$ 2,003.30
General information | |
Product type designation | CPU 1215C DC/DC/DC |
Firmware version | V4.1 |
based on | 6ES7215-1AG40-0XB0 |
Engineering with | |
● STEP 7 TIA Portal configurable/integrated from version | see entry ID: 109746275 |
Supply voltage | |
Rated value (DC) | |
● 24 V DC | Yes |
permissible range, lower limit (DC) | 20.4 V |
permissible range, upper limit (DC) | 28.8 V |
Load voltage L+ | |
● Rated value (DC) | 24 V |
● permissible range, lower limit (DC) | 5 V |
● permissible range, upper limit (DC) | 250 V |
Input current | |
Current consumption (rated value) | 500 mA; CPU only |
Current consumption, max. | 1 500 mA; CPU with all expansion modules |
Inrush current, max. | 12 A; at 28.8 V DC |
Output current | |
for backplane bus (5 V DC), max. | 1 600 mA; Max. 5 V DC for SM and CM |
Encoder supply | |
24 V encoder supply | |
● 24 V | L+ minus 4 V DC min. |
Power loss | |
Power loss, typ. | 12 W |
Memory | |
Work memory | |
● integrated | 100 kbyte |
Load memory | |
● integrated | 4 Mbyte |
● Plug-in (SIMATIC Memory Card), max. | with SIMATIC memory card |
Backup | |
● present | Yes; maintenance-free |
● without battery | Yes |
CPU processing times | |
for bit operations, typ. | 0.085 µs; / instruction |
for word operations, typ. | 1.5 µs; / instruction |
for floating point arithmetic, typ. | 2.5 µs; / instruction |
CPU-blocks | |
Number of blocks (total) | DBs, FCs, FBs, counters and timers. The maximum number of addressable blocks ranges from 1 to 65535. There is no restriction, the entire working memory can be used |
OB | |
● Number, max. | Limited only by RAM for code |
Data areas and their retentivity | |
Retentive data area (incl. timers, counters, flags), max. | 10 kbyte |
Flag | |
● Size, max. | 8 kbyte; Size of bit memory address area |
Address area | |
I/O address area | |
● Inputs | 1 024 byte |
● Outputs | 1 024 byte |
Process image | |
● Inputs, adjustable | 1 kbyte |
● Outputs, adjustable | 1 kbyte |
Hardware configuration | |
Number of modules per system, max. | 3 comm. modules, 1 signal board, 8 signal modules |
Time of day | |
Clock | |
● Hardware clock (real-time) | Yes |
● Backup time | 480 h; Typical |
● Deviation per day, max. | ±60 s/month at 25 °C |
Digital inputs | |
Number of digital inputs | 14; Integrated |
● of which inputs usable for technological functions | 6; HSC (High Speed Counting) |
Source/sink input | Yes |
Number of simultaneously controllable inputs | |
all mounting positions | |
— up to 40 °C, max. | 14 |
Input voltage | |
● Rated value (DC) | 24 V |
● for signal “0” | 5 V DC at 1 mA |
● for signal “1” | 15 V DC at 2.5 mA |
Input delay (for rated value of input voltage) | |
for standard inputs | |
— parameterizable | 0.2 ms, 0.4 ms, 0.8 ms, 1.6 ms, 3.2 ms, 6.4 ms and 12.8 ms, selectable in groups of four |
— at “0” to “1”, min. | 0.2 ms |
— at “0” to “1”, max. | 12.8 ms |
for interrupt inputs | |
— parameterizable | Yes |
for technological functions | |
— parameterizable | Single phase : 3 at 100 kHz & 3 at 30 kHz, differential: 3 at 80 kHz & 3 at 30 kHz |
Cable length | |
● shielded, max. | 500 m; 50 m for technological functions |
● unshielded, max. | 300 m; for technological functions: No |
Digital outputs | |
Number of digital outputs | 10 |
● of which high-speed outputs | 4; 100 kHz Pulse Train Output |
Switching capacity of the outputs | |
● with resistive load, max. | 0.5 A |
Output delay with resistive load | |
● “0” to “1”, max. | 1 µs |
● “1” to “0”, max. | 5 µs |
Relay outputs | |
● Number of relay outputs | 0 |
Cable length | |
● shielded, max. | 500 m |
● unshielded, max. | 150 m |
Analog inputs | |
Number of analog inputs | 2 |
Input ranges | |
● Voltage | Yes |
Input ranges (rated values), voltages | |
● 0 to +10 V | Yes |
— Input resistance (0 to 10 V) | ≥100k ohms |
Cable length | |
