering time for rated value of the output current in the event of power failure minimum |
20 ms |
20 ms |
operating condition of the mains buffering |
at Vin = 93/187 V |
at Vin = 93/187 V |
line frequency |
|
|
● 1 rated value |
50 Hz |
50 Hz |
● 2 rated value |
60 Hz |
60 Hz |
line frequency |
45 … 65 Hz |
45 … 65 Hz |
input current |
|
|
● at rated input voltage 120 V |
1.4 A |
3.7 A |
● at rated input voltage 230 V |
0.8 A |
1.7 A |
current limitation of inrush current at 25 °C maximum |
23 A |
62 A |
duration of inrush current limiting at 25 °C |
|
|
● maximum |
3 ms |
3 ms |
I2t value maximum |
1.3 A²·s |
12 A²·s |
fuse protection type |
T 3,15 A/250 V (not accessible) |
T 6.3 A/250 V (not accessible) |
● in the feeder |
Recommended miniature circuit breaker: 10 A characteristic B or 6 A characteristic C |
Recommended miniature circuit breaker: 16 A characteristic B or 10 A characteristic C |
Output |
|
|
voltage curve at output |
Controlled, isolated DC voltage |
Controlled, isolated DC voltage |
output voltage at DC rated value |
24 V |
24 V |
output voltage |
|
|
● at output 1 at DC rated value |
24 V |
24 V |
relative overall tolerance of the voltage |
1 % |
1 % |
relative control precision of the output voltage |
|
|
● on slow fluctuation of input voltage |
0.1 % |
0.1 % |
● on slow fluctuation of ohm loading |
0.1 % |
0.1 % |
residual ripple |
|
|
● maximum |
50 mV |
50 mV |
voltage peak |
|
|
● maximum |
150 mV |
150 mV |
product function output voltage adjustable |
No |
No |
display version for normal operation |
LED green for 24 V OK; LED red for error; LED yellow for stand-by |
LED green for 24 V OK; LED red for error; LED yellow for stand-by |
behavior of the output voltage when switching on |
No overshoot of Vout (soft start) |
No overshoot of Vout (soft start) |
response delay maximum |
1.5 s |
1.5 s |
voltage increase time of the output voltage |
|
|
● typical |
10 ms |
10 ms |
output current |
|
|
● rated value |
3 A |
8 A |
● rated range |
0 … 3 A |
0 … 8 A |
supplied active power typical |
72 W |
192 W |
short-term overload current |
|
|
● on short-circuiting during the start-up typical |
12 A |
35 A |
● at short-circuit during operation typical |
12 A |
35 A |
duration of overloading capability for excess current |
|
|
● on short-circuiting during the start-up |
70 ms |
70 ms |
● at short-circuit during operation |
70 ms |
70 ms |
product feature |
|
|
● bridging of equipment |
Yes |
Yes |
number of parallel-switched equipment resources for increasing the power |
2 |
2 |
Efficiency |
|
|
efficiency in percent |
87 % |
90 % |
power loss [W] |
|
|
● at rated output voltage for rated value of the output current typical |
11 W |
21 W |
Closed-loop control |
|
|
relative control precision of the output voltage with rapid fluctuation of the input voltage by +/- 15% typical |
0.1 % |
0.1 % |
relative control precision of the output voltage load step of resistive load 50/100/50 % typical |
1 % |
2 % |
relative control precision of the output voltage at load step of resistive load 10/90/10 % typical |
3 % |
3 % |
setting time |
|
|
● load step 10 to 90% typical |
5 ms |
5 ms |
● load step 90 to 10% typical |
5 ms |
5 ms |
● maximum |
5 ms |
5 ms |
Protection and monitoring |
|
|
design of the overvoltage protection |
Additional control loop, limitation (closed loop control) at < 28.8 V |
Additional control loop, limitation (closed loop control) at < 28.8 V |
response value current limitation |
3.15 … 3.6 A |
8.4 … 9.6 A |
response value current limitation typical |
3.4 A |
9 A |
property of the output short-circuit proof |
Yes |
Yes |
design of short-circuit protection |
Electronic shutdown, automatic restart |
Electronic shutdown, automatic restart |
display version for overload and short circuit |
– |
– |
Safety |
|
|
