| General information | |
| Product type designation | CPU 1215C DC/DC/DC | 
| Firmware version | V4.1 | 
| based on | 6ES7215-1AG40-0XB0 | 
| Engineering with | |
| ● STEP 7 TIA Portal configurable/integrated from version | see entry ID: 109746275 | 
| Supply voltage | |
| Rated value (DC) | |
| ● 24 V DC | Yes | 
| permissible range, lower limit (DC) | 20.4 V | 
| permissible range, upper limit (DC) | 28.8 V | 
| Load voltage L+ | |
| ● Rated value (DC) | 24 V | 
| ● permissible range, lower limit (DC) | 5 V | 
| ● permissible range, upper limit (DC) | 250 V | 
| Input current | |
| Current consumption (rated value) | 500 mA; CPU only | 
| Current consumption, max. | 1 500 mA; CPU with all expansion modules | 
| Inrush current, max. | 12 A; at 28.8 V DC | 
| Output current | |
| for backplane bus (5 V DC), max. | 1 600 mA; Max. 5 V DC for SM and CM | 
| Encoder supply | |
| 24 V encoder supply | |
| ● 24 V | L+ minus 4 V DC min. | 
| Power loss | |
| Power loss, typ. | 12 W | 
| Memory | |
| Work memory | |
| ● integrated | 100 kbyte | 
| Load memory | |
| ● integrated | 4 Mbyte | 
| ● Plug-in (SIMATIC Memory Card), max. | with SIMATIC memory card | 
| Backup | |
| ● present | Yes; maintenance-free | 
| ● without battery | Yes | 
| CPU processing times | |
| for bit operations, typ. | 0.085 µs; / instruction | 
| for word operations, typ. | 1.5 µs; / instruction | 
| for floating point arithmetic, typ. | 2.5 µs; / instruction | 
| CPU-blocks | |
| Number of blocks (total) | DBs, FCs, FBs, counters and timers. The maximum number of addressable blocks ranges from 1 to 65535. There is no restriction, the entire working memory can be used | 
| OB | |
| ● Number, max. | Limited only by RAM for code | 
| Data areas and their retentivity | |
| Retentive data area (incl. timers, counters, flags), max. | 10 kbyte | 
| Flag | |
| ● Size, max. | 8 kbyte; Size of bit memory address area | 
| Address area | |
| I/O address area | |
| ● Inputs | 1 024 byte | 
| ● Outputs | 1 024 byte | 
| Process image | |
| ● Inputs, adjustable | 1 kbyte | 
| ● Outputs, adjustable | 1 kbyte | 
| Hardware configuration | |
| Number of modules per system, max. | 3 comm. modules, 1 signal board, 8 signal modules | 
| Time of day | |
| Clock | |
| ● Hardware clock (real-time) | Yes | 
| ● Backup time | 480 h; Typical | 
| ● Deviation per day, max. | ±60 s/month at 25 °C | 
| Digital inputs | |
| Number of digital inputs | 14; Integrated | 
| ● of which inputs usable for technological functions | 6; HSC (High Speed Counting) | 
| Source/sink input | Yes | 
| Number of simultaneously controllable inputs | |
| all mounting positions | |
| — up to 40 °C, max. | 14 | 
| Input voltage | |
| ● Rated value (DC) | 24 V | 
| ● for signal “0” | 5 V DC at 1 mA | 
| ● for signal “1” | 15 V DC at 2.5 mA | 
| Input delay (for rated value of input voltage) | |
| for standard inputs | |
| — parameterizable | 0.2 ms, 0.4 ms, 0.8 ms, 1.6 ms, 3.2 ms, 6.4 ms and 12.8 ms, selectable in groups of four | 
| — at “0” to “1”, min. | 0.2 ms | 
| — at “0” to “1”, max. | 12.8 ms | 
| for interrupt inputs | |
| — parameterizable | Yes | 
| for technological functions | |
| — parameterizable | Single phase : 3 at 100 kHz & 3 at 30 kHz, differential: 3 at 80 kHz & 3 at 30 kHz | 
| Cable length | |
| ● shielded, max. | 500 m; 50 m for technological functions | 
| ● unshielded, max. | 300 m; for technological functions: No | 
| Digital outputs | |
| Number of digital outputs | 10 | 
| ● of which high-speed outputs | 4; 100 kHz Pulse Train Output | 
| Switching capacity of the outputs | |
| ● with resistive load, max. | 0.5 A | 
| Output delay with resistive load | |
| ● “0” to “1”, max. | 1 µs | 
| ● “1” to “0”, max. | 5 µs | 
| Relay outputs | |
| ● Number of relay outputs | 0 | 
| Cable length | |
| ● shielded, max. | 500 m | 
| ● unshielded, max. | 150 m | 
| Analog inputs | |
| Number of analog inputs | 2 | 
| Input ranges | |
| ● Voltage | Yes | 
| Input ranges (rated values), voltages | |
| ● 0 to +10 V | Yes | 