● shielded, max. | 100 m; twisted and shielded |
Analog outputs | |
Number of analog outputs | 2 |
Output ranges, current | |
● 0 to 20 mA | Yes |
Analog value generation for the inputs | |
Integration and conversion time/resolution per channel | |
● Resolution with overrange (bit including sign), max. | 10 bit |
● Integration time, parameterizable | Yes |
● Conversion time (per channel) | 625 µs |
Analog value generation for the outputs | |
Integration and conversion time/resolution per channel | |
● Resolution with overrange (bit including sign), max. | 10 bit |
Encoder | |
Connectable encoders | |
● 2-wire sensor | Yes |
1. Interface | |
Interface type | PROFINET |
Isolated | Yes |
automatic detection of transmission rate | Yes |
Autonegotiation | Yes |
Autocrossing | Yes |
Interface types | |
● RJ 45 (Ethernet) | Yes |
Protocols | |
● PROFINET IO Controller | Yes |
● PROFINET IO Device | Yes; Also simultaneously with IO-Device functionality |
PROFINET IO Controller | |
● Transmission rate, max. | 100 Mbit/s |
Services | |
— Number of connectable IO Devices, max. | 16 |
PROFINET IO Device | |
Services | |
— Shared device | Yes |
— Number of IO Controllers with shared device, max. | 2 |
Protocols | |
Supports protocol for PROFINET IO | Yes |
PROFIsafe | No |
PROFIBUS | Yes; CM 1243-5 required |
AS-Interface | Yes |
Protocols (Ethernet) | |
● TCP/IP | Yes |
Open IE communication | |
● TCP/IP | Yes |
● ISO-on-TCP (RFC1006) | Yes |
● UDP | Yes |
Web server | |
● supported | Yes |
● User-defined websites | Yes |
Further protocols | |
● MODBUS | Yes |
communication functions / header | |
S7 communication | |
● supported | Yes |
● as server | Yes |
● as client | Yes |
Number of connections | |
● overall | 16; dynamically |
Test commissioning functions | |
Status/control | |
● Status/control variable | Yes |
● Variables | Inputs/outputs, memory bits, DBs, distributed I/Os, timers, counters |
Forcing | |
● Forcing | Yes |
Diagnostic buffer | |
● present | Yes |
Integrated Functions | |
Counter | |
● Number of counters | 6 |
● Counting frequency, max. | 100 kHz |
Frequency measurement | Yes |
controlled positioning | Yes |
Number of position-controlled positioning axes, max. | 8 |
Number of positioning axes via pulse-direction interface | 4; With integrated outputs |
PID controller | Yes |
Number of alarm inputs | 4 |
Number of pulse outputs | 4 |
Limit frequency (pulse) | 100 kHz |
Potential separation | |
Potential separation digital inputs | |
● Potential separation digital inputs | No |
● between the channels, in groups of | 1 |
Potential separation digital outputs | |
● between the channels | No |
● between the channels, in groups of | 1 |
EMC | |
Interference immunity against discharge of static electricity | |
● Interference immunity against discharge of static electricity acc. to IEC 61000-4-2 |
Yes |
— Test voltage at air discharge | 8 kV |
— Test voltage at contact discharge | 6 kV |
Interference immunity to cable-borne interference | |
● Interference immunity on supply lines acc. to IEC 61000- 4-4 |
Yes |
● Interference immunity on signal cables acc. to IEC 61000- 4-4 |
Yes |
Interference immunity against voltage surge | |
● Interference immunity on supply lines acc. to IEC 61000- 4-5 |
Yes |
Interference immunity against conducted variable disturbance induced by high-frequency fields | |
● Interference immunity against high-frequency radiation acc. to IEC 61000-4-6 |
Yes |
Emission of radio interference acc. to EN 55 011 | |
● Limit class A, for use in industrial areas | Yes; Group 1 |
● Limit class B, for use in residential areas | Yes; When appropriate measures are used to ensure compliance with the limits for Class B according to EN 55011 |
Degree and class of protection | |
IP degree of protection | IP20 |
Ambient conditions | |
Free fall | |
