| Input | |
| type of the power supply network | 1-phase AC | 
| supply voltage at AC | Automatic range selection | 
| supply voltage | 120 V/230 V | 
| input voltage 1 at AC | 85 … 132 V | 
| input voltage 2 at AC | 170 … 264 V | 
| wide range input | No | 
| overvoltage overload capability | 2.3 × Vin rated, 1.3 ms | 
| buffering time for rated value of the output current in the event of power failure minimum | 20 ms | 
| operating condition of the mains buffering | at Vin = 93/187 V | 
| line frequency | 50/60 Hz | 
| line frequency | 47 … 63 Hz | 
| input current ● at rated input voltage 120 V ● at rated input voltage 230 V | 4.49 A 1.91 A | 
| current limitation of inrush current at 25 °C maximum | 60 A | 
| I2t value maximum | 5.6 A²·s | 
| fuse protection type | T 6.3 A/250 V (not accessible) | 
| fuse protection type in the feeder | Recommended miniature circuit breaker: from 10 A characteristic C | 
| output | |
| voltage curve at output | Controlled, isolated DC voltage | 
| output voltage at DC rated value | 24 V | 
| output voltage ● at output 1 at DC rated value | 24 V | 
| output voltage adjustable | Yes; via potentiometer | 
| adjustable output voltage | 22.8 … 28 V | 
| relative overall tolerance of the voltage | 3% | 
| relative control precision of the output voltage ● on slow fluctuation of input voltage ● on slow fluctuation of ohm loading | 0.1 % 1 % | 
| residual ripple ● maximum ● typical | 150 mV 20 mV | 
| voltage peak ● maximum ● typical | 240 mV 160 mV | 
| display version for normal operation | Green LED for 24 V OK | 
| type of signal at output | Relay contact (NO contact, rating 60 V DC/ 0.3 A) for “24 V OK” | 
| behavior of the output voltage when switching on | Overshoot of Vout < 3 % | 
| response delay maximum | 0.3 s | 
| voltage increase time of the output voltage ● typical | 20 ms | 
| output current ● rated value ● rated range | 10 A 0 … 12 A; 12 A up to +45°C; +60 … +70 °C: Derating 3%/K | 
| supplied active power typical | 288 W | 
| short-term overload current ● on short-circuiting during the start-up typical ● at short-circuit during operation typical | 32 A 32 A | 
| duration of overloading capability for excess current ● on short-circuiting during the start-up ● at short-circuit during operation | 1 000 ms 1 000 ms | 
| bridging of equipment | Yes | 
| number of parallel-switched equipment resources for increasing the power | 2 | 
| efficiency | |
| efficiency in percent | 90% | 
| power loss [W] ● at rated output voltage for rated value of the output current typical | 25 W | 
| closed-loop control | |
| relative control precision of the output voltage with rapid fluctuation of the input voltage by +/- 15% typical | 0.30% | 
| relative control precision of the output voltage at load step of resistive load 10/90/10 % typical | 3% | 
| setting time ● load step 10 to 90% typical ● load step 90 to 10% typical | 1 ms 1 ms | 
| protection and monitoring | |
| design of the overvoltage protection | protection against overvoltage in case of internal fault Vout < 33 V | 
| property of the output short-circuit proof | Yes | 
| design of short-circuit protection | Constant current characteristic | 
| response value current limitation | 12 … 14.6 A | 
| overcurrent overload capability ● in normal operation | overload capability 150 % Iout rated up to 5 s/min | 
| enduring short circuit current RMS value ● typical | 14.6 A | 
| safety | |
| galvanic isolation between input and output | Yes | 
| galvanic isolation | Safety extra-low output voltage Uout acc. to EN 60950-1 and EN 50178 | 
| operating resource protection class | Class I | 
| leakage current ● maximum ● typical | 3.5 mA 0.8 mA | 
| protection class IP | IP20 | 
| EMC | |
| standard ● for emitted interference ● for mains harmonics limitation ● for interference immunity | EN 55022 Class B EN 61000-3-2 EN 61000-6-2 | 
| standards, specifications, approvals | |
| certificate of suitability ● CE marking ● UL approval ● CSA approval ● UKCA marking ● EAC approval ● NEC Class 2 | Yes Yes; cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259; cCSAus (CSA C22.2 No. 60950-1, UL 60950-1) Yes; cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259; cCSAus (CSA C22.2 No. 60950-1, UL 60950-1) Yes Yes No | 
| type of certification ● BIS ● CB-certificate | Yes; R-41188271 Yes | 
| MTBF at 40 °C | 1 614 510 h | 
| standards, specifications, approvals hazardous environments | |
| certificate of suitability ● IECEx No ● ATEX No ● ULhazloc approval No ● cCSAus, Class 1, Division 2 No ● FM registration | No No No No No | 
| standards, specifications, approvals marine classification | |
| shipbuilding approval | Yes | 
| Marine classification association ● American Bureau of Shipping Europe Ltd. (ABS) ● French marine classification society (BV) ● Det Norske Veritas (DNV) ● Lloyds Register of Shipping (LRS) | No Yes Yes No | 
| standards, specifications, approvals Environmental Product Declaration | |
| Environmental Product Declaration | Yes | 
| global warming potential [CO2 eq] ● total ● during manufacturing ● during operation ● after end of life | 803.2 kg 20.7 kg 781.8 kg 0.57 kg | 
| ambient conditions | |
| ambient temperature ● during operation ● during transport ● during storage | -25 … +70; with natural convection -40 … +85 -40 … +85 | 
| environmental category according to IEC 60721 | Climate class 3K3, 5 … 95% no condensation | 
| connection method | |
| type of electrical connection screw terminal ● at input ● at output ● for auxiliary contacts ● for signaling contact | screw terminal L, N, PE: 1 each for 0.5 … 2.5 mm² single-core/finely stranded +, -: 2 screw terminals each for 0.5 … 2.5 mm² Alarm signals: 2 screw terminals for 0.5 … 2.5 mm² 2 screw terminals for 0.5 … 2.5 mm² | 
| mechanical data | |
| width × height × depth of the enclosure | 70 × 125 × 120 mm | 
| installation width × mounting height | 70 mm × 225 mm | 
| required spacing ● top ● bottom ● left ● right | 50 mm 50 mm 0 mm 0 mm | 
| fastening method ● DIN-rail mounting ● S7 rail mounting ● wall mounting | Snaps onto DIN rail EN 60715 35×7.5/15 Yes No No | 
| housing can be lined up | Yes | 
| net weight | 0.8 kg | 
| accessories | |
| electrical accessories | Buffer module | 
| mechanical accessories | Device identification label 20 mm × 7 mm, pale turquoise 3RT1900-1SB20 | 
| Weight | 0.700 kg | 
|---|---|
| Dimensions | 14 × 14 × 8 cm |