$ 284.51 – $ 452.18
Unit type |
Specification | Unit version |
Model | |||||
---|---|---|---|---|---|---|---|---|
Number of safety output points |
Internal I/O common |
Maximum load current |
Rated voltage |
Number of safety slave con- nections |
I/O re- freshing method |
|||
Safety Output Units |
2 points | Sourcing outputs (PNP) |
2.0 A/point, 4.0 A/Unit at 40°C, and 2.5 A/ Unit at 55°C The maximum load current depends on the installation orientation and ambient temperature. |
24 VDC | 1 | Free-Run refreshing |
Ver. 1.0 | NX-SOH200 |
4 points | Sourcing outputs (PNP) |
0.5 A/point and 2.0 A/Unit |
24 VDC | 1 | Free-Run refreshing |
Ver. 1.0 | NX-SOD400 |
Certification body | Standards |
---|---|
TÜV Rheinland *1 | • EN ISO 13849-1 • EN ISO 13849-2 • IEC 61508 parts 1-7 • IEC/EN 62061 • IEC/EN 61131-2 • IEC 61326-3-1 |
UL | • NRAG (UL 508 and ANSI/ISA 12.12.01) • NRAG7 (CSA C22.2 No. 142 and CSA C22.2 No. 213) |
Shipbuilding Standards | NK, LK |
*1 Using the NX-series Safety I/O Units in conjunction with the NX-series Safety CPU Unit allows you to build a safety control
system that meets the following standards:
• Requirements for SIL 3 in IEC 61508 and IEC/EN 62061
• Requirements for PLe and Safety Category 4 in EN ISO 13849-1
The NX-series Safety I/O Units are also registered for RCM, EAC, and KC compliance.
Item | Specification | |
---|---|---|
Enclosure | Mounted in a panel (open) | |
Grounding method | Ground to 100 Ω or less. | |
Operating environment |
Ambient operating temperature | 0 to 55°C (The upper limit of the ambient operating temperature is restricted by the installation orientation.) |
Ambient operating humidity | 10% to 95% (with no condensation or icing) | |
Atmosphere | Must be free from corrosive gases. | |
Ambient storage temperature | -25 to 70°C (with no condensation or icing) | |
Altitude | 2,000 m max. | |
Pollution degree | 2 or less. | |
Noise immunity | Conforms to IEC 61131-2. 2 kV on power supply line (Conforms to IEC 61000-4-4.) |
|
Insulation class | Class III (SELV) | |
Overvoltage category | II | |
EMC immunity level | Zone B | |
Vibration resistance | Conforms to IEC 60068-2-6. 5 to 8.4 Hz with 3.5-mm amplitude, 8.4 to 150 Hz, acceleration of 9.8 m/s2, 100 minutes each in X, Y, and Z directions (10 sweeps of 10 min each = 100 min total) |
|
Shock resistance | Conforms to IEC 60068-2-27. 147 m/s2, 3 times each in X, Y, and Z directions |
|
Insulation resistance | 20 MΩ between isolated circuits (at 100 VDC) | |
Dielectric strength | 510 VAC for 1 min between isolated circuits, leakage current: 5 mA max. |
|
Installation method | DIN Track (IEC 60715 TH35-7.5/TH35-15) |
Unit name | Safety Output Unit | |
---|---|---|
Model | NX-SOH200 | NX-SOD400 |
Number of safety output points |
2 points | 4 points |
Internal I/O common | PNP (sourcing outputs) | |
Maximum load current |
2.0 A/point 4.0 A/Unit at 40°C 2.5 A/Unit at 55°C The maximum load current depends on the installation orientation and ambient temperature. See Installation orientation and restrictions. |
0.5 A/point and 2.0 A/Unit |
Rated voltage | 24 VDC (20.4 to 28.8 VDC) | |
Number of safety slave connections |
1 | |
I/O refreshing method | Free-Run refreshing | |
External connection terminals |
Screwless clamping terminal block (8 terminals) | |
Indicators | ![]() |
![]() |
Safety output ON residual voltage |
1.2 V max. (Between IOV and all output terminals) | |
Safety output OFF residual voltage |
2 V max. (Between IOG and all output terminals) | |
Safety output leakage current |
0.1 mA max. | |
Dimensions | 12 × 100 × 71 mm (W × H × D) | |
Isolation method | Photocoupler isolation | |
Insulation resistance | 20 MΩ min. between isolated circuits (at 100 VDC) | |
Dielectric strength | 510 VAC for 1 min between isolated circuits, leakage current: 5 mA max. | |
I/O power supply method |
Power supplied from the NX bus | |
Current capacity of I/O power supply terminals |
IOG: 2 A max./terminal | IOG (A3 and B3): 2 A max./terminal IOG (A7 and B7): 0.5 A max./terminal |
NX Unit power consumption |
• Connected to a CPU Unit or a Communication Control Unit *1 1.05 W max. • Connected to a Communications Coupler Unit *2 0.70 W max. |
• Connected to a CPU Unit or a Communication Control Unit *1 1.10 W max. • Connected to a Communications Coupler Unit *2 0.75 W max. |
Current consumption from I/O power supply |
40 mA max. | 60 mA max. |
Weight | 65 g max. | |
Circuit layout | ![]() |
![]() |
Terminal connection diagram |
So0 and So1: Safety output terminals IOG: I/O power supply 0 V ![]() Refer to User’s manual (Cat.No.Z930) for details. |
So0 to So3: Safety output terminals IOG: I/O power supply 0 V ![]() Refer to User’s manual (Cat.No.Z930) for details. |
Installation orientation and restrictions |
Installation orientation: • Connected to a CPU Unit or a Communication Control Unit *1 Possible in the upright installation orientation. • Connected to a Communications Coupler Unit *2 6 possible orientations Restrictions: For upright installation, the ambient temperature is restricted as shown below depending on the total Unit load current. ![]() For all installation orientations other than upright installation, the ambient temperature is restricted as shown below according to the total Unit load current. ![]() |
Installation orientation: • Connected to a CPU Unit or a Communication Control Unit *1 Possible in the upright installation orientation. • Connected to a Communications Coupler Unit *2 6 possible orientations Restrictions: None |
Protective functions | Overvoltage protection circuit and short detection |
*1 The NX102 CPU Unit and the NX-CSG Communication Control Unit can be connected. The NX1P2 CPU Unit cannot be
connected.
*2 The NX-ECC20 EtherCAT Coupler Unit and NX-EIC202 EtherNet/IP Coupler Unit can be connected.
INOSAKI Limited
RM B 5/F Gaylord Comm,
Bldg 114-118 Lockhart Rd.
Hong Kong
INOSAKI Sdn. Bhd.
2-1-9, Ground Floor, One Square, Tingkat Mahsuri 1,
11900 Bayan Lepas, Penang
INOSAKI Pte. Ltd.
101 Upper Cross Street,
No. 06-17, People’s Park Centre,
Singapore (058357)