● Fall height, max. | 0.3 m; five times, in product package |
Ambient temperature during operation | |
● min. | -40 °C; = Tmin (incl. condensation/frost); start-up @ -25 °C |
● max. | 60 °C; = Tmax; Tmax > +55 °C number of simultaneously switched-on digital inputs 7, digital outputs 5, analog inputs 2, analog outputs 2 (no adjacent points) with horizontal mounting position |
● At cold restart, min. | -25 °C |
Ambient temperature during storage/transportation | |
● min. | -40 °C |
● max. | 70 °C |
Altitude during operation relating to sea level | |
● Installation altitude above sea level, max. | 5 000 m |
● Ambient air temperature-barometric pressure-altitude | Tmin … Tmax at 1 140 hPa … 795 hPa (-1 000 m … +2 000 m) // Tmin … (Tmax – 10 K) at 795 hPa … 658 hPa (+2 000 m … +3 500 m) // Tmin … (Tmax -20 K) |
at 658 hPa … 540 hPa (+3 500 m … +5 000 m) | |
Relative humidity | |
● With condensation, tested in accordance with IEC 60068- 2-38, max. |
100 %; RH incl. condensation/frost (no commissioning under condensation conditions) |
Vibrations | |
● Vibration resistance during operation acc. to IEC 60068- 2-6 |
2 g (m/s²) wall mounting, 1 g (m/s²) DIN rail |
● Operation, tested according to IEC 60068-2-6 | Yes |
Shock testing | |
● tested according to IEC 60068-2-27 | Yes; IEC 68, Part 2-27 half-sine: strength of the shock 15 g (peak value), duration 11 ms |
Resistance | |
Coolants and lubricants | |
— Resistant to commercially available coolants and lubricants |
Yes; Incl. diesel and oil droplets in the air |
Use in stationary industrial systems | |
— to biologically active substances according to EN 60721-3-3 |
Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request |
— to chemically active substances according to EN 60721-3-3 |
Yes; Class 3C4 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); * |
— to mechanically active substances according to EN 60721-3-3 |
Yes; Class 3S4 incl. sand, dust, * |
Use on ships/at sea | |
— to biologically active substances according to EN 60721-3-6 |
Yes; Class 6B2 mold and fungal spores (excluding fauna); Class 6B3 on request |
— to chemically active substances according to EN 60721-3-6 |
Yes; Class 6C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); * |
— to mechanically active substances according to EN 60721-3-6 |
Yes; Class 6S3 incl. sand, dust; * |
Usage in industrial process technology | |
— Against chemically active substances acc. to EN 60654-4 |
Yes; Class 3 (excluding trichlorethylene) |
— Environmental conditions for process, measuring and control systems acc. to ANSI/ISA-71.04 |
Yes; Level GX group A/B (excluding trichlorethylene; harmful gas concentrations up to the limits of EN 60721-3-3 class 3C4 permissible); level LC3 (salt spray) and level LB3 (oil) |
Remark | |
— Note regarding classification of environmental conditions acc. to EN 60721, EN 60654-4 and ANSI/ISA-71.04 |
* The supplied plug covers must remain in place over the unused interfaces during operation! |
Conformal coating | |
● Coatings for printed circuit board assemblies acc. to EN 61086 |
Yes; Class 2 for high reliability |
● Protection against fouling acc. to EN 60664-3 | Yes; Type 1 protection |
● Military testing according to MIL-I-46058C, Amendment 7 | Yes; Discoloration of coating possible during service life |
● Qualification and Performance of Electrical Insulating Compound for Printed Board Assemblies according to IPC- CC-830A |
Yes; Conformal coating, Class A |
configuration / header | |
configuration / programming / header | |
Programming language | |
— LAD | Yes |
— FBD | Yes |
— SCL | Yes |
programming / cycle time monitoring / header | |
● adjustable | Yes |
Dimensions | |
Width | 130 mm |
Height | 100 mm |
Depth | 75 mm |
Weights | |
Weight, approx. | 500 g |
Weight | 0.467 kg |
---|---|
Dimensions | 11.50 × 13.50 × 8.50 cm |