| — Input resistance (0 to 10 V) | ≥100k ohms | 
| Cable length | |
| ● shielded, max. | 100 m; twisted and shielded | 
| Analog outputs | |
| Number of analog outputs | 2 | 
| Output ranges, current | |
| ● 0 to 20 mA | Yes | 
| Analog value generation for the inputs | |
| Integration and conversion time/resolution per channel | |
| ● Resolution with overrange (bit including sign), max. | 10 bit | 
| ● Integration time, parameterizable | Yes | 
| ● Conversion time (per channel) | 625 µs | 
| Analog value generation for the outputs | |
| Integration and conversion time/resolution per channel | |
| ● Resolution with overrange (bit including sign), max. | 10 bit | 
| Encoder | |
| Connectable encoders | |
| ● 2-wire sensor | Yes | 
| 1. Interface | |
| Interface type | PROFINET | 
| Isolated | Yes | 
| automatic detection of transmission rate | Yes | 
| Autonegotiation | Yes | 
| Autocrossing | Yes | 
| Interface types | |
| ● RJ 45 (Ethernet) | Yes | 
| Protocols | |
| ● PROFINET IO Controller | Yes | 
| ● PROFINET IO Device | Yes; Also simultaneously with IO-Device functionality | 
| PROFINET IO Controller | |
| ● Transmission rate, max. | 100 Mbit/s | 
| Services | |
| — Number of connectable IO Devices, max. | 16 | 
| PROFINET IO Device | |
| Services | |
| — Shared device | Yes | 
| — Number of IO Controllers with shared device, max. | 2 | 
| Protocols | |
| Supports protocol for PROFINET IO | Yes | 
| PROFIsafe | No | 
| PROFIBUS | Yes; CM 1243-5 required | 
| AS-Interface | Yes | 
| Protocols (Ethernet) | |
| ● TCP/IP | Yes | 
| Open IE communication | |
| ● TCP/IP | Yes | 
| ● ISO-on-TCP (RFC1006) | Yes | 
| ● UDP | Yes | 
| Web server | |
| ● supported | Yes | 
| ● User-defined websites | Yes | 
| Further protocols | |
| ● MODBUS | Yes | 
| communication functions / header | |
| S7 communication | |
| ● supported | Yes | 
| ● as server | Yes | 
| ● as client | Yes | 
| Number of connections | |
| ● overall | 16; dynamically | 
| Test commissioning functions | |
| Status/control | |
| ● Status/control variable | Yes | 
| ● Variables | Inputs/outputs, memory bits, DBs, distributed I/Os, timers, counters | 
| Forcing | |
| ● Forcing | Yes | 
| Diagnostic buffer | |
| ● present | Yes | 
| Integrated Functions | |
| Counter | |
| ● Number of counters | 6 | 
| ● Counting frequency, max. | 100 kHz | 
| Frequency measurement | Yes | 
| controlled positioning | Yes | 
| Number of position-controlled positioning axes, max. | 8 | 
| Number of positioning axes via pulse-direction interface | 4; With integrated outputs | 
| PID controller | Yes | 
| Number of alarm inputs | 4 | 
| Number of pulse outputs | 4 | 
| Limit frequency (pulse) | 100 kHz | 
| Potential separation | |
| Potential separation digital inputs | |
| ● Potential separation digital inputs | No | 
| ● between the channels, in groups of | 1 | 
| Potential separation digital outputs | |
| ● between the channels | No | 
| ● between the channels, in groups of | 1 | 
| EMC | |
| Interference immunity against discharge of static electricity | |
| ● Interference immunity against discharge of static electricity acc. to IEC 61000-4-2 | Yes | 
| — Test voltage at air discharge | 8 kV | 
| — Test voltage at contact discharge | 6 kV | 
| Interference immunity to cable-borne interference | |
| ● Interference immunity on supply lines acc. to IEC 61000- 4-4 | Yes | 
| ● Interference immunity on signal cables acc. to IEC 61000- 4-4 | Yes | 
| Interference immunity against voltage surge | |
| ● Interference immunity on supply lines acc. to IEC 61000- 4-5 | Yes | 
| Interference immunity against conducted variable disturbance induced by high-frequency fields | |
| ● Interference immunity against high-frequency radiation acc. to IEC 61000-4-6 | Yes | 
| Emission of radio interference acc. to EN 55 011 | |
| ● Limit class A, for use in industrial areas | Yes; Group 1 | 
| ● Limit class B, for use in residential areas | Yes; When appropriate measures are used to ensure compliance with the limits for Class B according to EN 55011 | 
