| Article number |
6EP1332-4BA00 |
6EP1333-4BA00 |
| Product |
S7-1500 PM1507 |
S7-1500 PM1507 |
| Power supply, type |
24 V/3 A |
24 V/8 A |
| Input |
|
|
| type of the power supply network |
1-phase AC |
1-phase AC |
| supply voltage at AC |
|
|
| ● initial value |
Automatic range selection |
Automatic range selection |
| supply voltage |
|
|
| ● 1 at AC rated value |
120 V |
120 V |
| ● 2 at AC rated value |
230 V |
230 V |
| input voltage |
|
|
| ● 1 at AC |
85 … 132 V |
85 … 132 V |
| ● 2 at AC |
170 … 264 V |
170 … 264 V |
| design of input wide range input |
No |
No |
| overvoltage overload capability |
2.3 × Vin rated, 1.3 ms |
2.3 × Vin rated, 1.3 ms |
| operating condition of the mains buffering |
at Vin = 93/187 V |
at Vin = 93/187 V |
| buffering time for rated value of the output current in the event of power failure minimum |
20 ms |
20 ms |
| operating condition of the mains buffering |
at Vin = 93/187 V |
at Vin = 93/187 V |
| line frequency |
|
|
| ● 1 rated value |
50 Hz |
50 Hz |
| ● 2 rated value |
60 Hz |
60 Hz |
| line frequency |
45 … 65 Hz |
45 … 65 Hz |
| input current |
|
|
| ● at rated input voltage 120 V |
1.4 A |
3.7 A |
| ● at rated input voltage 230 V |
0.8 A |
1.7 A |
| current limitation of inrush current at 25 °C maximum |
23 A |
62 A |
| duration of inrush current limiting at 25 °C |
|
|
| ● maximum |
3 ms |
3 ms |
| I2t value maximum |
1.3 A²·s |
12 A²·s |
| fuse protection type |
T 3,15 A/250 V (not accessible) |
T 6.3 A/250 V (not accessible) |
| ● in the feeder |
Recommended miniature circuit breaker: 10 A characteristic B or 6 A characteristic C |
Recommended miniature circuit breaker: 16 A characteristic B or 10 A characteristic C |
| Output |
|
|
| voltage curve at output |
Controlled, isolated DC voltage |
Controlled, isolated DC voltage |
| output voltage at DC rated value |
24 V |
24 V |
| output voltage |
|
|
| ● at output 1 at DC rated value |
24 V |
24 V |
| relative overall tolerance of the voltage |
1 % |
1 % |
| relative control precision of the output voltage |
|
|
| ● on slow fluctuation of input voltage |
0.1 % |
0.1 % |
| ● on slow fluctuation of ohm loading |
0.1 % |
0.1 % |
| residual ripple |
|
|
| ● maximum |
50 mV |
50 mV |
| voltage peak |
|
|
| ● maximum |
150 mV |
150 mV |
| product function output voltage adjustable |
No |
No |
| display version for normal operation |
LED green for 24 V OK; LED red for error; LED yellow for stand-by |
LED green for 24 V OK; LED red for error; LED yellow for stand-by |
| behavior of the output voltage when switching on |
No overshoot of Vout (soft start) |
No overshoot of Vout (soft start) |
| response delay maximum |
1.5 s |
1.5 s |
| voltage increase time of the output voltage |
|
|
| ● typical |
10 ms |
10 ms |
| output current |
|
|
| ● rated value |
3 A |
8 A |
| ● rated range |
0 … 3 A |
0 … 8 A |
| supplied active power typical |
72 W |
192 W |
| short-term overload current |
|
|
| ● on short-circuiting during the start-up typical |
12 A |
35 A |
| ● at short-circuit during operation typical |
12 A |
35 A |
| duration of overloading capability for excess current |
|
|
| ● on short-circuiting during the start-up |
70 ms |
70 ms |
| ● at short-circuit during operation |
70 ms |
70 ms |
| product feature |
|
|
| ● bridging of equipment |
Yes |
Yes |
| number of parallel-switched equipment resources for increasing the power |
2 |
2 |
| Efficiency |
|
|
| efficiency in percent |
87 % |
90 % |
| power loss [W] |
|
|
| ● at rated output voltage for rated value of the output current typical |
11 W |
21 W |
| Closed-loop control |
|
|
| relative control precision of the output voltage with rapid fluctuation of the input voltage by +/- 15% typical |
0.1 % |
0.1 % |
| relative control precision of the output voltage load step of resistive load 50/100/50 % typical |
1 % |
2 % |
| relative control precision of the output voltage at load step of resistive load 10/90/10 % typical |
3 % |
3 % |
| setting time |
|
|
| ● load step 10 to 90% typical |
5 ms |
5 ms |
| ● load step 90 to 10% typical |
5 ms |
5 ms |
| ● maximum |
5 ms |
5 ms |
| Protection and monitoring |
|
|
| design of the overvoltage protection |
Additional control loop, limitation (closed loop control) at < 28.8 V |
Additional control loop, limitation (closed loop control) at < 28.8 V |
