| General specifications | 
| Switching function | Normally closed (NC) | 
| Output type | NAMUR | 
| Rated operating distance | 5 mm | 
| Installation | flush | 
| Assured operating distance | 0 … 4.05 mm | 
| Actual operating distance | 4.5 … 5.5 mm typ. 5 mm | 
| Reduction factor rAl | 0.35 | 
| Reduction factor rCu | 0.3 | 
| Reduction factor r304 | 0.74 | 
| Output type | 2-wire | 
| Nominal ratings | 
| Nominal voltage | 8.2 V (Ri approx. 1 kΩ) | 
| Switching frequency | 0 … 400 Hz | 
| Hysteresis | 1 … 15 typ. 5 % | 
| Reverse polarity protection | reverse polarity protected | 
| Short-circuit protection | yes | 
| Current consumption |  | 
| Measuring plate not detected | min. 3 mA | 
| Measuring plate detected | ≤ 1 mA | 
| Switching state indicator | Multihole-LED, yellow | 
| Functional safety related parameters | 
| Safety Integrity Level (SIL) | SIL 2 | 
| MTTFd | 1880 a | 
| Mission Time (TM) | 20 a | 
| Diagnostic Coverage (DC) | 0 % | 
| Compliance with standards and directives | 
| Standard conformity |  | 
| NAMUR | EN 60947-5-6:2000 IEC 60947-5-6:1999
 | 
| Electromagnetic compatibility | NE 21:2007 | 
| Standards | EN 60947-5-2:2007 EN 60947-5-2/A1:2012
 IEC 60947-5-2:2007
 IEC 60947-5-2 AMD 1:2012
 | 
| Approvals and certificates | 
| IECEx approval |  | 
| Equipment protection level Ga | IECEx PTB 11.0037X | 
| Equipment protection level Gb | IECEx PTB 11.0037X | 
| Equipment protection level Da | IECEx PTB 11.0037X | 
| Equipment protection level Mb | IECEx PTB 11.0037X | 
| ATEX approval |  | 
| Equipment protection level Ga | PTB 00 ATEX 2048 X | 
| Equipment protection level Gb | PTB 00 ATEX 2048 X | 
| Equipment protection level Da | PTB 00 ATEX 2048 X | 
| UL approval |  | 
| Ordinary Location | E87056 | 
| Hazardous Location | E501628 | 
| Control drawing | 116-0452 | 
| CCC approval |  | 
| Hazardous Location | 2020322315002255 | 
| NEPSI approval |  | 
| NEPSI certificate | GYJ16.1393X | 
| TIIS approval | on request | 
| ANZEx | 18.3018X | 
| KCC approval |  | 
| Hazardous Location | 09-AV4BO-0226 | 
| Marine approval | DNVGL TAA00001A5 | 
| Ambient conditions | 
| Ambient temperature | -25 … 100 °C (-13 … 212 °F) | 
| Storage temperature | -40 … 100 °C (-40 … 212 °F) | 
| Mechanical specifications | 
| Connection type | Connector plug | 
| Housing material | Stainless steel 1.4305 / AISI 303 | 
| Sensing face | PBT | 
| Degree of protection | IP66 / IP67 | 
| Connector |  | 
| Threading | M12 x 1 | 
| Number of pins | 4 | 
| General information | 
| Use in the hazardous area | see instruction manuals |