galvanic isolation between input and output |
Yes |
Yes |
galvanic isolation |
Safety extra-low output voltage Uout acc. to EN 60950-1 and EN 50178 and EN 61131-2 |
Safety extra-low output voltage Uout acc. to EN 60950-1 and EN 50178 and EN 61131-2 |
operating resource protection class |
Class I |
Class I |
leakage current |
|
|
● maximum |
3.5 mA |
3.5 mA |
● typical |
0.4 mA |
1.3 mA |
protection class IP |
IP20 |
IP20 |
Approvals |
|
|
certificate of suitability |
|
|
● CE marking |
Yes |
Yes |
● UL approval |
Yes; cULus-Listed (UL 508, CSA C22.2 No. 142), File E143289 |
Yes; cULus-Listed (UL 508, CSA C22.2 No. 142), File E143289 |
● CSA approval |
Yes; cULus-Listed (UL 508, CSA C22.2 No. 142), File E143289 |
Yes; cULus-Listed (UL 508, CSA C22.2 No. 142), File E143289 |
● cCSAus, Class 1, Division 2 |
No |
No |
● ATEX |
Yes; ATEX (EX) II 3G Ex nA nC IIC T4 Gc |
Yes; ATEX (EX) II 3G Ex nA nC IIC T3 Gc |
certificate of suitability |
|
|
● relating to ATEX |
IECEx Ex nA nC IIC T4 Gc; ATEX (EX) II 3G Ex nA nC IIC T4 Gc; cULus (ANSI/ISA 12.12.01, CSA C22.2 No.213) Class I, Div. 2, Group ABCD, T4, File E330455 |
IECEx Ex nA nC IIC T3 Gc; ATEX (EX) II 3G Ex nA nC IIC T3 Gc; cULus (ANSI/ISA 12.12.01, CSA C22.2 No.213) Class I, Div. 2, Group ABCD, T3, File E330455 |
● IECEx |
Yes; IECEx Ex nA nC IIC T4 Gc |
Yes; IECEx Ex nA nC IIC T3 Gc |
● NEC Class 2 |
No |
No |
● ULhazloc approval |
Yes |
Yes |
● FM registration |
Yes; Class I, Div. 2, Group ABCD, T4 |
Yes; Class I, Div. 2, Group ABCD, T4 |
type of certification CB-certificate |
Yes |
Yes |
certificate of suitability |
|
|
● EAC approval |
Yes |
Yes |
certificate of suitability shipbuilding approval |
Yes |
Yes |
shipbuilding approval |
ABS, BV, DNV GL |
ABS, BV, DNV GL |
Marine classification association |
|
|
● American Bureau of Shipping Europe Ltd. (ABS) |
Yes |
Yes |
● French marine classification society (BV) |
Yes |
Yes |
● DNV GL |
Yes |
Yes |
● Lloyds Register of Shipping (LRS) |
No |
No |
● Nippon Kaiji Kyokai (NK) |
No |
No |
EMC |
|
|
standard |
|
|
● for emitted interference |
EN 55022 Class B |
EN 55022 Class B |
● for mains harmonics limitation |
EN 61000-3-2 |
EN 61000-3-2 |
● for interference immunity |
EN 61000-6-2 |
EN 61000-6-2 |
environmental conditions |
|
|
ambient temperature |
|
|
● during operation |
0 … 60 °C; with natural convection |
0 … 60 °C; with natural convection |
● during transport |
-40 … +85 °C |
-40 … +85 °C |
● during storage |
-40 … +85 °C |
-40 … +85 °C |
environmental category according to IEC 60721 |
Climate class 3K3, 5 … 95% no condensation |
Climate class 3K3, 5 … 95% no condensation |
Mechanics |
|
|
type of electrical connection |
Screw-/spring clamp connection |
Screw-/spring clamp connection |
● at input |
L, N, PE: 1 screw terminal each for 0.5 … 2.5 mm² |
L, N, PE: 1 screw terminal each for 0.5 … 2.5 mm² |
● at output |
L+, M: 2 spring-loaded terminals each for 0.5 to 2.5 mm² |
L+, M: 2 spring-loaded terminals each for 0.5 to 2.5 mm² |
product function |
|
|
● removable terminal at input |
Yes |
Yes |
● removable terminal at output |
Yes |
Yes |
width of the enclosure |
50 mm |
75 mm |
height of the enclosure |
147 mm |
147 mm |
depth of the enclosure |
129 mm |
129 mm |
required spacing |
|
|
● top |
40 mm |
40 mm |
● bottom |
40 mm |
40 mm |
● left |
0 mm |
0 mm |
● right |
0 mm |
0 mm |
net weight |
0.45 kg |
0.74 kg |
product feature of the enclosure housing can be lined up |
Yes |
Yes |
fastening method |
Can be mounted onto S7-1500 rail |
Can be mounted onto S7-1500 rail |
MTBF at 40 °C |
1 611 993 h |
1 362 918 h |
other information |
Specifications at rated input voltage and ambient temperature +25 °C (unless otherwise specified) |
Specifications at rated input voltage and ambient temperature +25 °C (unless otherwise specified) |