product type designation |
CP 443-1 |
transfer rate |
|
transfer rate |
|
● at the 1st interface |
10 … 100 Mbit/s |
interfaces |
|
number of interfaces according to Industrial Ethernet |
2 |
number of electrical connections |
|
● at the 1st interface according to Industrial Ethernet |
2 |
type of electrical connection |
|
● at the 1st interface according to Industrial Ethernet |
RJ45 port |
design of the removable storage |
|
● C-PLUG |
No |
supply voltage, current consumption, power loss |
|
type of voltage of the supply voltage |
DC |
supply voltage 1 from backplane bus |
5 V |
relative symmetrical tolerance at DC |
|
● at 5 V |
5 % |
consumed current |
|
● from backplane bus at DC at 5 V typical |
1.4 A |
power loss [W] |
7.25 W |
ambient conditions |
|
ambient temperature |
|
● during operation |
0 … 60 °C |
● during storage |
-40 … +70 °C |
● during transport |
-40 … +70 °C |
relative humidity |
|
● at 25 °C without condensation during operation maximum |
95 % |
protection class IP |
IP20 |
design, dimensions and weights |
|
module format |
Compact module S7-400 single width |
width |
25 mm |
height |
290 mm |
depth |
210 mm |
net weight |
0.7 kg |
product features, product functions, product components general |
|
number of units |
|
● per CPU maximum |
14 |
● note |
max. 4 as PN IO ctrl. |
performance data open communication |
|
number of possible connections for open communication by means of SEND/RECEIVE blocks maximum |
64 |
data volume |
|
● as user data per ISO connection for open communication by means of SEND/RECEIVE blocks maximum |
8 Kibyte |
● as user data per ISO on TCP connection for open communication by means of SEND/RECEIVE blocks maximum |
8 Kibyte |
● as user data per TCP connection for open communication by means of SEND/RECEIVE blocks maximum |
8 Kibyte |
● as user data per UDP connection for open IE communication by means of SEND/RECEIVE blocks maximum |
2 Kibyte |
number of possible connections for open communication |
|
● by means of T blocks maximum |
64 |
data volume |
|
● as user data per ISO on TCP connection for open communication by means of T blocks maximum |
1 452 byte |
performance data S7 communication |
|
number of possible connections for S7 communication |
|
● maximum |
128; when using several CPUs |
● with PG connections maximum |
2 |
performance data multi-protocol mode |
|
number of active connections with multi-protocol mode |
128 |
performance data PROFINET communication as PN IO controller |
|
product function PROFINET IO controller |
Yes |
number of PN IO devices on PROFINET IO controller operable total |
128 |
number of PN IO IRT devices on PROFINET IO controller operable |
64 |
number of external PN IO lines with PROFINET per rack |
4 |
data volume |
|
● as user data for input variables as PROFINET IO controller maximum |
4 Kibyte |
● as user data for output variables as PROFINET IO controller maximum |
4 Kibyte |
● as user data for input variables per PN IO device as PROFINET IO controller maximum |
1 433 byte |
● as user data for output variables per PN IO device as PROFINET IO controller maximum |
1 433 byte |
● as user data for input variables per PN IO device for each sub-module as PROFINET IO controller maximum |
240 byte |
● as user data for output variables per PN IO device for each sub-module as PROFINET IO controller maximum |
240 byte |
product functions management, configuration, engineering |
|
product function MIB support |
Yes |
protocol is supported |
|
● SNMP v1 |
Yes |
● DCP |
Yes |
● LLDP |
Yes |
configuration software |
|
● required |
STEP 7 V5.5 SP3 or higher / STEP 7 Professional V12 (TIA Portal) or higher |
product functions diagnostics |
|
product function web-based diagnostics |
Yes |
product functions switch |
|
product feature switch |
Yes |
product function |
|
● switch-managed |
No |
● with IRT PROFINET IO switch |
Yes |
● configuration with STEP 7 |
Yes |
product functions redundancy |
|
product function |
|
● ring redundancy |
Yes |
● redundancy manager |
Yes |
protocol is supported Media Redundancy Protocol (MRP) |
Yes |
product functions security |
|
product function |
|
● password protection for Web applications |
No |
● ACL – IP-based |
Yes |
● ACL – IP-based for PLC/routing |
No |
● switch-off of non-required services |
Yes |
● blocking of communication via physical ports |
Yes |
● log file for unauthorized access |
No |
product functions time |
|
product function SICLOCK support |
Yes |
product function pass on time synchronization |
Yes |
protocol is supported |
|
● NTP |
Yes |
● SIMATIC time synchronization (SIMATIC Time) |
Yes |
standards, specifications, approvals hazardous environments |
|
certificate of suitability CCC for hazardous zone according to GB standard |
Yes |