| response value current limitation |
3.15 … 3.6 A |
8.4 … 9.6 A |
| response value current limitation typical |
3.4 A |
9 A |
| property of the output short-circuit proof |
Yes |
Yes |
| design of short-circuit protection |
Electronic shutdown, automatic restart |
Electronic shutdown, automatic restart |
| display version for overload and short circuit |
– |
– |
| Safety |
|
|
| galvanic isolation between input and output |
Yes |
Yes |
| galvanic isolation |
Safety extra-low output voltage Uout acc. to EN 60950-1 and EN 50178 and EN 61131-2 |
Safety extra-low output voltage Uout acc. to EN 60950-1 and EN 50178 and EN 61131-2 |
| operating resource protection class |
Class I |
Class I |
| leakage current |
|
|
| ● maximum |
3.5 mA |
3.5 mA |
| ● typical |
0.4 mA |
1.3 mA |
| protection class IP |
IP20 |
IP20 |
| Approvals |
|
|
| certificate of suitability |
|
|
| ● CE marking |
Yes |
Yes |
| ● UL approval |
Yes; cULus-Listed (UL 508, CSA C22.2 No. 142), File E143289 |
Yes; cULus-Listed (UL 508, CSA C22.2 No. 142), File E143289 |
| ● CSA approval |
Yes; cULus-Listed (UL 508, CSA C22.2 No. 142), File E143289 |
Yes; cULus-Listed (UL 508, CSA C22.2 No. 142), File E143289 |
| ● cCSAus, Class 1, Division 2 |
No |
No |
| ● ATEX |
Yes; ATEX (EX) II 3G Ex nA nC IIC T4 Gc |
Yes; ATEX (EX) II 3G Ex nA nC IIC T3 Gc |
| certificate of suitability |
|
|
| ● relating to ATEX |
IECEx Ex nA nC IIC T4 Gc; ATEX (EX) II 3G Ex nA nC IIC T4 Gc; cULus (ANSI/ISA 12.12.01, CSA C22.2 No.213) Class I, Div. 2, Group ABCD, T4, File E330455 |
IECEx Ex nA nC IIC T3 Gc; ATEX (EX) II 3G Ex nA nC IIC T3 Gc; cULus (ANSI/ISA 12.12.01, CSA C22.2 No.213) Class I, Div. 2, Group ABCD, T3, File E330455 |
| ● IECEx |
Yes; IECEx Ex nA nC IIC T4 Gc |
Yes; IECEx Ex nA nC IIC T3 Gc |
| ● NEC Class 2 |
No |
No |
| ● ULhazloc approval |
Yes |
Yes |
| ● FM registration |
Yes; Class I, Div. 2, Group ABCD, T4 |
Yes; Class I, Div. 2, Group ABCD, T4 |
| type of certification CB-certificate |
Yes |
Yes |
| certificate of suitability |
|
|
| ● EAC approval |
Yes |
Yes |
| certificate of suitability shipbuilding approval |
Yes |
Yes |
| shipbuilding approval |
ABS, BV, DNV GL |
ABS, BV, DNV GL |
| Marine classification association |
|
|
| ● American Bureau of Shipping Europe Ltd. (ABS) |
Yes |
Yes |
| ● French marine classification society (BV) |
Yes |
Yes |
| ● DNV GL |
Yes |
Yes |
| ● Lloyds Register of Shipping (LRS) |
No |
No |
| ● Nippon Kaiji Kyokai (NK) |
No |
No |
| EMC |
|
|
| standard |
|
|
| ● for emitted interference |
EN 55022 Class B |
EN 55022 Class B |
| ● for mains harmonics limitation |
EN 61000-3-2 |
EN 61000-3-2 |
| ● for interference immunity |
EN 61000-6-2 |
EN 61000-6-2 |
| environmental conditions |
|
|
| ambient temperature |
|
|
| ● during operation |
0 … 60 °C; with natural convection |
0 … 60 °C; with natural convection |
| ● during transport |
-40 … +85 °C |
-40 … +85 °C |
| ● during storage |
-40 … +85 °C |
-40 … +85 °C |
| environmental category according to IEC 60721 |
Climate class 3K3, 5 … 95% no condensation |
Climate class 3K3, 5 … 95% no condensation |
| Mechanics |
|
|
| type of electrical connection |
Screw-/spring clamp connection |
Screw-/spring clamp connection |
| ● at input |
L, N, PE: 1 screw terminal each for 0.5 … 2.5 mm² |
L, N, PE: 1 screw terminal each for 0.5 … 2.5 mm² |
| ● at output |
L+, M: 2 spring-loaded terminals each for 0.5 to 2.5 mm² |
L+, M: 2 spring-loaded terminals each for 0.5 to 2.5 mm² |
| product function |
|
|
| ● removable terminal at input |
Yes |
Yes |
| ● removable terminal at output |
Yes |
Yes |
| width of the enclosure |
50 mm |
75 mm |
| height of the enclosure |
147 mm |
147 mm |
| depth of the enclosure |
129 mm |
129 mm |
| required spacing |
|
|
| ● top |
40 mm |
40 mm |
| ● bottom |
40 mm |
40 mm |
| ● left |
0 mm |
0 mm |
| ● right |
0 mm |
0 mm |
| net weight |
0.45 kg |
0.74 kg |
| product feature of the enclosure housing can be lined up |
Yes |
Yes |
| fastening method |
Can be mounted onto S7-1500 rail |
Can be mounted onto S7-1500 rail |
| MTBF at 40 °C |
1 611 993 h |
1 362 918 h |
| other information |
Specifications at rated input voltage and ambient temperature +25 °C (unless otherwise specified) |
Specifications at rated input voltage and ambient temperature +25 °C (unless otherwise specified) |