| Degree and class of protection | |
| IP degree of protection | IP20 | 
| Ambient conditions | |
| Free fall | |
| ● Fall height, max. | 0.3 m; five times, in product package | 
| Ambient temperature during operation | |
| ● min. | -40 °C; = Tmin (incl. condensation/frost); start-up @ -25 °C | 
| ● max. | 60 °C; = Tmax; Tmax > +55 °C number of simultaneously switched-on digital inputs 7, digital outputs 5, analog inputs 2, analog outputs 2 (no adjacent points) with horizontal mounting position | 
| ● At cold restart, min. | -25 °C | 
| Ambient temperature during storage/transportation | |
| ● min. | -40 °C | 
| ● max. | 70 °C | 
| Altitude during operation relating to sea level | |
| ● Installation altitude above sea level, max. | 5 000 m | 
| ● Ambient air temperature-barometric pressure-altitude | Tmin … Tmax at 1 140 hPa … 795 hPa (-1 000 m … +2 000 m) // Tmin … (Tmax – 10 K) at 795 hPa … 658 hPa (+2 000 m … +3 500 m) // Tmin … (Tmax -20 K) | 
| at 658 hPa … 540 hPa (+3 500 m … +5 000 m) | |
| Relative humidity | |
| ● With condensation, tested in accordance with IEC 60068- 2-38, max. | 100 %; RH incl. condensation/frost (no commissioning under condensation conditions) | 
| Vibrations | |
| ● Vibration resistance during operation acc. to IEC 60068- 2-6 | 2 g (m/s²) wall mounting, 1 g (m/s²) DIN rail | 
| ● Operation, tested according to IEC 60068-2-6 | Yes | 
| Shock testing | |
| ● tested according to IEC 60068-2-27 | Yes; IEC 68, Part 2-27 half-sine: strength of the shock 15 g (peak value), duration 11 ms | 
| Resistance | |
| Coolants and lubricants | |
| — Resistant to commercially available coolants and lubricants | Yes; Incl. diesel and oil droplets in the air | 
| Use in stationary industrial systems | |
| — to biologically active substances according to EN 60721-3-3 | Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request | 
| — to chemically active substances according to EN 60721-3-3 | Yes; Class 3C4 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); * | 
| — to mechanically active substances according to EN 60721-3-3 | Yes; Class 3S4 incl. sand, dust, * | 
| Use on ships/at sea | |
| — to biologically active substances according to EN 60721-3-6 | Yes; Class 6B2 mold and fungal spores (excluding fauna); Class 6B3 on request | 
| — to chemically active substances according to EN 60721-3-6 | Yes; Class 6C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); * | 
| — to mechanically active substances according to EN 60721-3-6 | Yes; Class 6S3 incl. sand, dust; * | 
| Usage in industrial process technology | |
| — Against chemically active substances acc. to EN 60654-4 | Yes; Class 3 (excluding trichlorethylene) | 
| — Environmental conditions for process, measuring and control systems acc. to ANSI/ISA-71.04 | Yes; Level GX group A/B (excluding trichlorethylene; harmful gas concentrations up to the limits of EN 60721-3-3 class 3C4 permissible); level LC3 (salt spray) and level LB3 (oil) | 
| Remark | |
| — Note regarding classification of environmental conditions acc. to EN 60721, EN 60654-4 and ANSI/ISA-71.04 | * The supplied plug covers must remain in place over the unused interfaces during operation! | 
| Conformal coating | |
| ● Coatings for printed circuit board assemblies acc. to EN 61086 | Yes; Class 2 for high reliability | 
| ● Protection against fouling acc. to EN 60664-3 | Yes; Type 1 protection | 
| ● Military testing according to MIL-I-46058C, Amendment 7 | Yes; Discoloration of coating possible during service life | 
| ● Qualification and Performance of Electrical Insulating Compound for Printed Board Assemblies according to IPC- CC-830A | Yes; Conformal coating, Class A | 
| configuration / header | |
| configuration / programming / header | |
| Programming language | |
| — LAD | Yes | 
| — FBD | Yes | 
| — SCL | Yes | 
| programming / cycle time monitoring / header | |
| ● adjustable | Yes | 
| Dimensions | |
| Width | 130 mm | 
| Height | 100 mm | 
| Depth | 75 mm | 
| Weights | |
| Weight, approx. | 500 g | 
| Weight | 0.467 kg | 
|---|---|